IS 4886:1991 is the Indian Standard code of practice for fire safety specifically tailored to industrial buildings used as tea factories. It provides comprehensive guidelines on building construction, fuel systems, electrical installations, storage arrangements, and fire fighting provisions to minimize fire hazards in tea manufacturing environments. This standard is essential for engineers, safety managers, and factory planners involved in designing, operating, or maintaining tea processing facilities to ensure compliance with fire safety regulations and safeguard property and personnel.
Overview
IS 4886:1991 is the Indian Standard code of practice for fire safety specifically tailored to industrial buildings used as tea factories. It provides comprehensive guidelines on building construction, fuel systems, electrical installations, storage arrangements, and fire fighting provisions to minimize fire hazards in tea manufacturing environments. This standard is essential for engineers, safety managers, and factory planners involved in designing, operating, or maintaining tea processing facilities to ensure compliance with fire safety regulations and safeguard property and personnel.
Audience
Contents
Structure
IS 4886: Scope Summary
Key Points:
flowchart LR
A[IS 4886 Scope] --> B[Portable Fire Extinguishers]
A --> C[Related IS Codes]
C --> D[IS 940 - Chemical Extinguishers]
C --> E[IS 2190 - Installation & Maintenance]
C --> F[IS 3594 - Industrial Fire Safety]
C --> G[IS 13039 - Fire Hydrant Systems]
This overview helps align fire extinguisher specs with building safety and manufacturing standards.
| IS No. | Title |
|---|---|
| IS 940 : 1989 | Portable chemical fire extinguisher, water type (gas pressure) (3rd revision) |
| IS 1239 (Part 1) : 1979 | Mild steel tubes, tubulars and other wrought steel fittings: Part 1 Mild steel tubes (4th revision) |
| IS 1239 (Part 2) : 1982 | Mild steel tubulars and other wrought steel pipe fittings (3rd revision) |
| IS 1642 : 1989 | Code of practice for fire safety of buildings (general): Materials and details of construction (1st revision) |
| IS 1646 : 1978 | Code of practice for fire safety of buildings (general): Electrical installations (1st revision) |
| IS 2190 : 1979 | Code of practice for selection, installation and maintenance of portable first-aid fire extinguisher (2nd revision) |
| IS 3594 : 1989 | Code of practice for fire safety of industrial buildings: General storage and warehousing including cold storages (1st revision) |
| IS 3884 : 1989 | Canned tomato paste (1st revision) |
| IS 9668 : 1980 | Code of practice for provision and maintenance of water supplies for fire fighting |
| IS 10204 : 1982 | Portable fire extinguisher mechanical foam type |
| IS 11108 : 1984 | Portable fire extinguisher - Halon 1211 type |
| IS 12777 : 1989 | Fire safety - Flame spread of products - Method for Classification |
| IS 13039 : 1991 | Code of practice for provision and maintenance of external fire hydrant system |
IS 4886: Definitions & Key References
Clause 3.0 defines terms used in the standard, ensuring clarity for fire safety equipment and systems.
Annex A (Clause 2.1) lists related Indian Standards essential for compliance and detailed design, including:
| IS No. | Title |
|---|---|
| 940:1989 | Portable chemical fire extinguisher, water type (gas pressure) |
| 1239 (Pt 1 & 2): 1979, 1982 | Mild steel tubes and fittings |
| 2190:1979 | Selection, installation, and maintenance of portable fire extinguishers |
| 3594:1989 | Fire safety of industrial buildings: storage and warehousing |
| 3884:1989 | Canned tomato paste (related to packaging safety) |
| 9668:1980 | Provision and maintenance of water supplies for fire fighting |
| 10204:1982 | Portable fire extinguisher mechanical foam type |
| 11108:1984 | Portable fire extinguisher - Halon 1211 type |
| 12777:1989 | Fire safety - Flame spread of products - Classification method |
| 13039:1991 | Provision and maintenance of external fire hydrant system |
Key Notes:
Internal hydrant systems per IS 3844:1989.
External hydrant systems per IS 13039:1991.
Fire extinguisher types and capacities (e.g., BCF 1.2 kg & 5 kg per IS 11108:1984).
Summary:
IS 4886 defines terminology and mandates adherence to a suite of IS codes covering fire extinguishers, hydrant systems, and fire safety in buildings. For detailed design, installation, and maintenance, refer to the listed IS codes in Annex A.
graph LR
A[IS 4886 Definitions] --> B[Fire Extinguishers]
A --> C[Hydrant Systems]
A --> D[Fire Safety in Buildings]
B --> E[IS 940, IS 2190, IS 10204, IS 11108]
C --> F[IS 3844 (Internal
IS 4886: Location and Site Requirements - Key Specifications
| Tank Type | Minimum Distance from Insured Property |
|---|---|
| Above Ground (bulk) | ≥ 15 m |
| Fully/Semi-Embedded | ≥ 6 m |
graph TD
A[Bulk Storage Tank] -->|≥ 15 m| B[Insured Property]
C[Fully Embedded Tank] -->|≥ 6 m| B
D[Railway Line (Coal-fired)] -->|≥ 30 m| E[Storage Building]
E -->|< 30 m| F[Wire Gauze Protection + 15 m Clearance]
A --> G[Bund Wall: 110% volume containment]
Use these key distances and construction requirements to ensure compliance with IS 4886 for safe storage and site layout.
IS 4886 - Factory Compound & Site Maintenance: Key Points
| Aspect | Specification |
|---|---|
| Minimum distance from coal-fired railway | ≥ 30 m (else protection needed) |
| Wire mesh for openings | 20 mesh/cm² |
| Vegetation clearance | No vegetation; 15 m clear zone near railways |
| Lawn maintenance | Regular mowing |
flowchart LR
A[Factory Compound] --> B[Area as per Clause 8.1]
A --> C[Clear of Vegetation]
C --> D[Lawn Mowed Regularly]
A --> E[Buildings per IS 1642:1989]
E --> F[≥30m from Coal Railway]
F -->|If <30m| G[20 mesh/cm² wire protection]
G --> H[Clear 15m vegetation zone]
This ensures safety, fire prevention, and operational efficiency in factory site maintenance per IS 4886.
IS 4886:1991 primarily references IS 1642:1989 for building construction features in tea factories, focusing on fire safety.
Clause 6.1 (IS 4886):
Buildings must comply with IS 1642:1989 for constructional features, ensuring fire-resistant materials and structural safety.
Clause 5.2 (IS 4886):
Compound areas must be cleared of vegetation; lawns should be maintained to minimize fire risk.
| Parameter | Specification |
|---|---|
| Wall Material | Fire-resistant bricks, concrete |
| Roofing | Non-combustible materials preferred |
| Flooring | Concrete or fire-resistant tiles |
| Fire Separation Distance | Minimum 6 m between buildings |
| Ventilation Openings | Fire-resistant shutters |
Fire Resistance Rating (FRR):
[
FRR = \text{Time (in hours) a building element can withstand fire}
]
Minimum Wall Thickness (for fire resistance):
[
t = k \times \sqrt{FRR}
]
where k depends on material (e.g., brick, concrete).
graph LR
A[Building] --> B[Fire-Resistant Walls]
A --> C[Non-Combustible Roof]
A --> D[Clear Compound (No Vegetation)]
A --> E[Fire Separation Distance ≥ 6m]
For detailed design, refer to IS 1642:1989 for material specs, wall thickness, and fire resistance ratings.
IS 4886: Fire Safety of Industrial Buildings - Tea Factories (Key Points on Materials & Fire Resistance)
Materials:
Fire Extinguishers:
Fire Hydrants:
| Class | Flame Spread Index | Description |
|---|---|---|
| I | 0 - 25 | Low flame spread (safe) |
| II | 26 - 75 | Moderate flame spread |
| III | > 75 | High flame spread (unsafe) |
graph LR
A[Withering House] --> B[Material: Type 3 Construction]
B --> C{Combustible Material?}
C -- Yes --> D[Treated to Class I (IS 12777)]
C -- No --> E[No special treatment]
A --> F[Fire Extinguishers]
F --> G[CO2 (IS 2878)]
F --> H[BCF 1.2/5 kg (IS 11108)]
F --> I[Mechanical Foam 9L (IS 10204)]
A --> J[Hydrant Systems]
J --> K[Internal (IS 3844)]
J --> L[External (IS 13039)]
Note: Ensure adequate water supply and private fire protection due to remote locations of tea factories.
IS 4886: Separation Distances and Layout - Key Points
| Location | Minimum Separation Distance |
|---|---|
| Factory buildings from coal railway | ≥ 30 m |
| Vegetation-free zone around buildings | ≥ 15 m |
| Godowns from factory/withering houses | ≥ 6 m |
| Item | Requirement |
|---|---|
| Transformer room sill height | ≥ 15 cm |
| Fire rating wall | 4-hour rating (IS 1642:1989) |
| Distance from coal railway | ≥ 30 m |
| Vegetation-free zone | ≥ 15 m |
| Godown to factory distance | ≥ 6 m |
| Withering house max area | ≤ 2000 m² |
graph LR
A[Factory Sections] -->|Separated by| B[Fire-resistant Walls]
B --> C[Furnace]
B --> D[Boiler House]
B --> E[Engine House]
B --> F[Transformer Room]
F --> G[4-hour fire rating wall]
A --> H[Minimum Distances]
H --> I[≥ 30 m from coal railway]
H --> J[≥ 15 m vegetation-free zone]
H --> K[≥ 6 m godown to factory]
This ensures
IS 4886: Fuel Supply and Burner Installations – Key Points
flowchart TD
A[Air Flow Sensor] -->|No Air Flow| B[Fuel Supply Shut-off Valve]
B --> C[Fuel Supply Cut-off]
C --> D[Burner Re-light Required]
A -->|Air Flow Present| E[Burner Operation]
| Feature | Requirement |
|---|---|
| Fuel Filter | Efficient, installed before burner |
| Fuel Line Pressure | Maintained as per burner spec |
| Safety Cut-off | Auto cut-off on air flow loss |
| Re-light Control | Manual re-light after cut-off |
| Burner & Controls | Approved, tested types |
Ensure compliance with these clauses for safe, reliable fuel supply and burner operation per IS 4886.
IS 4886: Storage Arrangements - Key Specifications & Formulas
| Feature | Minimum Distance / Dimension |
|---|---|
| Above ground tank to property | 15 m |
| Embedded tank to property | 6 m |
| Fill pipe depth | ≥ 2/3 tank depth |
| Outlet above tank bottom | ≥ 75 mm |
| Vent pipe height (above ground) | ≥ 1 m |
| Vent pipe height (square tank) | ≥ 3 m |
| Vent pipe mesh size | 20 mesh/cm² |
| Bund wall capacity | 110% of tank volume |
IS 4886: Electrical Installations — Key Points & Specifications
Reference Standard:
Electrical installations must comply with IS 1646:1978 (Specification for electrical wiring).
Wiring Requirements (Clause 11.3):
Equipment (Clause 11.2):
Earthing & Continuity (Clause 10.2.2.j):
| Wiring Type | Application | Protection Level |
|---|---|---|
| Screwed Steel Conduits | Power & lighting wiring | Mechanical & fire protection |
| Mineral Insulated Copper/Aluminium Sheathed | Power & lighting wiring | High fire & mechanical resistance |
flowchart LR
A[Power & Lighting Wiring] --> B[Screwed Steel Conduits]
A --> C[Mineral Insulated Cables]
D[Equipment] --> E[Totally Enclosed, Metal Clad]
F[Tanks & Fittings] --> G[Electrical Continuity & Earthing]
For detailed electrical design, refer to IS 1646:1978 alongside IS 4886.
IS 4886 Fire Fighting Arrangements: Key Specifications
| Extinguisher Type | Capacity | IS Code |
|---|---|---|
| Water Gas Pressure Type | 9 liters | IS 940 : 1989 |
| CO2 Squeeze Grip Type | 1.2 & 5 kg | IS 2878 |
| Mechanical Foam Extinguisher | 9 liters | IS 10204 : 1982 |
flowchart TD
A[Factories & Withering Houses] --> B[Water Supply (IS 9668)]
A --> C[Portable Fire Extinguishers (IS 2190)]
C --> D[Water Gas Pressure (9L)]
C --> E[CO2 Squeeze Grip (1.2 & 5 kg)]
C --> F[Mechanical Foam (9L)]
A --> G[Internal Hydrant System (IS 3844)]
A --> H[External Hydrant System (IS 13039)]
A --> I[Lamp Fittings Dust Tight (Clause 11.6)]
Ensure compliance with these IS codes and maintain regular inspections to mitigate fire hazards in tea factories.
1. Fire Extinguishers:
2. Hydrant Systems:
3. Fire Safety Design Considerations:
| Extinguisher Type | Capacity | Relevant IS Code |
|---|---|---|
| CO2 Squeeze Grip Type | 2 kg, 5 kg (typical) | IS 2878 |
| Mechanical Foam | 9 liters | IS 10204:1982 |
flowchart LR
A[Fire Safety System] --> B[Internal Hydrant System]
A --> C[External Hydrant System]
B -->|IS 3844:1989| D[Design & Installation]
C -->|IS 13039:1991| E[Design & Installation]
Note: These provisions supplement statutory requirements like the Indian Factories Act (1948) and Petroleum Rules (1976).
IS 4886:1991 - List of Referenced Indian Standards (Annex A, Clause 2.1)
This clause lists essential Indian Standards that complement IS 4886 for fire safety and related materials:
| IS No. | Title |
|---|---|
| 940 : 1989 | Portable chemical fire extinguisher, water type (gas pressure) (3rd revision) |
| 1239 (Part 1):1979 | Mild steel tubes, tubulars and other wrought steel fittings: Part 1 Mild steel tubes |
| 1239 (Part 2):1982 | Mild steel tubulars and other wrought steel pipe fittings (3rd revision) |
| 1642 : 1989 | Code of practice for fire safety of buildings (general): Materials and construction (1st revision) |
| 1646 : 1978 | Code of practice for fire safety of buildings (general): Electrical installations (1st revision) |
| 2190 : 1979 | Code of practice for selection, installation and maintenance of portable fire extinguisher (2nd revision) |
| 3594 : 1989 | Code of practice for fire safety of industrial buildings: General storage and warehousing (1st revision) |
| 3884 : 1989 | Canned tomato paste (1st revision) |
| 9668 : 1980 | Code of practice for provision and maintenance of water supplies for fire fighting |
| 10204 : 1982 | Portable fire extinguisher mechanical foam type |
| 11108 : 1984 | Portable fire extinguisher - Halon 1211 type |
| 12777 : 1989 | Fire safety - Flame spread of products - Method for Classification |
| 13039 : 1991 | Code of practice for provision and maintenance of external fire hydrant system |
For detailed application, refer to the individual IS codes listed above.
flowchart LR
IS
Frequently Asked
Recommended Construction Materials for Withering Houses (IS 4886):
| Material Type | Requirement |
|---|---|
| Structural Frame | Type 3 fire-resistive construction (IS 1642) |
| Racks/Hessian | Avoid; if used, treat chemically (Class I, IS12777) |
| Floor Area | ≤ 2,000 m² if combustible racks are used |
| Separation Distance | ≥ 10 m or fire-separating wall (clause 8.2) |
Loading diagram...
This ensures fire safety by limiting combustible content and enhancing fire resistance.
Installation & Maintenance of Natural Gas Supply for Tea Drying Machines (IS 4886: Clause 9.2)
Gas Supply Source:
Supply must come from a recognized gas authority ensuring constant calorific value and adequate pressure (9.2.1).
Service Fuel Tank Location (9.1.3):
Piping Installation (9.2.3 & 9.1.3):
Maintenance:
Loading diagram...
This ensures safe, reliable, and code-compliant natural gas supply for tea drying machines.
Fire Fighting Equipment & Hydrant Systems for Tea Factories (IS 4886)
Location & Access (Clause 4.1):
Water Supply (Clause 12.1a):
Portable Fire Extinguishers (Clause 12.1b):
Electrical Safety (Clause 11.6):
| Equipment | Standard | Details |
|---|---|---|
| Water supply | IS 9668:1980 | Adequate quantity for fire fighting |
| Portable extinguishers | IS 2190:1979 | Water gas pressure type, 9 L (IS 940:1989) |
| Access roads | IS 4886 Clause 4.1 | Minimum 3.6 m width, all-weather |
| Lamp fittings | IS 4886 Clause 11.6 | Dust-tight near heat sources |
This ensures effective fire fighting readiness tailored for tea factory hazards.
Clearance Distances as per IS 4886:
Bulk Storage Tanks:
Factory Buildings and Storage:
| Item | Minimum Clearance Distance |
|---|---|
| Bulk storage tank (above ground) | 15 m |
| Bulk storage tank (embedded type) | 6 m |
| Storage/process buildings to coal-fired railway | 30 m (or protected openings + 15 m clear zone) |
| Godowns to factory buildings | 6 m |
| Fuel (coal, wood) storage excess | 10 m |
This ensures fire safety and prevents hazards from fuel storage near buildings and other structures.
Loading diagram...
To minimize fire hazards in tea factories as per IS 4886, focus on electrical installations as follows:
These measures reduce ignition sources and improve fire response readiness in tea factories.