IS 8758 Part b1993AI Search Enabled✦ AI Generated

Recommendations for fire precautionary measures in the construction of temporary structures and pandals (BI-LINGUAL)

IS 8758 Part B (1993) provides comprehensive recommendations for fire precautionary measures in the construction, maintenance, and use of temporary structures and pandals used for public and private outdoor assemblies in India. It covers material selection, structural design, electrical safety, fire fighting arrangements, and evacuation protocols to ensure minimum fire resistance and safe occupancy. This standard is essential for engineers, architects, and safety officials involved in planning and managing temporary event structures to mitigate fire risks effectively.

12Sections
114Clauses Indexed
AI Search Ready
1993Edition
Fire SafetyCategory
Alternative search terms: IS 8758 Part b PDF, IS 8758 Part b pdf free download, IS 8758 Part b free download pdf, IS8758Partb PDF, IS-8758-Part-b PDF, IS 8758 Part b 1993 PDF, IS 8758 Part b:1993 PDF, IS 8758 Part b-1993 PDF, IS 8758 Part b (1993) PDF, IS 8758 Part b 1993 edition PDF, IS 8758 Part b edition 1993 PDF

What This Standard Covers

IS 8758 Part B (1993) provides comprehensive recommendations for fire precautionary measures in the construction, maintenance, and use of temporary structures and pandals used for public and private outdoor assemblies in India. It covers material selection, structural design, electrical safety, fire fighting arrangements, and evacuation protocols to ensure minimum fire resistance and safe occupancy. This standard is essential for engineers, architects, and safety officials involved in planning and managing temporary event structures to mitigate fire risks effectively.

Who Uses This Standard

  • Fire Safety Engineers
  • Structural Engineers
  • Event Organizers
  • Electrical Engineers
  • Municipal Licensing Authorities
  • Safety Inspectors
  • Construction Contractors

Key Topics Covered

Fire resistance requirements for materials and structures
Use of fire retardant treatments on fabrics and decorations
Structural stability and wind resistance
Layout and capacity calculations for seating and standing areas
Design and dimensions of exits and gangways
Electrical installation safety and restrictions
Prohibition of open flames and fireworks
Fire fighting equipment specifications and placement
Water supply requirements for fire fighting
Emergency evacuation planning and management
Licensing and inspection protocols
Safe distances from hazards and adjacent structures

Table of Contents

1Scope

IS 8758 Part B – Scope Summary

  • Scope (Clause 3.1):
    Covers materials, design, construction, and fabrication of fire-resistant structures/devices.

    • Must ensure minimum fire resistance of 10 minutes or the total evacuation time, whichever is greater.
  • Key Specification:
    Fire resistance time ≥ max(10 minutes, total evacuation time)

ParameterRequirement
Fire resistance durationMinimum 10 minutes or evacuation time
Materials & designMust comply with fire resistance criteria
  • Purpose:
    To ensure safety by allowing sufficient time for evacuation during fire incidents.

Practical Note:

  • Design fire resistance based on expected evacuation time for the specific building/use.
  • Use fire-resistant materials and construction methods as per IS 8758 guidelines.
flowchart TD
    A[Start: Design Fire-Resistant Structure] --> B{Determine Evacuation Time}
    B -->|Evacuation Time < 10 mins| C[Set Fire Resistance = 10 mins]
    B -->|Evacuation Time ≥ 10 mins| D[Set Fire Resistance = Evacuation Time]
    C --> E[Select Materials & Design Accordingly]
    D --> E
    E --> F[Construct & Fabricate as per IS 8758]
    F --> G[Achieve Fire Resistance Compliance]

For detailed design and material specifications, refer to full IS 8758 Part B text and related fire safety codes.

2Referenced Standards

IS 8758 Part B: Referenced Standards - Key Points

Referenced Standards are essential adjuncts to IS 8758 Part B, ensuring comprehensive fire safety and structural integrity.


Key Referenced IS Codes (Clause 2.1)

  • IS 1646:1982 — Code of Practice for Fire Safety of Buildings (General): Electrical Installations

General Requirements (Clause 3.1)

  • Materials, design, fabrication must ensure minimum fire resistance of 10 minutes or total evacuation time, whichever is greater.

Important Notes:

  • The standards referenced provide guidelines on fire resistance, electrical safety, and construction practices.
  • Compliance with these referenced standards is mandatory for holistic fire safety in temporary structures and pandals.

Summary Table:

ClauseDescriptionKey Requirement
2.1Referenced Indian StandardsIS 1646:1982 (Fire safety in electrical installations)
3.1Fire Resistance RequirementsMin. 10 minutes or evacuation time

For detailed fire safety design, refer to IS 1646 for electrical installations and related fire precautionary measures.

flowchart LR
    A[IS 8758 Part B] --> B[Fire Resistance: Min 10 min]
    A --> C[Referenced Standards]
    C --> D[IS 1646:1982 - Electrical Fire Safety]
    B --> E[Material & Design Compliance]
    D --> E

Contact BIS or consult the full standards for detailed tables and formulas on fire resistance ratings.

3General Requirements

IS 8758 Part B: General Requirements Summary

Key Specifications (Clause 3.1)

  • Minimum fire resistance: Structures/devices must resist fire for at least 10 minutes or the total evacuation time, whichever is greater.
  • Applies to materials, design, construction, fabrication within the scope.

Relevant Standards (Clause 2.1)

  • Refer to IS 1646:1982 for electrical installations fire safety guidelines.

Fire Precautionary Measures (Clause 3)

  • Temporary structures and pandals must follow fire precautionary recommendations to ensure safety during occupancy.

Fire Resistance Time Table (Clause 3.2 - Example format)

Location/TypeMinimum Fire Resistance (minutes)
Exit routes10
Assembly areas15
Electrical rooms30

(Note: Exact values to be confirmed from full Table 4 in Clause 3.2)


Summary Diagram of Fire Resistance Requirement

flowchart LR
    A[Design & Materials] --> B{Fire Resistance Time}
    B -->|≥ 10 min| C[Meets IS 8758 Part B]
    B -->|< 10 min| D[Revise Design]
    C --> E[Safe for Evacuation]

Use IS 1646 and IS 8758 together for comprehensive fire safety design in temporary structures.

4Location and Safety Distances

IS 8758 Part B: Location and Safety Distances - Key Points

1. Safety Distance Requirements (Clause 4.3)

  • Minimum safety distance of 15 m must be maintained between temporary structures and:
    • Furnace
    • Railway line
    • Electrical sub-station
    • Chimney
    • High tension wires or similar hazards

2. Clearing Area Around Temporary Structures (Clause 9.1)

  • Ground enclosed by the structure plus an additional 4.5 m outside must be cleared of:
    • Combustible materials
    • Vegetation
    • Obstructions to movement

3. Access and Capacity (Clause 6.2)

  • Number of persons admitted must not exceed the capacity calculated as per Clause 6.1 (usually based on floor area and exit widths).

4. Location Table (Clause 3.2)

  • Specifies permissible locations for temporary structures relative to hazards (refer IS 8758 Part B Table 4).

Summary Table

Hazard/FeatureMinimum Safety Distance (m)
Furnace15
Railway line15
Electrical sub-station15
Chimney15
High tension wires15
Clearing zone around structure4.5 outside perimeter

flowchart LR
    A[Temporary Structure] -->|15 m| B[Furnace/Railway/Electrical Sub-station/Chimney/HT Wire]
    A -->|4.5 m clearance| C[Combustible Material Free Zone]
    A --> D[Access & Exits per Capacity]

Ensure compliance with these distances to maintain safety and regulatory adherence.

5Means of Access

IS 8758 Part B: Means of Access - Key Points

1. Safety Distance (Clause 4.3)

  • Maintain minimum 15 m clearance from hazards like:
    • Furnace
    • Railway line
    • Electrical sub-station
    • Chimney
    • High tension wires

2. Access Specifications (Clause 5.1)

  • Gate clear opening: Minimum 5 m width
  • Archway height: Minimum 5 m from ground level
  • Ensures easy approach and emergency access

3. Capacity Control (Clause 6.2)

  • Number of persons allowed ≤ capacity calculated per Clause 6.1 (not detailed here, but typically based on area and occupant density)

4. Means of Escape (Clause 11.3)

  • Gangways, exits must be unobstructed
  • Fire safety equipment (buckets, extinguishers) must be visible and accessible

Summary Table

ParameterMinimum Dimension/Requirement
Safety distance from hazards15 m
Gate clear opening width5 m
Archway height5 m
Capacity controlAs per Clause 6.1 (area-based)
Escape routesUnobstructed, visible equipment

flowchart LR
    A[Temporary Structure] --> B[Maintain 15m Safety Distance]
    A --> C[Gate Opening ≥ 5m]
    A --> D[Archway Height ≥ 5m]
    A --> E[Capacity ≤ Clause 6.1]
    A --> F[Unobstructed Exits & Visible Fire Equipment]

This ensures safe, easy access and egress for temporary structures per IS 8758 Part B.

6Capacity and Occupancy

IS 8758 Part B: Capacity and Occupancy Key Points

Capacity Calculation (Clause 6.1)

  • Capacity = Number of fixed seats + allowance for standing/movable seats.
  • Standing allowance: 1 person per 0.50 m² of floor area designated for standing/movable seats.
  • Bench seating: 450 mm length along an undivided bench/platform = 1 seat.
  • Excluded areas: Ramps, aisles, passageways, and circulation spaces do not count towards capacity or standing space.

Occupancy Limit (Clause 6.2)

  • Number of persons admitted ≤ Computed capacity (from 6.1).

Exits (Clause 7)

  • Minimum exit width: 1.5 m per exit.
  • If standard provisions (7.1) are not met, provide adequate unrestricted exits based on capacity (7.3 to 7.9).

Summary Table for Capacity

ParameterValue/Formula
Standing space per person0.50 m²
Bench seat length per person450 mm (0.45 m)
Minimum exit width1.5 m
Capacity formulaFixed seats + (Floor area for standing ÷ 0.5)

flowchart TD
    A[Floor Area] --> B{Designated for?}
    B -->|Fixed seats| C[Count seats]
    B -->|Standing/movable seats| D[Area ÷ 0.5 m² per person]
    C --> E[Sum seats]
    D --> E
    E --> F[Total Capacity]
    F --> G[Check Occupancy ≤ Capacity]
    G --> H[Provide exits ≥ 1.5 m width]

This ensures safe, code-compliant assembly occupancy and egress design.

7Enclosure and Exits

IS 8758 Part B: Enclosure and Exits Key Points

1. Occupancy Limit (Clause 6.2)

  • Maximum persons allowed = Capacity computed as per Clause 6.1 (based on area and usage).

2. Exits Requirements (Clause 7.2 - 7.9)

  • If Clause 7.1 provisions can't be met, provide adequate and unrestricted exits based on assembly capacity.

3. Minimum Number and Width of Exits (Clause 7.3 & 1.5)

  • Minimum 2 exits for any temporary structure.
  • Each exit width ≥ 2.5 m (Clause 7.3).
  • Minimum width of each exit should not be less than 1.5 m (Clause 1.5).

Summary Table for Exits:

ParameterRequirement
Number of exitsMinimum 2
Width of each exit≥ 2.5 m (preferred), ≥ 1.5 m minimum
Location of exitsAt extremities, separately located

Diagram: Exit Layout for Temporary Structure

graph LR
    A[Temporary Structure] --> B(Exit 1: ≥ 2.5 m width)
    A --> C(Exit 2: ≥ 2.5 m width)
    B --- C

Note: Ensure exits are unrestricted, well-marked, and located at opposite ends for safe evacuation.

8Electrical Arrangements

IS 8758 Part B — Electrical Arrangements Key Points

Relevant Clauses Summary:

  • Clause 8.1:

    • Temporary lighting must be installed by a licensed electrical engineer.
    • Load per circuit, insulation tests, and installation must comply with IS 1646:1982 (Fire safety code for electrical installations).
  • Clause 8.2:

    • Electrical wiring must use PVC sheathed conductors or vulcanized rubber cables of tough rubber.
    • All joints must be made with porcelain insulated connectors.
    • Twisted and taped joints are prohibited.

Important Specifications:

ParameterSpecification
Minimum clearance (seating)55 cm (general), 30 cm (self-folding seats)
Wiring typePVC sheathed or vulcanized rubber cables
JointsPorcelain insulated connectors only
Installation standardIS 1646:1982

Notes:

  • Refer to IS 1646:1982 for detailed electrical load calculations, circuit design, and fire safety practices.
  • Ensure all wiring and joints follow the specified standards to prevent fire hazards.
flowchart TD
    A[Temporary Lighting Installation] --> B[Licensed Electrical Engineer]
    B --> C[Load per Circuit & Insulation Test]
    C --> D[Compliance with IS 1646:1982]
    D --> E[Use PVC Sheathed or Vulcanized Rubber Cables]
    E --> F[Joints with Porcelain Insulated Connectors]
    F --> G[No Twisted & Taped Joints Allowed]

This ensures safe, fire-resistant electrical arrangements in temporary pandal structures.

9Fire Protection Measures

Fire Protection Measures as per IS 8758 Part B


1. Fire Fighting Equipment (Clause 10.2)

  • Fire Buckets:
    • Minimum 2 buckets per 50 m² floor area
  • Water Extinguishers:
    • Minimum 1 water-type extinguisher (9 litres) per 100 m² floor area
  • Electrical Fire Extinguishers:
    • For each switchgear, main meter, stage area: 1 CO₂ or BCF extinguisher of adequate size

2. Water Supply for Fire Fighting (Clause 10.1)

  • Minimum water supply:
    • 0.75 litres/m² of floor area
  • Storage:
    • Stored in buckets/drums
    • Half quantity inside the structure, half outside nearby
    • Always readily available for immediate use

3. Fire Resistance of Materials (Clause 3.1)

  • Minimum fire resistance of materials, design, and construction:
    • At least 10 minutes or total evacuation time, whichever is greater

4. Prohibited Items (Clause 8.5)

  • No halogen lamps allowed inside temporary structures/pandals

Summary Table:

ItemRequirement
Fire Buckets2 per 50 m² floor area
Water Extinguishers1 (9 L) per 100 m² floor area
CO₂/BCF Extinguishers1 per electrical installation area
Water Supply0.75 L/m² floor area
Fire Resistance of Materials≥ 10 minutes or evacuation time
Halogen LampsNot allowed inside structures

flowchart LR
    A[Temporary Structure] --> B[Fire Buckets (2 per 50 m²)]
    A --> C[Water Extinguishers (1 per 100 m²)]
    A --> D[Water Supply (0.75 L/m²)]
    A --> E[Electrical Fire Extinguishers (CO₂/BCF)]
    A --> F[Materials Fire Resistance ≥ 10 mins]
    A --> G[No Halogen Lamps Allowed]

This ensures compliance with

10Fire Fighting Arrangements

IS 8758 Part B – Fire Fighting Arrangements: Key Points

1. Water Supply for Fire Fighting (Clause 10.1)

  • Minimum water supply: 0.75 liters/m² of floor area.
  • Water stored in buckets/drums, half inside and half outside the structure.
  • Buckets/receptacles must be clearly marked and readily accessible.

2. Fire Buckets and Extinguishers (Clause 10.2)

ItemQuantity per Floor Area
Fire buckets2 buckets per 50 m²
Water-type extinguisher (9L)1 extinguisher per 100 m²
CO₂ or BCF extinguisher1 for each switchgear, main meter, and stage area (for electrical protection)

3. Kitchen Area (Clause 9.6)

  • Kitchen must be segregated from main structure.
  • Preferably constructed with GI sheets to reduce fire risk.

4. Additional Provisions (Clause 10.3.1)

  • Local authority may require standby fire service.
  • Adequate water supply must be ensured for such services.

Summary Table

AspectRequirement
Water supply0.75 l/m²
Fire buckets2 per 50 m²
Water extinguisher9L, 1 per 100 m²
CO₂/BCF extinguisher1 per switchgear/main meter/stage
Kitchen segregationSeparate, GI sheets preferred
Standby fire serviceAs per local authority
flowchart LR
    A[Temporary Structure] --> B[Water Supply: 0.75 l/m²]
    B --> C[Buckets: 2 per 50 m²]
    B --> D[Water Extinguisher: 9L per 100 m²]
    A --> E[Electrical Installations]
    E --> F[CO₂/BCF Extinguisher per switchgear/meter/stage]
    A --> G[Kitchen Area]
    G --> H[Segregated, GI Sheets]
    A
11Maintenance and Inspection

IS 8758 Part B: Maintenance and Inspection Key Points

Maintenance (Clause 11.1)

  • Temporary structures must be kept safe and sanitary.
  • All devices and safeguards required by the standard must be maintained in good working condition.

Inspection (Clause 11.2)

  • Periodic inspection of temporary structures is mandatory.
  • Any deterioration or defects must be reported immediately to the authority for corrective action.

Fire Resistance (Clause 3.1)

  • Materials and construction must ensure a minimum fire resistance of 10 minutes or the total evacuation time, whichever is greater.

Practical Guidelines for Maintenance & Inspection

ActivityFrequencyAction Required
Visual InspectionDaily/WeeklyCheck for visible defects/damage
Functional Testing of DevicesMonthlyEnsure all safety devices operate
Structural Integrity CheckQuarterly/After EventCheck for corrosion, cracks, etc.
Fire Resistance VerificationAnnuallyConfirm compliance with fire rating

Summary Formula for Fire Resistance Time

[ t_{fire} \geq \max(10 \text{ minutes}, t_{evacuation}) ]

Where:

  • (t_{fire}) = Required fire resistance time
  • (t_{evacuation}) = Total evacuation time for the structure

flowchart TD
    A[Temporary Structure] --> B[Periodic Inspection]
    B --> C{Defects Found?}
    C -- Yes --> D[Report to Authority]
    C -- No --> E[Continue Operation]
    D --> F[Remedial Action]
    F --> E
    E --> G[Maintain Fire Resistance ≥ 10 min]

Note: Always refer to the latest IS 8758 Part B for detailed inspection checklists and maintenance procedures.

Annex ACommittee Composition

Committee Composition - IS 8758 Part b

From Annex A (Foreword):

  • The Committee responsible for IS 8758 Part b includes experts from:
    • Fire Safety Sectional Committee, CED 36
    • Tariff Advisory Committees (Bombay, Madras)
    • Institution of Engineers (India)
    • Ministry of Defence (DR & DO, Engineer-in-Chief's Branch)
    • Municipal Corporations (Bombay, Delhi)
    • Central Public Works Department
    • Various Engineering and Fire Safety organizations (Tata Consulting Engineers, Lloyds Institution, Mather and Platt Ltd, Hindustan Construction Co Ltd, etc.)
    • Representatives from Central Electricity Authority, Ministry of Petroleum and Natural Gas, National Thermal Power Corporation, and others.
    • Director General, BIS (Ex-officio Member)

Key Points:

  • The committee comprises multidisciplinary experts from government, industry, and research institutions.
  • Members have designated alternates ensuring continuity.
  • The committee oversees standards related to fire safety and outdoor assembly structures.

Relevant Specifications from Clauses:

  • Capacity Calculation (Clause 6.1): [ \text{Capacity} = \text{Number of fixed seats} + \frac{\text{Standing area (m}^2)}{0.5} ]

    • 450 mm bench length = 1 seat.
    • Exclude aisles, ramps, passageways from capacity area.
  • Admission Limit (Clause 6.2):

    • Persons admitted ≤ computed capacity.
  • Seating Clearance (Clause 7.9):

    • Minimum clearance between rows = 55 cm (30 cm for self-folding seats).

flowchart TD
    A[Committee Composition] --> B[Government Agencies]
    A --> C[Industry Experts]
    A --> D[Research Institutes]
    A --> E[Fire Safety Authorities]
    B --> F[Ministry of Defence, BIS, CEA]
    C --> G[Tata Consulting Engineers, Hindustan Construction]
    D --> H[CSIR, Metallurgical Engg. Consultants]
    E --> I[Institution of Fire Engineers, Fire Advisers]

Summary:
IS 8758 Part b’s committee is a multidisciplinary panel ensuring comprehensive fire safety standards, with clear capacity and seating guidelines for outdoor assembly structures.

Popular Questions About IS 8758 Part b

?What fire resistance rating must materials used in temporary structures meet?

According to IS 8758 Part b for temporary structures:

  • Minimum fire resistance: Materials must resist fire for at least 10 minutes or the total evacuation time, whichever is longer (Clause 3.1).
  • Material types: Includes straw, hay, grass, canvas, and similar non-permanent materials (Clause 1.1).
  • Fabric treatment: All fabrics/decorative cloth must be treated with fire retardant solutions or pre-treated to achieve Class I flame spread rating before use (Clause 3.6).

Summary:

RequirementDetail
Fire resistance durationMinimum 10 minutes or total evacuation time
Applicable materialsStraw, hay, grass, canvas, etc.
Fabric treatmentFire retardant solution or Class I flame spread

This ensures safe evacuation and reduces fire hazards in temporary public assembly structures.

Loading diagram...
?How should decorative fabrics be treated to reduce fire hazards?

According to IS 8758 Part B, decorative fabrics used in construction must be treated to reduce fire hazards as follows:

  • Pre-treatment: All fabrics and decorative cloths must be dipped in a fire retardant solution or treated with other suitable materials to achieve a Class I flame spread factor (Clause 3.6).

  • Fire retardant solution composition (Clause 3.2):

MaterialParts by Mass
Ammonium sulphate4
Ammonium carbonate2
Borax1
Boric acid1
Alum2
Water35
  • The fabric is dipped in this solution before use, ensuring enhanced fire resistance.

Additional precautions (Clause 8.5): Avoid using halogen lamps inside temporary structures to minimize ignition risk.

This treatment significantly lowers fabric combustibility, ensuring safer temporary structures and pandals.

?What are the minimum requirements for exits and gangways in pandals?

Minimum Requirements for Exits and Gangways in Pandals (IS 8758 Part B):

  • Exits:

    • At least two exits, each with a minimum width of 2.5 m.
    • Exits must be located at extremities and separately to ensure safe evacuation (Clause 7.3).
  • Gangways:

    • Side longitudinal gangways: Minimum width 1.2 m.
    • Central longitudinal gangway: Minimum width 1.5 m.
    • Seating arrangement:
      • Maximum 12 seats per row between gangways.
      • Seats tied in banks of at least 4 seats and secured to the ground (Clause 7.8).
  • Ceiling height: Minimum 3 m from ground level (Clause 3.4).

  • Safety clearance: Clear combustible materials within 4.5 m outside the structure (Clause 9.1).

Loading diagram...

This ensures safe, unobstructed evacuation and orderly seating in temporary pandal structures.

?What types and quantities of fire fighting equipment are required?

According to IS 8758 Part B, the minimum fire fighting equipment requirements for temporary structures are:

  • Fire Buckets:

    • 2 buckets per 50 m² of floor area (filled with water).
    • Water supply: minimum 0.75 liters/m², stored in buckets/drums. Half inside, half outside the structure.
  • Water-type Fire Extinguishers:

    • 1 extinguisher of 9 liters capacity per 100 m² floor area.
  • CO₂ or BCF Extinguishers:

    • 1 extinguisher for each electric installation such as switchgear, main meter, and stage area.
  • Location:

    • Equipment must be easily accessible in case of fire.
  • Additional Measures:

    • Local fire authorities may require more extinguishers or standby fire services.

Summary Table

Equipment TypeQuantityNotes
Fire Buckets2 per 50 m²Filled with water
Water Extinguishers1 per 100 m² (9 liters)
CO₂/BCF Extinguishers1 per electric installation (switchgear, etc.)For electrical fires
Water Supply0.75 liters/m² totalHalf inside, half outside

Loading diagram...

Ensure compliance with local fire authority for additional requirements.

?How should electrical installations be safely arranged in temporary structures?

Safe Arrangement of Electrical Installations in Temporary Structures (IS 8758 Part B)

  • Competent Installation: Electrical work must be done by a licensed electrical engineer.
  • Conformance: Load per circuit, insulation resistance tests, and overall installation must comply with IS 1646 (Code of Practice for Electrical Wiring Installations).
  • Material Consideration: Temporary structures use combustible materials (straw, canvas, etc.), so wiring must minimize fire risk.
  • Maintenance: All electrical devices and safeguards must be maintained in good working condition throughout use.
  • Load Management: Avoid overloading circuits; ensure proper distribution and protective devices (fuses, MCBs).
  • Insulation Testing: Conduct insulation resistance tests to detect faults before energizing circuits.

Key Reference:

ParameterRequirement
InstallerLicensed electrical engineer
Load per circuitAs per IS 1646
Insulation resistanceMinimum as per IS 1646 standards
MaintenanceContinuous, safe, and sanitary
Loading diagram...

Summary: Follow IS 1646 for wiring and load, ensure licensed installation, test insulation, and maintain devices for fire-safe electrical setups in temporary structures.