IS 113601985AI Search Enabled✦ AI Generated

Specification for smoke detectors for use in an automatic electrical fire alarm system
1985 Edition

The IS 11360:1985 standard outlines the design, performance benchmarks, and testing procedures for optical and ionization smoke detectors intended for indoor automatic electrical fire alarm systems. It guarantees that these detectors function dependably under diverse environmental factors such as varying temperatures, humidity, vibrations, and dust exposure. This specification is crucial for manufacturers, system integrators, and fire safety professionals to ensure detector reliability and adherence to Indian fire safety norms.

9Sections
142Clauses Indexed
AI Search Ready
1985Edition
Fire FightingCategory
Alternative search terms: specification-for-smoke-detectors-in-automatic-fire-alarm-systems-1985 PDF, specification-for-smoke-detectors-in-automatic-fire-alarm-systems-1985 pdf free download, specification-for-smoke-detectors-in-automatic-fire-alarm-systems-1985 free download pdf, specification-for-smoke-detectors-in-automatic-fire-alarm-systems-1985 PDF, specification-for-smoke-detectors-in-automatic-fire-alarm-systems-1985 PDF, specification-for-smoke-detectors-in-automatic-fire-alarm-systems-1985 1985 PDF, specification-for-smoke-detectors-in-automatic-fire-alarm-systems-1985:1985 PDF, specification-for-smoke-detectors-in-automatic-fire-alarm-systems-1985-1985 PDF, specification-for-smoke-detectors-in-automatic-fire-alarm-systems-1985 (1985) PDF, specification-for-smoke-detectors-in-automatic-fire-alarm-systems-1985 1985 edition PDF, specification-for-smoke-detectors-in-automatic-fire-alarm-systems-1985 edition 1985 PDF

What This Standard Covers

The IS 11360:1985 standard outlines the design, performance benchmarks, and testing procedures for optical and ionization smoke detectors intended for indoor automatic electrical fire alarm systems. It guarantees that these detectors function dependably under diverse environmental factors such as varying temperatures, humidity, vibrations, and dust exposure. This specification is crucial for manufacturers, system integrators, and fire safety professionals to ensure detector reliability and adherence to Indian fire safety norms.

Who Uses This Standard

  • Fire protection engineers
  • Electrical system engineers
  • Producers of smoke detection devices
  • Designers of fire alarm systems
  • Building safety auditors
  • Installation service providers
  • Quality control specialists

Key Topics Covered

Fundamental construction specifications
Types of smoke detectors: optical and ionization
Performance standards and testing methodologies
Testing under environmental stresses: temperature, moisture, dust, corrosion
Electrical properties and voltage variation handling
Mechanical durability and vibration resistance
Alarm signaling and indication protocols
Consistency and reproducibility of detector output
Endurance and power interruption evaluations
Fire simulation tests with various fire sources
Impact of ambient air movement and lighting
Requirements for labeling and marking

Table of Contents

1Scope and Key Specifications

Overview of Scope in IS 11360

  • Establishes standards for smoke detectors and their measurement tools in fire detection.
  • Facilitates selection of standardized devices by users and ensures manufacturers produce uniform detector units.
  • Includes specifications for light sources, smoke production, and measurement techniques.

Essential Specifications

  • Light Source: Tungsten filament automotive lamp operated at approximately 50% of rated voltage to maintain consistent light intensity.
  • Smoke Generation: Smoke produced by smouldering Whatman No. 2 filter papers, weighing between 80 and 110 g/m², placed on a heated plate.
  • Smoke optical density increment rate limited to 0.2 dB/m/min with a maximum of 1.5 dB/m.
  • Smoke Measurement Instruments: Instruments must be stable, with output proportional to smoke concentration, utilizing ionization or scattering chambers as specified.

Important Formula for Optical Smoke Density

[ \text{Optical Density (dB/m)} = \frac{10}{L} \log_{10} \frac{I_0}{I_e} ]

where (L) is the light path length in meters, (I_0) the light intensity without smoke, and (I_e) the intensity with smoke.


Summary of SI Units Used

QuantityUnitSymbol
Lengthmeterm
Masskilogramkg
Timeseconds
Electric currentampereA
Thermodynamic temp.kelvinK
Luminous intensitycandelacd
Plane angleradianrad
Solid anglesteradiansr

This scope ensures uniformity in manufacturing and testing procedures for smoke detection devices.

2Terminology and Definitions

Essential Definitions and Specifications in IS 11360

Definitions (Clause 2)

  • Standardized terminology for components and concepts related to smoke detectors and fire alarm systems.

Light Source Details (Clause 3.1)

  • Utilizes tungsten filament automotive lamps.
  • Operated at roughly half the rated voltage to ensure a uniform light beam.
  • Photocell output corresponds proportionally to smoke concentration.

SI Units Reference

Physical QuantityUnitSymbolNotes
Lengthmeterm
Masskilogramkg
Timeseconds
Electric currentampereA
Thermodynamic temp.kelvinK
Luminous intensitycandelacd
ForcenewtonN1 N = 1 kg·m/s²
EnergyjouleJ1 J = 1 N·m
PowerwattW1 W = 1 J/s
Pressure, stresspascalPa1 Pa = 1 N/m²

Smoke Generation Method (Clause 1.5)

  • Employed circular hot plate with Whatman No. 2 filter papers of 80-110 g/m².
  • Smoke generated by smouldering the filter papers.
  • Optical density increase rate restricted to 0.2 dB/m/min, with a maximum of 1.5 dB/m.

Optical Density Calculation (Appendix D)

[ \text{OD (dB/m)} = \frac{10}{L} \log_{10} \left(\frac{I_0}{I_e}\right) ]

where (I_0) is the light intensity without smoke, (I_e) with smoke, and (L) the path length.

Smoke Measurement Instruments (Appendix C)

  • Instruments must maintain stability and output proportionality.
  • Ionization or scattering meters are used depending on detector type.
3General Requirements for Smoke Detectors

Highlights of General Requirements (Clause 4.2) in IS 11360

  • Directional Dependence (4.1): Randomly select one detector from the batch for testing direction sensitivity.
  • Reproducibility and Sensitivity Consistency (4.2): Detectors must demonstrate repeatable and optimum sensitivity in tests.
  • Voltage Variation Handling (4.6): Devices should perform reliably within specified voltage fluctuations.
  • Insulation Resistance (4.7): Minimum insulation resistance levels to guarantee electrical safety.
  • Temperature Resistance: Tests at elevated (4.10) and reduced (4.11) temperatures to confirm detector function under thermal stress.
  • Full-Scale Fire Response (4.18): Detectors must respond appropriately to simulated full-scale fire scenarios.

Optical Density Formula (Appendix D)

[ \text{OD (dB/m)} = 10 \times \log_{10} \frac{I_0}{I_e} ]

  • (I_0): Intensity of light in absence of smoke
  • (I_e): Intensity of light in presence of smoke
  • Path length (l) in meters

Smoke Generation Details (Clause 1.5)

  • Employ Whatman No. 2 filter papers (80-110 g/m²)
  • Optical density increase rate limited to 0.2 dB/m/min
  • Maximum optical density maintained at or above 1.5 dB/m

SI Units Summary

QuantityUnitSymbol
Lengthmeterm
Electric currentampereA
TemperaturekelvinK
Optical densitydecibel/mdB/m

Flowchart Summary

flowchart LR
    A[Smoke Generation] --> B[Optical Density Meter]
    B --> C[Detector Performance Testing]
    C --> D{Test Types}
    D -->|Directional Dependence| E[Clause 4.1]
    D -->|Reproducibility| F[Clause 4.2]
    D -->|Voltage Variation| G[Clause 4.6]
    D -->|Temperature Tests| H[Clauses 4.10,4.11]
    D -->|Full Scale Fires| I[Clause 4.18]

This framework ensures detectors meet performance, stability, and environmental durability requirements.

4Performance Testing and Compliance Criteria

Performance Evaluation and Compliance Tests in IS 11360

Overview of Tests (Clause 4.0 & Appendix A)

Test NameClauseSample DetectorsNotes
General Requirements3AllApplicable to entire detector batch
Directional Dependence4.1One detectorEvaluates sensitivity relative to orientation
Reproducibility & Sensitivity4.2MultipleConfirms consistent detector output
Stability4.3SelectedAssesses long-term sensor behavior
Repeatability4.4SelectedChecks consistency across repeated trials
Endurance4.5SelectedMeasures durability under extended use
Voltage Variation4.6SelectedTests operation under fluctuating voltage
Insulation Resistance4.7SelectedVerifies electrical insulation quality
Environmental Conditioning4.8-4.17SelectedIncludes humidity, temperature, vibration, shock, corrosion, dust tests
Full Scale Fire Tests4.18SelectedValidates response to actual fire smoke

Example: Humidity Exposure Test (Clause 4.12)

ParameterSpecification
Temperature30 ± 2 °C
Relative Humidity85 ± 5 %
Duration7 consecutive days

Detector number 7 is subjected to this controlled climatic chamber environment, connected to control and monitoring apparatus.


Additional Specification (Clause 3.8)

  • Smoke entry apertures must be positioned at least 30 mm below a smooth and flat ceiling surface.

Testing Process Flow

flowchart TD
    A[Start: Detector Sample] --> B[General Requirement Tests]
    B --> C{Directional Dependence Required?}
    C -->|Yes| D[Directional Test]
    D --> E[Reproducibility & Sensitivity Assessment]
    C -->|No| E
    E --> F[Environmental Conditioning Tests]
    F --> G[Electrical Integrity Tests]
    G --> H[Full Scale Fire Simulation]

This sequence ensures thorough verification of detector sensitivity, durability, and operational robustness.

5Marking and Identification Protocols

Marking and Identification Requirements in IS 11360

Marking Guidelines (Clause 5.1.1)

  • Devices may bear the ISI Certification Mark, signifying compliance with Indian standards.
  • The ISI mark placement is governed by the Indian Standards Institution (Certification Marks) Act and ensures ongoing inspection and quality control.

Detector Numbering and Test Identification (Appendix A, Clause 4.0)

  • Each smoke detector is assigned a unique identifier corresponding to specific performance tests it has undergone.
  • Tests include directional dependence, reproducibility, stability, repeatability, endurance, voltage variation, insulation resistance, vibration, shock, temperature, humidity, corrosion, ambient light, transient conditions, dust exposure, and full-scale fire simulation.

Optical Density Formula (Appendix D)

[ \text{OD (dB/m)} = 10 \log_{10} \frac{I_0}{I_e} ] where (I_0) is the intensity without smoke, (I_e) with smoke, and (d) the path length in meters.

Smoke Measurement Instrument Requirements (Appendices C & E)

  • Instruments must be stable and provide linear output proportional to smoke concentration.
  • Different types of meters are employed depending on detector technology (ionization, scattering, or light obscuration).

Summary Table: Marking and Identification Elements

AspectSpecification/Note
ISI Certification MarkOptional, regulated by certification act
Detector NumberingLinked to performed test types
Optical Density (OD)Calculated as per formula above
Smoke GenerationUsing Whatman No. 2 filter papers (80-110 g/m²)
Smoke MetersMust be stable and linear with proportional output

flowchart LR
    A[Detector Unit] --> B[Marking with Test Numbers and ISI Mark]

This ensures traceability and quality assurance throughout the detector lifecycle.

6Instructions and Technical Details

Summary of Instructions and Technical Specifications in IS 11360

Key Testing and Performance Requirements (Clause 4.0 & Appendix A)

  • Tests cover aspects such as:
    • Directional dependence (4.1)
    • Reproducibility and optimal sensitivity (4.2)
    • Stability (4.3)
    • Repeatability (4.4)
    • Endurance (4.5)
    • Variations in supply voltage (4.6)
    • Electrical insulation resistance (4.7)
    • Environmental exposures including vibration (4.8), shock (4.9), high and low temperature (4.10, 4.11), humidity (4.12), corrosion (4.14), and dust (4.17).

Detector Marking and Sampling

  • Specific detectors such as M2 and M14 are chosen for repeatability and sensitivity tests to ensure consistent quality.

Technical Specifications Highlights

  • Light Source (Clause 3.1): Tungsten filament automotive lamp operated at roughly 50% rated voltage for consistent light output.
  • Reset Time Variation (r.t.v.): Ratio of maximum to minimum r.t.v. should not exceed 1.6; average r.t.v. calculated from key detectors.

Reference SI Units

QuantityUnitSymbolNotes
ForcenewtonN1 N = 1 kg·m/s²
EnergyjouleJ1 J = 1 N·m
PowerwattW1 W = 1 J/s
Pressure, stresspascalPa1 Pa = 1 N/m²
Electric currentampereA
Thermodynamic temp.kelvinK
Luminous intensitycandelacd

Summary Table of Key Tests

Test NameClauseDetector SampleNotes
Directional Dependence4.1Selected

This section lays out comprehensive instructions to ensure detector quality and operational reliability.

Appendix ASchedule of Tests

Overview of Test Schedule as per IS 11360

Sample Size and Scope:

  • A batch of 15 detectors randomly chosen from a production lot of at least 200 units.
  • The tests are designed for batches producing up to 10,000 detectors.
  • Each detector is assigned a number from 1 to 15 for identification.

Summary of Test Schedule (Appendix A)

Test DescriptionClauseDetector Numbers Involved
General Requirements3All (1 to 15)
Directional Dependence4.114, 15, 1
Reproducibility & Sensitivity4.22 to 15 (excluding 1)
Stability4.33
Repeatability4.42 (M2), 14 (M14)
Endurance4.53, 13, 14
Supply Voltage Variation4.61
Insulation Resistance4.79
Vibration4.84
Shock4.95
High Temperature4.101
Low Temperature4.1115
Humidity4.127
Air Movement4.1315
Corrosion4.149
Ambient Light4.1510
Transients4.1611
Dust4.1713
Full Scale Fire Tests4.181, 3, 14, 15

Humidity Test Parameters (Clause 4.12)

ParameterValue
Temperature30 ± 2 °C
Relative Humidity85 ± 5 %
Duration7 Days (continuous)

Detector number 7 undergoes testing inside a climatic chamber under these conditions and is connected to control and indicating systems.

Appendix BMeasurement of Relative Transmittance Value (r.t.v.)

Procedure for Measuring Relative Transmittance Value (r.t.v.) According to IS 11360 Appendix B


Test Environment and Setup

  • Wind Tunnel Conditions (as per IS 9972-1981 Fig.6):
    • Airflow velocity maintained at 0.2 ± 0.05 m/s
    • Ambient air temperature maintained at 25 ± 5 °C
  • Detector Installation:
    • Positioned on the top horizontal section of the tunnel
    • Installed in the orientation found least favorable by directional dependence testing
  • Smoke Generation:
    • Conducted as per Appendix B-2 specifications
  • Measurement Protocol:
    • Detector powered and warmed up before testing
    • Smoke density measured at the moment the detector triggers an alarm using an optical density meter placed close by
    • Recorded smoke density at alarm is the r.t.v.

Acceptance Criteria and Limits

ParameterThreshold/Value
Minimum acceptable r.t.v.≥ 0.05 dB/m
Maximum ratio of highest to lowest r.t.v.≤ 1.6
Ratio after corrosion exposureShould not exceed factor of 1.6
  • Average r.t.v. values computed from detectors M2 and M14 test results.

Formula for r.t.v.

[ \text{r.t.v.} = \text{Smoke Density at Alarm Trigger (dB/m)} ]


Test Flow Diagram

flowchart LR
    A[Wind Tunnel Setup] --> B[Mount Detector in Least Favorable Position]
    B --> C[Generate Smoke]
    C --> D[Detector Alarm Activation]
    D --> E[Measure Smoke Density Using Optical Meter]
    E --> F[Record r.t.v.]

Note: Detectors must be reset immediately after each measurement to maintain consistency.

Appendix EOptical Density Meter Configuration

Details of Optical Density Meter as per IS 11360


Optical Density Calculation (Appendix D)

[ \text{OD (dB/m)} = 10 \times \log_{10} \frac{I_0}{I_e} ]

  • (I_0): Light intensity without smoke
  • (I_e): Light intensity with smoke
  • (l): Length of light path in meters

Components of Optical Density Meter (Appendix E & Clause 1.1)

ComponentSpecification
Light Source (E-3.1)Tungsten filament automotive lamp, operated at half rated voltage for stable intensity
Sensor (E-2.1)Photovoltaic selenium barrier layer cell, 25 mm diameter, spectral response 350-660 nm, peak sensitivity 530-580 nm
Lens Assembly (Clause 1.1)Includes condensing lens (L1) and collimating lenses (L2, L3) for shaping the beam
Heating Section (Clause 1.5)Hot plate with Whatman No. 2 filter papers (80-110 g/m²), smoke generated by smouldering papers

Smoke Generation and Measurement (Clause 1.5)

  • Bundle diameter must not exceed heater plate diameter
  • Smoke generation rate controlled to increase optical density at no more than 0.2 dB/m per minute
  • Maximum optical density maintained at or above 1.5 dB/m
  • Consistent use of same filter paper type across tests

Functional Flow Schematic

flowchart LR
    A[Light Source: Tungsten Lamp] --> B[Condensing Lens (L1)]
    B --> C[Smoke Chamber with Filter Papers]
    C --> D[Collimating Lenses (L2 & L3)]
    D --> E[Photocell Sensor (Selenium Cell)]
    E --> F[Output: Optical Density Reading]

Additional Notes

  • The meter output is directly proportional to smoke concentration.
  • Sensor stability and linearity are critical for accurate measurement.
  • The measurement principle is based on light obscuration.

This design provides dependable and reproducible optical density measurements in accordance with IS 11360.

Popular Questions About IS 11360

?Which types of smoke detectors are encompassed by IS 11360?

IS 11360 (1985) delineates requirements for smoke detectors utilized in automatic electrical fire alarm systems, specifically focusing on two main categories:

  • Photoelectric (Optical) Smoke Detectors: These detect smoke by sensing light scattered by smoke particles.
  • Ionization Smoke Detectors: These detect smoke by monitoring changes in ion flow caused by smoke particles.

The standard defines the construction, performance, and testing criteria for these types, ensuring they provide dependable early fire detection and are suited for use in building fire alarm systems.

Loading diagram...
?In what ways does IS 11360 assure detector performance across diverse environmental conditions?

IS 11360 enforces reliable detector operation under varying environmental conditions through comprehensive conditioning and testing procedures such as:

  • Humidity Testing (Clause 4.12): Detectors are exposed to 30 ± 2 °C temperature and 85 ± 5% relative humidity inside a climatic chamber for a continuous period of 7 days to verify performance stability.

  • Low Temperature Testing (Clause 4.11): Detectors are cooled to 0 ± 1 °C at a rate not exceeding 1 °C per minute, held for one hour, followed by a 3-hour stabilization period and then returned to room temperature for 5 to 6 hours before performance evaluation.

These procedures simulate real environmental stresses to ensure that smoke detectors maintain sensitivity and reliability under high humidity and low temperature conditions.

Loading diagram...
?What are the main fire tests specified for smoke detectors in IS 11360?

IS 11360 mandates specific fire response tests for smoke detectors to verify sensitivity and reliability:

  • Tested Detectors: Detectors numbered 1, 2, 14, and 15 from a sample batch.
  • Test Fires: Four distinct types of test fires ignited once centrally on the test room floor (Clauses 4.18.1 to 4.18.4).
  • Setup: Detectors and optical density meters are mounted on the ceiling with a minimum 4-meter clearance from combustible surfaces.
  • Procedure: The room is cleared of smoke before each test; detectors are energized and functioning normally.
  • Data Collection: Optical density is recorded every 20 seconds post ignition until reaching or exceeding 2.0 dB/m or until values stabilize.
  • Analysis: Temporal mean optical density over 60 seconds is computed and plotted to produce a profile curve characterizing the fire.

This methodology ensures detectors reliably detect and respond to realistic fire smoke conditions.

Loading diagram...
?According to IS 11360, what markings must smoke detectors carry?

Per IS 11360 Clause 5.1, smoke detectors are required to bear the following mandatory markings:

  • Detector type designation.
  • Power supply specifications: including minimum and maximum voltage limits.
  • Date of manufacture.
  • Maximum interval between servicing or inspections.
  • Manufacturer's name.

For ionization-type detectors specifically, additional mandatory markings include:

  • Notification of radioactive content.
  • Details of the type and strength of the radioactive source used.

Optionally, devices may also display the ISI Certification Mark indicating compliance with Indian Standards and quality oversight.


Marking ElementRequirement
Detector TypeMandatory
Power Supply LimitsMandatory
Date of ManufactureMandatory
Maximum Service/Inspection IntervalMandatory
Manufacturer NameMandatory
Radioactivity Information (Ionization Detectors)Mandatory
ISI Certification MarkOptional

These markings ensure traceability, safety, and regulatory compliance.

?What procedures are used to assess the stability and repeatability of smoke detector responses under IS 11360?

IS 11360 evaluates stability and repeatability through the following tests:

  • Repeatability (Clause 4.4): Detectors numbered 2 and 14 are tested by measuring their relative transmittance value (r.t.v.) six times at 30-minute intervals. Before each measurement, the test environment and detector must be free of smoke to ensure accuracy.

  • Stability (Clause 4.3): Detector number 3 is continuously energized, with the first r.t.v. recorded after one day. After resetting and power cycling, a second r.t.v. measurement is taken 10 days later. The detector must not emit false alarms except within the first 2 minutes after energizing. The ratio of the two r.t.v. values should not exceed 1.6, and the lowest r.t.v. must be at least 0.05 dB/m.

  • Reproducibility (Clause 4.2): All detectors (numbers 1 to 15) are tested in their least favorable orientation. Detectors are ranked by r.t.v. from lowest to highest, and the ratio between highest and lowest r.t.v. must not exceed 1.6, with the minimum r.t.v. no less than 0.05 dB/m. No electrical or mechanical faults should be observed, and r.t.v. values must remain consistent within the specified factor.


Test ParameterDetector Nos.Measurement FrequencyAcceptance Criteria
Repeatability2, 14Six measurements, 30-min apartConsistent r.t.v. values
Stability3After 1 day and 10 daysRatio ≤ 1.6, no false alarms except initial 2 min, r.t.v. ≥ 0.05 dB/m
Reproducibility1 to 15Single measurementRatio highest/lowest ≤ 1.6, r.t.v. ≥ 0.05 dB/m

This process guarantees reliable and consistent detector performance over time and multiple uses.

Need Detailed Clause Answers?

Ask AI about any clause, requirement, or provision in IS 11360. Get instant, clause-cited responses powered by our indexed library.

Free tier includes 150 queries (50 AI + 100 Reference) · No credit card required