Code of practice for fire safety of industrial buildings: Tea factories

IS 4886:1991 is the Indian Standard code of practice for fire safety specifically tailored to industrial buildings used as tea factories. It provides comprehensive guidelines on building construction, fuel systems, electrical installations, storage arrangements, and fire fighting provisions to minimize fire hazards in tea manufacturing environments. This standard is essential for engineers, safety managers, and factory planners involved in designing, operating, or maintaining tea processing facilities to ensure compliance with fire safety regulations and safeguard property and personnel.

14Sections
106Clauses Indexed
AI Search Ready
1991Edition
Fire SafetyCategory
Alternative search terms: IS 4886 PDF, IS 4886 pdf free download, IS 4886 free download pdf, IS4886 PDF, IS-4886 PDF, IS 4886 1991 PDF, IS 4886:1991 PDF, IS 4886-1991 PDF, IS 4886 (1991) PDF, IS 4886 1991 edition PDF, IS 4886 edition 1991 PDF

What This Standard Covers

IS 4886:1991 is the Indian Standard code of practice for fire safety specifically tailored to industrial buildings used as tea factories. It provides comprehensive guidelines on building construction, fuel systems, electrical installations, storage arrangements, and fire fighting provisions to minimize fire hazards in tea manufacturing environments. This standard is essential for engineers, safety managers, and factory planners involved in designing, operating, or maintaining tea processing facilities to ensure compliance with fire safety regulations and safeguard property and personnel.

Who Uses This Standard

  • Fire safety engineers
  • Industrial building designers
  • Tea factory managers
  • Safety compliance officers
  • Mechanical and electrical engineers
  • Facility maintenance supervisors
  • Regulatory inspectors

Key Topics Covered

Fire safety requirements for tea factory buildings
Design and construction of withering houses and drying chambers
Fuel supply and burner safety systems
Natural gas fired tea drying machine installation
Electrical installation standards for tea factories
Storage and handling of combustible materials
Fire fighting equipment and hydrant systems
Ventilation and exhaust flue arrangements
Safety measures for heating units and heat exchangers
Provisions for emergency shut-off valves and interlocks
Clearance distances and site layout for fire prevention
Maintenance and cleaning protocols to reduce fire risk

Table of Contents

1Scope

IS 4886: Scope Summary

  • Scope: Covers specifications and requirements for portable fire extinguishers.
  • Purpose: To ensure quality, performance, and safety in fire extinguishing equipment.
  • Referenced Standards: Annex A lists related IS codes essential for comprehensive fire safety and extinguisher design, e.g.:
    • IS 940: Portable chemical fire extinguisher (water type)
    • IS 1239 (Parts 1 & 2): Mild steel tubes and fittings
    • IS 2190: Selection, installation, and maintenance of portable fire extinguishers
    • IS 3594: Fire safety of industrial buildings
    • IS 13039: External fire hydrant systems

Key Points:

  • The standard ensures conformity through BIS certification and continuous quality checks.
  • It is linked with fire safety codes for buildings, materials, and installation practices.
  • Users must refer to the latest amendments for up-to-date requirements.

flowchart LR
A[IS 4886 Scope] --> B[Portable Fire Extinguishers]
A --> C[Related IS Codes]
C --> D[IS 940 - Chemical Extinguishers]
C --> E[IS 2190 - Installation & Maintenance]
C --> F[IS 3594 - Industrial Fire Safety]
C --> G[IS 13039 - Fire Hydrant Systems]

This overview helps align fire extinguisher specs with building safety and manufacturing standards.

2Referenced Indian Standards

Referenced Indian Standards in IS 4886 (Clause 2.1, Annex A)

IS No.Title
IS 940 : 1989Portable chemical fire extinguisher, water type (gas pressure) (3rd revision)
IS 1239 (Part 1) : 1979Mild steel tubes, tubulars and other wrought steel fittings: Part 1 Mild steel tubes (4th revision)
IS 1239 (Part 2) : 1982Mild steel tubulars and other wrought steel pipe fittings (3rd revision)
IS 1642 : 1989Code of practice for fire safety of buildings (general): Materials and details of construction (1st revision)
IS 1646 : 1978Code of practice for fire safety of buildings (general): Electrical installations (1st revision)
IS 2190 : 1979Code of practice for selection, installation and maintenance of portable first-aid fire extinguisher (2nd revision)
IS 3594 : 1989Code of practice for fire safety of industrial buildings: General storage and warehousing including cold storages (1st revision)
IS 3884 : 1989Canned tomato paste (1st revision)
IS 9668 : 1980Code of practice for provision and maintenance of water supplies for fire fighting
IS 10204 : 1982Portable fire extinguisher mechanical foam type
IS 11108 : 1984Portable fire extinguisher - Halon 1211 type
IS 12777 : 1989Fire safety - Flame spread of products - Method for Classification
IS 13039 : 1991Code of practice for provision and maintenance of external fire hydrant system

Notes:

  • These standards cover fire extinguishers, fire safety of buildings, fire fighting water supply, materials, and construction details relevant to tea factories.
  • IS 2190 and IS 940 are critical for portable fire extinguisher specifications.
  • IS 9668
3Definitions

IS 4886: Definitions & Key References

  • Clause 3.0 defines terms used in the standard, ensuring clarity for fire safety equipment and systems.

  • Annex A (Clause 2.1) lists related Indian Standards essential for compliance and detailed design, including:

    IS No.Title
    940:1989Portable chemical fire extinguisher, water type (gas pressure)
    1239 (Pt 1 & 2): 1979, 1982Mild steel tubes and fittings
    2190:1979Selection, installation, and maintenance of portable fire extinguishers
    3594:1989Fire safety of industrial buildings: storage and warehousing
    3884:1989Canned tomato paste (related to packaging safety)
    9668:1980Provision and maintenance of water supplies for fire fighting
    10204:1982Portable fire extinguisher mechanical foam type
    11108:1984Portable fire extinguisher - Halon 1211 type
    12777:1989Fire safety - Flame spread of products - Classification method
    13039:1991Provision and maintenance of external fire hydrant system
  • Key Notes:

    • Internal hydrant systems per IS 3844:1989.

    • External hydrant systems per IS 13039:1991.

    • Fire extinguisher types and capacities (e.g., BCF 1.2 kg & 5 kg per IS 11108:1984).

Summary:

IS 4886 defines terminology and mandates adherence to a suite of IS codes covering fire extinguishers, hydrant systems, and fire safety in buildings. For detailed design, installation, and maintenance, refer to the listed IS codes in Annex A.

graph LR
A[IS 4886 Definitions] --> B[Fire Extinguishers]
A --> C[Hydrant Systems]
A --> D[Fire Safety in Buildings]
B --> E[IS 940, IS 2190, IS 10204, IS 11108]
C --> F[IS 3844 (Internal
4Location and Site Requirements

IS 4886: Location and Site Requirements - Key Specifications

1. Site Clearance & Vegetation (Clause 5.2)

  • Compound must be clear of growing vegetation.
  • Lawns, if any, should be regularly mowed to reduce fire risk.

2. Building Construction (Clause 6.1)

  • Must comply with IS 1642:1989 for constructional features.

3. Storage Tank Location & Specifications (Clause 10.2.1)

Tank TypeMinimum Distance from Insured Property
Above Ground (bulk)≥ 15 m
Fully/Semi-Embedded≥ 6 m
  • Tanks must be made of wrought iron or ungalvanized mild steel, oiltight, and hydraulically tested at 2 kN/m².
  • Fill pipe: extends ≥ 2/3 depth, discharges fuel horizontally.
  • Outlet centerline ≥ 75 mm above tank bottom.
  • Vent pipe:
    • Above ground tanks: extends ≥ 1 m above roof.
    • Square tanks: extends ≥ 3 m above ground.
  • Vent pipe end: inverted U-bend with 20 mesh/cm² wire gauze.
  • Bund wall: must contain 110% of tank volume for surface tanks.

4. Safety Distances from Railway (Clause 4.2)

  • Storage/process buildings ≥ 30 m from coal-fired locomotive railway lines.
  • If < 30 m, all openings protected with 20 mesh/cm² wire gauze.
  • Surroundings cleared of combustible material for ≥ 15 m.

Summary Diagram: Tank Location & Safety Distances

graph TD
    A[Bulk Storage Tank] -->|≥ 15 m| B[Insured Property]
    C[Fully Embedded Tank] -->|≥ 6 m| B
    D[Railway Line (Coal-fired)] -->|≥ 30 m| E[Storage Building]
    E -->|< 30 m| F[Wire Gauze Protection + 15 m Clearance]
    A --> G[Bund Wall: 110% volume containment]

Use these key distances and construction requirements to ensure compliance with IS 4886 for safe storage and site layout.

5Factory Compound and Site Maintenance

IS 4886 - Factory Compound & Site Maintenance: Key Points

1. Factory Compound Area (Clause 5.1)

  • Must comply with Clause 8.1 (usually specifying minimum area based on factory type & capacity).
  • Adequate space for safe operations, movement, and emergency access.

2. Building Construction (Clause 6.1)

  • Buildings must conform to IS 1642:1989 (Code for Construction of Industrial Buildings).
  • Ensures fire resistance, structural safety, and durability.

3. Vegetation Control (Clause 5.2)

  • Compound must be free from growing vegetation.
  • Lawns, if any, should be regularly mowed to reduce fire risk and maintain hygiene.

4. Distance from Railway Lines (Clause 4.2)

  • Storage/process buildings ≥ 30 m from coal-fired locomotive railway lines.
  • If < 30 m, then:
    • External openings protected by 20 mesh/cm² wire gauge.
    • Clear vegetation/combustible material within 15 m radius.

Summary Table:

AspectSpecification
Minimum distance from coal-fired railway≥ 30 m (else protection needed)
Wire mesh for openings20 mesh/cm²
Vegetation clearanceNo vegetation; 15 m clear zone near railways
Lawn maintenanceRegular mowing

flowchart LR
    A[Factory Compound] --> B[Area as per Clause 8.1]
    A --> C[Clear of Vegetation]
    C --> D[Lawn Mowed Regularly]
    A --> E[Buildings per IS 1642:1989]
    E --> F[≥30m from Coal Railway]
    F -->|If <30m| G[20 mesh/cm² wire protection]
    G --> H[Clear 15m vegetation zone]

This ensures safety, fire prevention, and operational efficiency in factory site maintenance per IS 4886.

6Building Construction

IS 4886:1991 primarily references IS 1642:1989 for building construction features in tea factories, focusing on fire safety.

Key Points on Building Construction (from IS 4886 & IS 1642):

  • Clause 6.1 (IS 4886):
    Buildings must comply with IS 1642:1989 for constructional features, ensuring fire-resistant materials and structural safety.

  • Clause 5.2 (IS 4886):
    Compound areas must be cleared of vegetation; lawns should be maintained to minimize fire risk.


From IS 1642:1989 (Relevant for Fire Safety in Industrial Buildings)

ParameterSpecification
Wall MaterialFire-resistant bricks, concrete
RoofingNon-combustible materials preferred
FlooringConcrete or fire-resistant tiles
Fire Separation DistanceMinimum 6 m between buildings
Ventilation OpeningsFire-resistant shutters

Typical Fire Safety Construction Formulas:

  • Fire Resistance Rating (FRR):
    [ FRR = \text{Time (in hours) a building element can withstand fire} ]

  • Minimum Wall Thickness (for fire resistance):
    [ t = k \times \sqrt{FRR} ]
    where k depends on material (e.g., brick, concrete).


Summary Diagram of Fire-Safe Building Layout

graph LR
A[Building] --> B[Fire-Resistant Walls]
A --> C[Non-Combustible Roof]
A --> D[Clear Compound (No Vegetation)]
A --> E[Fire Separation Distance ≥ 6m]

For detailed design, refer to IS 1642:1989 for material specs, wall thickness, and fire resistance ratings.

7Materials and Fire Resistance

IS 4886: Fire Safety of Industrial Buildings - Tea Factories (Key Points on Materials & Fire Resistance)

  • Materials:

    • Withering houses should be at least Type 3 construction (Clause 6.2.1).
    • Avoid combustible materials like timber racks and hessian. If used, treat chemically to meet Class I flame spread as per IS 12777:1989.
  • Fire Extinguishers:

    • Use CO2 squeeze grip type extinguishers (IS 2878).
    • Alternatively, BCF extinguishers of 1.2 kg & 5 kg as per IS 11108:1984.
    • Mechanical foam extinguisher of 9 liters as per IS 10204:1982.
  • Fire Hydrants:

    • Internal hydrant system per IS 3844:1989.
    • External hydrant system per IS 13039:1991.

Flame Spread Classification (IS 12777:1989)

ClassFlame Spread IndexDescription
I0 - 25Low flame spread (safe)
II26 - 75Moderate flame spread
III> 75High flame spread (unsafe)

Summary Diagram of Fire Safety Elements in Tea Factories

graph LR
A[Withering House] --> B[Material: Type 3 Construction]
B --> C{Combustible Material?}
C -- Yes --> D[Treated to Class I (IS 12777)]
C -- No --> E[No special treatment]
A --> F[Fire Extinguishers]
F --> G[CO2 (IS 2878)]
F --> H[BCF 1.2/5 kg (IS 11108)]
F --> I[Mechanical Foam 9L (IS 10204)]
A --> J[Hydrant Systems]
J --> K[Internal (IS 3844)]
J --> L[External (IS 13039)]

Note: Ensure adequate water supply and private fire protection due to remote locations of tea factories.

8Separation Distances and Layout

IS 4886: Separation Distances and Layout - Key Points

1. Separation Walls (Clause 7.1)

  • Separate critical sections with fire-resistant walls:
    • Furnace of directly fired driers
    • Tea-chest fabricating rooms
    • Boiler house and stores of directly heated driers
    • Engine house
    • Transformer room:
      • Located at building periphery or separate building
      • Entrance with rolling shutter & raised sill ≥ 15 cm
    • Sub-station separated from transformer by 4-hour fire rating wall (IS 1642:1989) without doors
    • Natural gas metering rooms

2. Minimum Distances (Clause 4.2 & 8.1)

LocationMinimum Separation Distance
Factory buildings from coal railway30 m
Vegetation-free zone around buildings15 m
Godowns from factory/withering houses6 m
  • External openings near coal railway must have 20 mesh/cm² wire gauge protection.

3. Floor Area Limitation (Clause 6.6.1)

  • Withering house with combustible racks: max floor area ≤ 2000 m²

Summary Table:

ItemRequirement
Transformer room sill height≥ 15 cm
Fire rating wall4-hour rating (IS 1642:1989)
Distance from coal railway≥ 30 m
Vegetation-free zone≥ 15 m
Godown to factory distance≥ 6 m
Withering house max area≤ 2000 m²

graph LR
A[Factory Sections] -->|Separated by| B[Fire-resistant Walls]
B --> C[Furnace]
B --> D[Boiler House]
B --> E[Engine House]
B --> F[Transformer Room]
F --> G[4-hour fire rating wall]
A --> H[Minimum Distances]
H --> I[≥ 30 m from coal railway]
H --> J[≥ 15 m vegetation-free zone]
H --> K[≥ 6 m godown to factory]

This ensures

9Fuel Supply and Burner Installations

IS 4886: Fuel Supply and Burner Installations – Key Points

Fuel Supply (Clauses 9.1.5, 9.1.6, 9.2.1)

  • Fuel line must include an efficient filter to remove impurities before reaching the burner.
  • Pressurized fuel lines require safety measures (e.g., pressure relief valves, shut-off valves).
  • Automatic fuel cut-off must activate if air flow to burner stops, preventing unsafe fuel accumulation.
  • Fuel supply remains cut off after air flow resumes until burners are manually re-lit.
  • Natural gas supply must come from a recognized gas undertaking with guaranteed calorific value and pressure.

Burner Installation (Clause 9.2.11)

  • Burners, igniters, safety controls, and ventilation must be approved types meeting safety and performance standards.

Typical Safety Control Logic (simplified):

flowchart TD
    A[Air Flow Sensor] -->|No Air Flow| B[Fuel Supply Shut-off Valve]
    B --> C[Fuel Supply Cut-off]
    C --> D[Burner Re-light Required]
    A -->|Air Flow Present| E[Burner Operation]

Summary Table: Fuel Supply Safety Features

FeatureRequirement
Fuel FilterEfficient, installed before burner
Fuel Line PressureMaintained as per burner spec
Safety Cut-offAuto cut-off on air flow loss
Re-light ControlManual re-light after cut-off
Burner & ControlsApproved, tested types

Ensure compliance with these clauses for safe, reliable fuel supply and burner operation per IS 4886.

10Storage Arrangements

IS 4886: Storage Arrangements - Key Specifications & Formulas

Storage Tank Placement (Clause 10.2.1)

  • Distance from insured property:
    • Above ground tanks: ≥ 15 m
    • Fully/semi-embedded tanks: ≥ 6 m

Tank Construction & Testing

  • Material: Wrought iron or ungalvanized mild steel.
  • Hydraulic test pressure: 2 kN/m² (internal pressure).
  • Manholes/inspection covers: Bolted, oiltight, reinforced, and welded/riveted.
  • Fill pipe: Screwed cap, extends ≥ 2/3 depth of tank, discharges horizontally.
  • Outlet centerline: ≥ 75 mm above tank bottom.
  • Sludge removal: Provided at lowest point with gland-packed plug cock/gate valve.
  • Vent pipe:
    • Above ground tanks: Extends ≥ 1 m above roof.
    • Square tanks: Extends ≥ 3 m above ground.
    • Vent opening: Inverted 'U' bend with 20 mesh/cm² wire gauze.

Valves & Safety

  • Stop valve on outlet/suction pipe near tank (except hand pump filling).
  • Anti-syphon valve on supply pipe to prevent unintended flow.
  • Electrical continuity & earthing mandatory.

Fuel Level Indicators

  • Preferred: Hydrostatic gauges.
  • Alternatives: Dip rods (open tanks), float gauges with glanded cords.
  • Gauge glasses: Not allowed.

Bund Wall (Clause 10.2.1 j)

  • Required for surface tanks.
  • Capacity: Contain 110% of tank volume.
  • No bund wall for underground tanks, but protection against damage mandatory.

Reference Table: Minimum Distances & Dimensions

FeatureMinimum Distance / Dimension
Above ground tank to property15 m
Embedded tank to property6 m
Fill pipe depth≥ 2/3 tank depth
Outlet above tank bottom≥ 75 mm
Vent pipe height (above ground)≥ 1 m
Vent pipe height (square tank)≥ 3 m
Vent pipe mesh size20 mesh/cm²
Bund wall capacity110% of tank volume

11Electrical Installations

IS 4886: Electrical Installations — Key Points & Specifications

  • Reference Standard:
    Electrical installations must comply with IS 1646:1978 (Specification for electrical wiring).

  • Wiring Requirements (Clause 11.3):

    • Use screwed steel conduits or
    • Mineral insulated copper/aluminium sheathed cables for power and lighting wiring in process/storage buildings.
  • Equipment (Clause 11.2):

    • Use totally enclosed, metal-clad, adequately rated equipment wherever practicable.
  • Earthing & Continuity (Clause 10.2.2.j):

    • Tanks and fittings must ensure electrical continuity and be efficiently earthed to prevent static hazards.

Summary Table: Wiring Types for Industrial Buildings

Wiring TypeApplicationProtection Level
Screwed Steel ConduitsPower & lighting wiringMechanical & fire protection
Mineral Insulated Copper/Aluminium SheathedPower & lighting wiringHigh fire & mechanical resistance

Important Tank Electrical Safety Measures (Clause 10.2.2):

  • Ensure earthing continuity of tanks and fittings.
  • Use anti-syphon valves and vent pipes positioned away from openings.
  • Overflow pipes sized ≥ 1.5 × inflow pipe cross-section, no stop valves on overflow.

flowchart LR
    A[Power & Lighting Wiring] --> B[Screwed Steel Conduits]
    A --> C[Mineral Insulated Cables]
    D[Equipment] --> E[Totally Enclosed, Metal Clad]
    F[Tanks & Fittings] --> G[Electrical Continuity & Earthing]

For detailed electrical design, refer to IS 1646:1978 alongside IS 4886.

12Fire Fighting Arrangements

IS 4886 Fire Fighting Arrangements: Key Specifications

1. Water for Fire Fighting

  • Adequate water supply must be ensured for factories and withering houses.
  • Refer IS 9668 : 1980 for detailed water requirements and storage.

2. Portable Fire Extinguishers

  • Must comply with IS 2190 : 1979.
  • Types recommended:
    • Water Gas Pressure Type: 9 liters (IS 940 : 1989)
    • CO2 Squeeze Grip Type (substituted for BCF): 1.2 kg and 5 kg (IS 2878)
    • Mechanical Foam Extinguisher: 9 liters (IS 10204 : 1982)

3. Hydrant Systems

  • Internal Hydrant: As per IS 3844 : 1989
  • External Hydrant: As per IS 13039 : 1991

4. Safety Notes

  • Lamp fittings near withering houses and within 6m of tea driers must be dust-tight (Clause 11.6).

Summary Table of Extinguishers

Extinguisher TypeCapacityIS Code
Water Gas Pressure Type9 litersIS 940 : 1989
CO2 Squeeze Grip Type1.2 & 5 kgIS 2878
Mechanical Foam Extinguisher9 litersIS 10204 : 1982

flowchart TD
    A[Factories & Withering Houses] --> B[Water Supply (IS 9668)]
    A --> C[Portable Fire Extinguishers (IS 2190)]
    C --> D[Water Gas Pressure (9L)]
    C --> E[CO2 Squeeze Grip (1.2 & 5 kg)]
    C --> F[Mechanical Foam (9L)]
    A --> G[Internal Hydrant System (IS 3844)]
    A --> H[External Hydrant System (IS 13039)]
    A --> I[Lamp Fittings Dust Tight (Clause 11.6)]

Ensure compliance with these IS codes and maintain regular inspections to mitigate fire hazards in tea factories.

13General Safety Provisions

IS 4886: General Safety Provisions - Key Points

1. Fire Extinguishers:

  • CO2 squeeze grip type extinguishers as per IS 2878 are recommended (replacing BCF 1.2 kg & 5 kg per IS 11108:1984).
  • Mechanical foam extinguisher of 9 liters capacity as per IS 10204:1982.

2. Hydrant Systems:

  • Internal hydrant system: Must comply with IS 3844:1989.
  • External hydrant system: Must comply with IS 13039:1991.

3. Fire Safety Design Considerations:

  • Use non-combustible materials or fire-retardant treatment for wooden racks and hessian.
  • Ensure adequate water supply for firefighting, considering remote locations.
  • Install private fire protection systems due to possible lack of public fire services.

Summary Table: Fire Extinguisher Types

Extinguisher TypeCapacityRelevant IS Code
CO2 Squeeze Grip Type2 kg, 5 kg (typical)IS 2878
Mechanical Foam9 litersIS 10204:1982

Hydrant System Compliance

flowchart LR
    A[Fire Safety System] --> B[Internal Hydrant System]
    A --> C[External Hydrant System]
    B -->|IS 3844:1989| D[Design & Installation]
    C -->|IS 13039:1991| E[Design & Installation]

Note: These provisions supplement statutory requirements like the Indian Factories Act (1948) and Petroleum Rules (1976).

Annex AList of Referenced Indian Standards

IS 4886:1991 - List of Referenced Indian Standards (Annex A, Clause 2.1)

This clause lists essential Indian Standards that complement IS 4886 for fire safety and related materials:

IS No.Title
940 : 1989Portable chemical fire extinguisher, water type (gas pressure) (3rd revision)
1239 (Part 1):1979Mild steel tubes, tubulars and other wrought steel fittings: Part 1 Mild steel tubes
1239 (Part 2):1982Mild steel tubulars and other wrought steel pipe fittings (3rd revision)
1642 : 1989Code of practice for fire safety of buildings (general): Materials and construction (1st revision)
1646 : 1978Code of practice for fire safety of buildings (general): Electrical installations (1st revision)
2190 : 1979Code of practice for selection, installation and maintenance of portable fire extinguisher (2nd revision)
3594 : 1989Code of practice for fire safety of industrial buildings: General storage and warehousing (1st revision)
3884 : 1989Canned tomato paste (1st revision)
9668 : 1980Code of practice for provision and maintenance of water supplies for fire fighting
10204 : 1982Portable fire extinguisher mechanical foam type
11108 : 1984Portable fire extinguisher - Halon 1211 type
12777 : 1989Fire safety - Flame spread of products - Method for Classification
13039 : 1991Code of practice for provision and maintenance of external fire hydrant system

Key Notes:

  • These standards cover fire extinguishers, steel tubulars, fire safety codes for buildings, industrial storage, water supplies, and fire hydrant systems.
  • Use of the Standard Mark ensures compliance with BIS quality and inspection systems.
  • Periodic revisions and amendments are issued to keep standards updated.

For detailed application, refer to the individual IS codes listed above.

flowchart LR
    IS

Popular Questions About IS 4886

?What are the recommended construction materials for withering houses to ensure fire safety?

Recommended Construction Materials for Withering Houses (IS 4886):

  • Withering houses should be constructed as Type 3 buildings (fire-resistive construction) per IS 1642:1989.
  • Avoid combustible materials such as timber racks or hessian spreads.
  • If timber or hessian must be used, they should be chemically treated to meet Class I flame spread rating as per IS 12777:1989.
  • Maximum floor area for withering houses using combustible racks is 2,000 m².
  • Maintain a minimum distance of 10 m from other buildings unless the wall between them is a fire-separating wall as per IS 4886 clause 8.2.

Summary Table

Material TypeRequirement
Structural FrameType 3 fire-resistive construction (IS 1642)
Racks/HessianAvoid; if used, treat chemically (Class I, IS12777)
Floor Area≤ 2,000 m² if combustible racks are used
Separation Distance≥ 10 m or fire-separating wall (clause 8.2)
Loading diagram...

This ensures fire safety by limiting combustible content and enhancing fire resistance.

?How should natural gas supply and piping be installed and maintained in tea drying machines?

Installation & Maintenance of Natural Gas Supply for Tea Drying Machines (IS 4886: Clause 9.2)

  • Gas Supply Source:
    Supply must come from a recognized gas authority ensuring constant calorific value and adequate pressure (9.2.1).

  • Service Fuel Tank Location (9.1.3):

    • Outside building preferred.
    • If inside, must be in a fire-rated enclosed room with direct outside access (2-hour fire resistance per IS 1642:1989).
    • Max capacity: 1.1 kl.
  • Piping Installation (9.2.3 & 9.1.3):

    • Use robust, gas-tight piping rigidly supported to avoid mechanical damage.
    • Pipes must be away from exhaust/hot air and any burning fuel source.
    • Avoid routing pipes across factory buildings where possible.
    • Threaded connections mandatory.
    • Pipes and fittings must comply with IS 1239 (Part 1 & 2).
    • Provide drainage for condensed water.
  • Maintenance:

    • Regular inspection for gas tightness and mechanical integrity.
    • Ensure drainage system for condensate is functional.
Loading diagram...

This ensures safe, reliable, and code-compliant natural gas supply for tea drying machines.

?What fire fighting equipment and hydrant systems are required for tea factories?

Fire Fighting Equipment & Hydrant Systems for Tea Factories (IS 4886)

  • Location & Access (Clause 4.1):

    • Factories must be sited where ample water supply is available.
    • Access roads should be all-weather, minimum 3.6 m wide for fire service vehicles.
  • Water Supply (Clause 12.1a):

    • Adequate water quantity must be ensured for the factory and withering houses.
    • Refer to IS 9668:1980 for detailed water requirements.
  • Portable Fire Extinguishers (Clause 12.1b):

    • Factories and withering houses must have portable extinguishers complying with IS 2190:1979.
    • Recommended type: Water gas pressure type, 9 liters (per IS 940:1989).
  • Electrical Safety (Clause 11.6):

    • Lamps near tea driers and withering troughs must be dust-tight to prevent ignition.

Summary Table

EquipmentStandardDetails
Water supplyIS 9668:1980Adequate quantity for fire fighting
Portable extinguishersIS 2190:1979Water gas pressure type, 9 L (IS 940:1989)
Access roadsIS 4886 Clause 4.1Minimum 3.6 m width, all-weather
Lamp fittingsIS 4886 Clause 11.6Dust-tight near heat sources

This ensures effective fire fighting readiness tailored for tea factory hazards.

?What are the clearance distances between storage areas, factory buildings, and fuel tanks?

Clearance Distances as per IS 4886:

  • Bulk Storage Tanks:

    • Above ground (not embedded): ≥ 15 m from any insured property.
    • Fully or semi-embedded tanks: ≥ 6 m from any insured property.
  • Factory Buildings and Storage:

    • Storage/process buildings from coal-fired railway line: ≥ 30 m (if not possible, protect openings and clear 15 m vegetation-free zone).
    • Godowns to factory buildings/withering houses (non-combustible racks): ≥ 6 m.
    • Coal, wood, or other fuels (excess daily requirement) storage: ≥ 10 m from any building.

Summary Table

ItemMinimum Clearance Distance
Bulk storage tank (above ground)15 m
Bulk storage tank (embedded type)6 m
Storage/process buildings to coal-fired railway30 m (or protected openings + 15 m clear zone)
Godowns to factory buildings6 m
Fuel (coal, wood) storage excess10 m

This ensures fire safety and prevents hazards from fuel storage near buildings and other structures.

Loading diagram...
?How should electrical installations be designed to minimize fire hazards in tea factories?

To minimize fire hazards in tea factories as per IS 4886, focus on electrical installations as follows:

  • Dust-tight lamp fittings: Use dust-tight lamps in withering houses and within 6 m of tea driers and withering troughs (Clause 11.6). This prevents dust accumulation and sparks.
  • Safe location and access: Ensure factories have ample water supply nearby and all-weather access roads ≥ 3.6 m wide for fire fighting (Clause 4.1).
  • Electrical design considerations:
    • Use flameproof or explosion-proof fittings near combustible dust zones.
    • Avoid exposed wiring; use conduits or cable trays sealed against dust ingress.
    • Install residual current devices (RCDs) and proper earthing to prevent electrical faults.
    • Regular maintenance and inspection to detect overheating or insulation failures.

These measures reduce ignition sources and improve fire response readiness in tea factories.

Loading diagram...