Methods of physical tests for hydraulic cement, Part 5: Determination of initial and final setting times

IS 4031 Part 5 (1988) specifies the standardized procedure for determining the initial and final setting times of hydraulic cement using the Vicat apparatus. This method ensures consistent evaluation of cement setting characteristics critical for construction quality control. It applies to cement manufacturers, quality assurance engineers, and laboratory technicians involved in cement testing and compliance verification.

6Sections
30Clauses Indexed
AI Search Ready
1988Edition
Cement Concrete Aggregates and RCCCategory
Alternative search terms: IS 4031 Part 5 PDF, IS 4031 Part 5 pdf free download, IS 4031 Part 5 free download pdf, IS4031Part5 PDF, IS-4031-Part-5 PDF, IS 4031 Part 5 1988 PDF, IS 4031 Part 5:1988 PDF, IS 4031 Part 5-1988 PDF, IS 4031 Part 5 (1988) PDF, IS 4031 Part 5 1988 edition PDF, IS 4031 Part 5 edition 1988 PDF

What This Standard Covers

IS 4031 Part 5 (1988) specifies the standardized procedure for determining the initial and final setting times of hydraulic cement using the Vicat apparatus. This method ensures consistent evaluation of cement setting characteristics critical for construction quality control. It applies to cement manufacturers, quality assurance engineers, and laboratory technicians involved in cement testing and compliance verification.

Who Uses This Standard

  • Cement manufacturing engineers
  • Quality control laboratory technicians
  • Civil engineers
  • Construction material testing professionals
  • Research and development scientists in cement technology
  • Regulatory compliance officers
  • Concrete technologists

Key Topics Covered

Sampling and selection of cement specimens
Environmental conditions for testing (temperature and humidity)
Preparation of cement paste and test blocks
Use and specifications of Vicat apparatus
Procedure for determining initial setting time
Procedure for determining final setting time
Standard weights and balance requirements
Reporting and rounding off test results
Maintenance of moist room or moist closet
Handling and calibration of testing equipment
Use of gauging trowel
Interpretation of needle penetration results

Table of Contents

1Scope

IS 4031 Part 5 - Scope: Key Points and Specifications

  • Scope: This part covers methods for physical tests on hydraulic cement, focusing on setting times and related procedures.

  • Rounding Off (Clause 0.5):
    Test results must be rounded per IS 2-1960 rules, retaining the same significant figures as specified values.

  • Permissible Variation on Weights (Clause 4.3, Table 1):
    Weights used for cement testing have strict permissible variations:

Weight (g)Permissible Variation (g)
500±0.35
300±0.30
250±0.25
200±0.20
100±0.15
50±0.10
20±0.05
10±0.04
5±0.03
2±0.02
1±0.01
  • Reporting Results (Clause 6.1):
    Initial and final setting times must be reported to the nearest 5 minutes.

  • Balance Requirements (Clause 4.2):
    The balance used must meet accuracy standards compatible with the permissible weight variations.


Summary Diagram: Cement Testing Process Scope

flowchart TD
    A[Start: Cement Sample] --> B[Weighing with Standard Weights]
    B --> C{Weight Within Permissible Variation?}
    C -- Yes --> D[Conduct Physical Tests]
    C -- No --> B
    D --> E[Record Setting Times]
    E --> F[Round off Results (IS 2-1960)]
    F --> G[Report Results (nearest 5 mins)]

This standard ensures accuracy and consistency in cement testing by specifying equipment tolerances, rounding rules, and reporting precision.

2Sampling and Selection of Test Specimen

IS 4031 Part 5: Sampling & Selection of Test Specimen for Setting Time of Cement

Key Points from Clause 2.1 & Related Clauses:

  • Sampling Procedure:

    • Samples must be taken as per IS 3535-1986 and relevant cement type standards.
    • The sample should be representative and thoroughly mixed before testing.
  • Specimen Selection:

    • No explicit specimen size/formula given in this part; follow IS 4031 Part 4 for mould specifications.
    • Use standard moulds as per IS specifications for test specimens.
  • Rounding Off Results:

    • Follow IS 2-1960 rules for rounding numerical results.
    • Report setting times to the nearest 5 minutes (Clause 6.1).

Summary Table for Sampling & Testing:

AspectSpecification/Reference
Sampling MethodIS 3535-1986
Sample PreparationThorough mixing
Test Specimen MouldAs per IS 4031 Part 4
Rounding of Test ResultsIS 2-1960 (round to nearest 5 min)

Additional Notes:

  • Ensure temperature and humidity control during testing as per IS 4031 Part 5.
  • The initial and final setting times are determined on standard cement paste prepared from the sampled cement.
flowchart TD
    A[Sampling of Cement] --> B[Representative Sample per IS 3535]
    B --> C[Thorough Mixing]
    C --> D[Prepare Standard Paste]
    D --> E[Test Specimen in Standard Mould (IS 4031 Part 4)]
    E --> F[Determine Initial & Final Setting Times]
    F --> G[Round off Results (IS 2-1960)]
    G --> H[Report Results to Nearest 5 Minutes]

This concise guide ensures compliance with IS 4031 Part 5 for sampling and specimen selection in setting time tests.

3Temperature and Humidity

IS 4031 Part 5: Temperature and Humidity Specifications

  • Moulding Room & Materials Temperature:
    Maintain at 27 ± 2°C (Clause 3.1).

  • Laboratory Relative Humidity:
    Maintain at 65 ± 5% (Clause 3.1).

  • Moist Closet / Moist Room Conditions:
    Maintain at 27 ± 2°C and ≥ 90% relative humidity (Clause 3.2).


Key Points:

  • Temperature and humidity control is critical for consistent cement testing, especially for initial and final setting times.
  • Samples must be representative and thoroughly mixed (Clause 2.1).
  • Rounding off test results should follow IS 2-1960 rules for numerical precision.

Summary Table:

Location/EquipmentTemperature (°C)Relative Humidity (%)
Moulding Room27 ± 265 ± 5
Moist Closet/Room27 ± 2≥ 90

This ensures reproducibility and accuracy in cement testing as per IS 4031 Part 5.

4Apparatus and Equipment

IS 4031 Part 5 (1988) - Apparatus and Equipment for Cement Testing

Key Specifications:

  • Temperature & Humidity for Testing:

    • Moulding room, dry materials, water: 27 ± 2°C
    • Laboratory relative humidity: 65 ± 5%
  • Balance Requirements:

    • Permissible variation at 1000 g load: ± 1.0 g
    • For new balance: half of above, i.e., ± 0.5 g
    • Sensibility reciprocal ≤ twice permissible variation
    • Self-indicating balances with equivalent accuracy are allowed
  • Vicat Apparatus:

    • Must conform to IS 5513:1976
    • Used for determination of initial and final setting times of cement

Rounding Off Results:

  • Follow IS 2:1960 rules for rounding numerical values.
  • Retain the same number of significant figures as specified in the standard.

Summary Table:

ParameterSpecification
Temperature27 ± 2°C
Relative Humidity65 ± 5%
Balance Variation±1.0 g (used), ±0.5 g (new)
Vicat Apparatus StandardIS 5513:1976

flowchart TD
    A[Testing Environment] --> B{Conditions}
    B -->|Temp| C[27 ± 2°C]
    B -->|Humidity| D[65 ± 5%]
    A --> E[Equipment]
    E --> F[Balance]
    F --> G[±1.0 g variation at 1000 g]
    E --> H[Vicat Apparatus]
    H --> I[IS 5513:1976]

This ensures reproducible and accurate cement testing results as per IS 4031 Part 5.

5Test Procedure

IS 4031 Part 5: Test Procedure for Initial and Final Setting Time of Cement

Key Points from the Code:

  • Scope (Clause 1.1): Procedure to determine initial and final setting times of cement.
  • Rounding Off (Clause 0.5): Results are rounded per IS 2-1960 rules, retaining the same significant figures as specified.
  • Reporting (Clause 6.1): Setting times reported to the nearest 5 minutes.
  • Balance Requirements (Clause 4.2): Balance must meet specified accuracy (usually ±0.01 g or better).

Test Procedure Overview:

  1. Prepare Standard Cement Paste (per IS 4031 Part 4):
    • Mix cement with water at a specified ratio to form a paste.
  2. Filling the Vicat Mould:
    • Use standard moulds as per specifications.
  3. Penetration Test:
    • Use Vicat apparatus with a specified needle.
    • Measure penetration at intervals to determine:
      • Initial Setting Time: When needle penetration is 25 mm.
      • Final Setting Time: When needle fails to penetrate 0.5 mm from bottom.
  4. Record Times:
    • Start timing immediately after mixing.
    • Report times to nearest 5 minutes.

Summary Table: Setting Time Criteria

Setting Time TypePenetration CriterionReporting Accuracy
Initial SettingNeedle penetrates 25 mmNearest 5 minutes
Final SettingNeedle does not penetrate 0.5 mmNearest 5 minutes

Notes:

  • Use a balance accurate to 0.01 g for weighing cement and water.
  • Follow IS 2-1960 for rounding off numerical results.
  • Ensure environmental conditions (temperature, humidity) are controlled as per standard.
flowchart TD
    A[Start Mixing Cement Paste] --> B[Fill Vicat Mould]
    B --> C[Insert Needle]
    C --> D{Needle Penetration}
    D -->|25 mm| E[Record Initial Setting Time]
    D -->|< 0.5 mm| F[Record Final Setting Time]
    E --> G[Report Results (nearest 5 min)]
   
6Reporting of Results

IS 4031 Part 5 - Reporting of Results: Key Points

  • Rounding of Results (Clause 2.1):
    Final values for setting times must be rounded off according to IS 2-1960 rules. The number of significant digits in the reported value should match the standard's specified value.

  • Setting Time Reporting (Clause 6.1):
    Initial and final setting times shall be reported to the nearest 5 minutes.

  • Permissible Variation on Weights (Clause 4.3, Table 1):
    Weights used for weighing cement must conform to the permissible variations:

Weight (g)Permissible Variation (g)
500±0.35
300±0.30
250±0.25
200±0.20
100±0.15
50±0.10
20±0.05
10±0.04
5±0.03
2±0.02
1±0.01

Summary for Reporting:

  • Report initial and final setting times rounded to nearest 5 minutes.
  • Use weights within permissible tolerance for accuracy.
  • Follow rounding rules per IS 2-1960.
flowchart TD
    A[Conduct Setting Time Test] --> B[Record Initial Setting Time]
    B --> C[Round to nearest 5 minutes]
    A --> D[Record Final Setting Time]
    D --> E[Round to nearest 5 minutes]
    C --> F[Report Results]
    E --> F
    F --> G[Ensure weights used conform to permissible variation]

This ensures consistency, accuracy, and compliance with IS 4031 Part 5 standards.

Popular Questions About IS 4031 Part 5

?What is the required temperature and humidity for conducting the setting time test?

According to IS 4031 Part 5, the required environmental conditions for conducting the cement setting time test are:

  • Temperature: Maintain at 27 ± 2°C for the moulding room, dry materials, and water.
  • Relative Humidity: Maintain at 65 ± 5% in the laboratory.

Additional points:

  • Immediately after moulding, the test block should be placed in a moist closet or moist room to maintain moisture.
  • Use clean, vibration-free apparatus.
  • Keep the needle straight during penetration tests.

This ensures consistent and reproducible initial and final setting time measurements.

Loading diagram...

This setup aligns with IS 4031 Part 5 Clause 3.1 and 5.1.1 requirements.

?How is the initial setting time of cement determined using the Vicat apparatus?

Initial Setting Time Determination Using Vicat Apparatus (IS 4031 Part 5)

  1. Preparation of Test Block (Clause 5.1):

    • Mix cement with 0.85 × water for standard consistency (use potable/distilled water).
    • Fill the Vicat mould (E) resting on a non-porous plate with this paste, level the surface.
    • Start stopwatch when water is added.
  2. Testing Procedure (Clause 5.2):

    • Place the test block under the Vicat needle (needle C).
    • Lower needle gently until it touches the surface, then release to penetrate the paste.
    • Initially, needle penetrates fully. Repeat at intervals.
    • The initial setting time is when the needle fails to penetrate beyond 5.0 ± 0.5 mm from the bottom of the mould.

Summary Table

StepDescription
Water-to-cement ratio0.85 × standard consistency water
Needle usedNeedle C (without annular attachment)
Penetration limit for initial set5.0 ± 0.5 mm from mould bottom
Start timeWhen water is added to cement
Loading diagram...

This method ensures standardized measurement of the initial setting time of cement.

?What are the specifications for the Vicat apparatus and related equipment?

Vicat Apparatus Specifications (IS 4031 Part 5 referencing IS 5513-1976):

  • The Vicat apparatus must conform to IS 5513-1976, ensuring standard dimensions and accuracy.
  • Key components include:
    • Needle (C) for initial penetration.
    • Needle with annular attachment (F) for final setting time.
    • Vicat mould (E): used to prepare the cement test block.
  • Test conditions:
    • Temperature: 27 ± 2°C
    • Relative humidity: 65 ± 5%
  • Cement paste is prepared with 0.85 times the water for standard consistency.
  • Test block is formed by filling the Vicat mould resting on a non-porous plate, surface leveled.
  • Final setting time is when the needle makes an impression but the annular attachment does not.

Summary Table

ParameterSpecification
Apparatus StandardIS 5513-1976
Test Block Water Content0.85 × water for standard consistency
Test Temperature27 ± 2°C
Relative Humidity65 ± 5%
MouldVicat mould (E), non-porous plate
Needle TypesPlain (C) and annular attachment (F)
Loading diagram...

This ensures repeatability and accuracy in determining initial and final setting times.

?How should the cement paste be prepared for the setting time test?

Preparation of Cement Paste for Setting Time Test (IS 4031 Part 5, Clause 5.1):

  • Water Quantity: Use 0.85 times the water required for standard consistency (as per IS 4031 Part 4).
  • Water Type: Use potable or distilled water.
  • Mixing: Start a stopwatch the moment water is added to cement. Mix thoroughly to get a neat paste.
  • Mould Filling: Fill the Vicat mould completely with the paste, resting on a non-porous plate.
  • Surface Finish: Smooth off the surface so it is level with the top of the mould.
  • Test Block: This paste-filled mould is the test block for setting time determination.

This ensures consistent paste consistency and timing for accurate initial and final setting time measurement.

Loading diagram...
?What is the procedure to determine the final setting time of hydraulic cement?

Procedure to Determine Final Setting Time of Hydraulic Cement (IS 4031 Part 5, Clause 5.3):

  1. Replace Vicat Needle:

    • Remove the standard needle (C).
    • Fit the needle with an annular attachment (F).
  2. Test Block Preparation:

    • Prepare cement paste and cast into the Vicat mould.
    • Start timing from the moment water is added to cement.
  3. Testing:

    • Gently lower the annular needle onto the surface of the test block.
    • The final setting time is reached when the needle makes an impression on the surface but the annular attachment fails to do so.
  4. Special Case:

    • If a scum forms on the surface, use the underside of the test block for testing.
  5. Result:

    • The elapsed time from mixing to this point is the final setting time.

Summary Table:

StepAction
Needle ReplacementUse annular needle (F) instead of needle (C)
Test BlockCement paste in mould
Final Set CriterionNeedle penetrates; annular attachment does not
Time MeasurementFrom water addition to final set condition
Loading diagram...

This method ensures precise determination of the final setting time per IS 4031 Part 5.