IS 6932 Part 11:1983 specifies the standardized method for determining the initial and final setting times of hydrated lime used in building construction. This standard is essential for quality control and ensures that hydrated lime meets performance criteria for setting behavior under controlled temperature and humidity conditions. It applies primarily to engineers, quality inspectors, and manufacturers involved in the production and testing of building limes.
Overview
IS 6932 Part 11:1983 specifies the standardized method for determining the initial and final setting times of hydrated lime used in building construction. This standard is essential for quality control and ensures that hydrated lime meets performance criteria for setting behavior under controlled temperature and humidity conditions. It applies primarily to engineers, quality inspectors, and manufacturers involved in the production and testing of building limes.
Audience
Contents
Structure
Scope:
This part covers the determination of the setting time of hydrated lime using the Vicat apparatus.
Apparatus:
Final Setting Time:
Environmental Conditions (Clause 3.1.2):
| Parameter | Value/Condition |
|---|---|
| Test temperature | 27 ± 2°C |
| Relative humidity | ≥ 90% |
| Apparatus needle | Needle with annular attachment (for final setting) |
| Final setting time criteria | Needle impression without annular attachment impression |
This ensures standardized and reliable measurement of hydrated lime setting time per IS 6932 Part 11.
IS 6932 (Part 11) - 1983: Determination of Setting Time of Hydrated Lime
| Apparatus Component | Description |
|---|---|
| Needle (C) | Standard penetration needle |
| Annular Attachment (F) | Ring-shaped attachment for final set |
flowchart TD
A[Vicat Apparatus] --> B[Needle (C)]
A --> C[Annular Attachment (F)]
B --> D{Impression on surface?}
D -- Yes --> E[Check annular attachment]
E --> F{Annular makes impression?}
F -- No --> G[Final Setting Time reached]
F -- Yes --> H[Not final set]
D -- No --> H
This method ensures consistent determination of hydrated lime's final setting time as per IS 6932 (Part 11).
1. Vicat Apparatus (IS: 5513-1976)
2. Environmental Conditions for Testing (Clause 3.1.2)
3. Determination of Final Setting Time (Clause 3.3)
| Needle Type | Use |
|---|---|
| Needle C | Initial setting time |
| Needle F | Final setting time (annular) |
flowchart LR
A[Lime Test Block] --> B[Vicat Apparatus]
B --> C{Needle Type}
C -->|C| D[Initial Setting Time]
C -->|F (Annular)| E[Final Setting Time]
E --> F{Impression on surface?}
F -->|Yes| G[Final set reached]
F -->|No| H[Not set yet]
Note: Use clean appliances and maintain specified temperature and humidity for accurate results.
IS 6932 Part 11: Preparation of Test Sample for Building Limes
| Needle Type | Purpose |
|---|---|
| Needle (C) | Initial setting time |
| Needle with annular (F) | Final setting time |
flowchart TD
A[Prepare Lime Putty] --> B[Maintain 27 ± 2°C & 90% RH]
B --> C[Use Clean Appliances]
C --> D[Fill Vicat Mould]
D --> E{Test Setting Time}
E -->|Initial| F[Needle (C)]
E -->|Final| G[Needle with Annular (F)]
G --> H[Final Setting Time Determined]
For detailed mixing ratios and workability, refer IS 6932 Part 8 (Clause 3.2.4).
IS 6932 Part 11: Determination of Initial Setting Time of Hydrated Lime
| Penetration Depth (mm) | Interpretation |
|---|---|
| > 5 ± 0.5 | Lime not set yet |
| ≤ 5 ± 0.5 | Initial setting reached |
flowchart TD
A[Add water to lime] --> B[Prepare test block]
B --> C[Lower needle on block surface]
C --> D{Needle penetration > 5 ± 0.5 mm?}
D -- Yes --> E[Repeat test after interval]
D -- No --> F[Record elapsed time as Initial Setting Time]
This method ensures reliable determination of hydrated lime's initial setting time per IS 6932-11.
IS 6932 Part 11: Determination of Final Setting Time of Hydrated Lime
| Step | Description |
|---|---|
| Prepare test block | As per Clause 3.1 |
| Use Vicat apparatus | Replace needle with annular attachment |
| Apply needle gently | Needle should make impression |
| Check annular attachment | Should not make impression |
| Record time | Time at which above condition is met = Final Setting Time |
graph LR
A[Vicat Apparatus] --> B[Standard Needle (C)]
A --> C[Annular Attachment (F)]
B --> D[Penetrates test block surface]
C --> E[No impression on surface at final set]
This method ensures accurate determination of the final setting time critical for quality control of hydrated lime in construction.
IS 6932 Part 11 - Test Conditions Summary
| Parameter | Value |
|---|---|
| Temperature | 27 ± 2 °C |
| Relative Humidity | ≥ 90% |
| Air Movement | No draughts |
| Sample Form | Putty (IS 6932 Pt.8) |
flowchart TD
A[Test Preparation] --> B[Maintain Temp 27±2°C]
B --> C[Maintain RH ≥ 90%]
C --> D[Use Clean Appliances]
D --> E[Perform Test with Vicat Needle + Annular Attachment]
E --> F{Needle impression?}
F -- Yes, Attachment no impression --> G[Final Setting Time Recorded]
F -- No --> H[Continue Testing]
This ensures consistent, reliable lime setting time measurements per IS 6932 Part 11.
IS 6932 (Part 11) - Reporting of Results for Setting Time of Hydrated Lime
| Parameter | Specification |
|---|---|
| Temperature | 27 ± 2°C |
| Relative Humidity | ≥ 90% |
| Apparatus Needle | Needle with annular attachment (Vicat) |
| Impression Criterion | Needle makes impression; annular attachment does not |
| Surface for Test | Top surface or underside if scum forms |
| Rounding Off | As per IS 2-1960 |
flowchart TD
A[Test Block Preparation] --> B[Apply Needle with Annular Attachment]
B --> C{Does Needle Make Impression?}
C -- Yes --> D{Does Annular Attachment Make Impression?}
D -- No --> E[Record Final Setting Time]
D -- Yes --> F[Continue Testing]
C -- No --> F
F --> B
This ensures standardized and reproducible reporting of setting time results per IS 6932 (Part 11).
Frequently Asked
Apparatus for Determining Setting Time of Hydrated Lime (IS 6932 Part 11):
Penetration Needle and Rod Assembly:
A needle mounted on a rod (referred to as the "needle (C)" in the code) is used to test the setting time by penetration.
Mould:
To prepare the test block of hydrated lime paste.
Test Principle:
| Step | Description |
|---|---|
| Prepare test block | According to IS 6932-11 Clause 3.1 |
| Use needle on rod assembly | Lower gently, release to penetrate lime block |
| Measure penetration depth | Initial setting time = time when penetration ≤ 5 ± 0.5 mm |
Loading diagram...
This apparatus and method ensure consistent, repeatable determination of hydrated lime setting time as per IS 6932 Part 11.
Initial Setting Time of Hydrated Lime (IS 6932 Part 11)
Definition: The initial setting time is the duration from the moment water is added to hydrated lime until the test needle fails to penetrate the test block by 5 ± 0.5 mm.
Measurement Procedure (Clause 3.2):
This method ensures a consistent, reproducible measure of setting behavior for hydrated lime.
According to IS 6932 Part 11 (Clause 3.1.2), the environmental conditions during testing of building lime are:
These conditions ensure consistency and reliability in test results, especially for setting time and workability tests.
| Parameter | Required Value |
|---|---|
| Temperature | 27 ± 2°C |
| Relative Humidity | ≥ 90% |
| Air Movement | No drafts (still air) |
| Equipment | Clean appliances |
Maintaining these conditions is critical for accurate determination of lime properties as per IS 6932 Part 11.
According to IS 6932 Part 11, the final setting time using the Vicat apparatus is determined as follows:
| Step | Action |
|---|---|
| Use Vicat apparatus | Needle with annular attachment (F) |
| Test surface | Apply needle gently |
| Final set criteria | Needle makes impression; annular attachment does not |
This method ensures precise detection of the final setting stage of lime.
Loading diagram...
IS 6932 Part 11 does not explicitly mention procedures for scum formation on the lime test sample surface during setting time tests.
Recommended procedure (engineering practice):
This ensures accurate needle penetration readings and reliable initial setting time per Clause 3.2.
Loading diagram...
Summary: Remove scum carefully or redo the sample to maintain test accuracy.