Code of practice for fire safety of industrial buildings: General storage and warehousing including cold storage

IS 3594:1991 provides comprehensive fire safety guidelines specifically for industrial buildings used as general storage, warehousing, and cold storage facilities. It addresses fire prevention, detection, and control measures tailored to the unique hazards of stored materials, building design, and operational practices. This standard is essential for engineers, safety professionals, and facility managers involved in designing, operating, or maintaining fire-safe storage and cold storage warehouses in India.

15Sections
157Clauses Indexed
AI Search Ready
1991Edition
Fire SafetyCategory
Alternative search terms: IS 3594 PDF, IS 3594 pdf free download, IS 3594 free download pdf, IS3594 PDF, IS-3594 PDF, IS 3594 1991 PDF, IS 3594:1991 PDF, IS 3594-1991 PDF, IS 3594 (1991) PDF, IS 3594 1991 edition PDF, IS 3594 edition 1991 PDF

What This Standard Covers

IS 3594:1991 provides comprehensive fire safety guidelines specifically for industrial buildings used as general storage, warehousing, and cold storage facilities. It addresses fire prevention, detection, and control measures tailored to the unique hazards of stored materials, building design, and operational practices. This standard is essential for engineers, safety professionals, and facility managers involved in designing, operating, or maintaining fire-safe storage and cold storage warehouses in India.

Who Uses This Standard

  • Fire Safety Engineers
  • Warehouse Facility Managers
  • Industrial Building Designers
  • Cold Storage Operators
  • Safety Compliance Officers
  • Fire Protection System Installers
  • Industrial Risk Assessors

Key Topics Covered

Fire-resistant construction and compartmentation
Storage arrangements for hazardous and non-hazardous goods
Minimum separation distances between godowns
Fire detection and alarm systems requirements
Automatic sprinkler system design and application
Smoke ventilation and smoke vent installation
Electrical safety and flame-proof equipment
Outdoor storage regulations and clearance
Handling and storage of materials prone to water damage
Fire fighting water supply and hydrant systems
Illumination standards for storage areas
Fire safety in cold storage warehouses
Prohibition of hazardous operations within storage areas
Inspection and maintenance protocols for godowns
Segregation and stacking height limitations

Table of Contents

1Scope

IS 3594 - Scope Overview & Key References

Scope:
IS 3594 primarily deals with safety provisions related to specific building services and installations. It references several related Indian Standards essential for comprehensive safety compliance.


Key Referenced IS Codes (Annex A - Clause 2.1)

IS No.Title
659:1964Safety code for air conditioning (revised)
660:1963Safety code for mechanical refrigeration (revised)
1641:1988Code of practice for safety of buildings (general): Fire grading and classification
1642:1989Code of practice for fire safety of buildings (general): Details of construction
1646:1982Code of practice for fire safety of buildings (general): Electrical installations
2189:1988Code of practice for automatic fire detection and alarm system (second revision)
2190:1979Code of practice for portable first-aid fire extinguisher (second revision)
3614(Part1):1966Specification for fire check doors: Plate, metal covered and rolling type
9668:1980Code of practice for provision and maintenance of water supplies for fire fighting

Notes:

  • These codes cover fire safety, mechanical refrigeration, air conditioning, fire detection, extinguishers, and water supply for firefighting.
  • IS 3594 is a complementary standard, requiring adherence to these codes for holistic safety.
  • For detailed design, installation, and maintenance, consult the respective IS codes above.

Summary Diagram: Scope & Related IS Codes

graph LR
    A[IS 3594 Scope] --> B[Air Conditioning Safety (IS 659)]
    A --> C[Mechanical Refrigeration Safety (IS 660)]
    A --> D[Fire Safety of Buildings (IS 1641, 1642, 1646)]
    A --> E[Fire Detection & Alarm (IS 2189)]
    A --> F[Fire Extinguishers (IS 2190)]
    A --> G[Fire Check Doors (IS 3614 Part 1)]
    A
2Referenced Indian Standards

IS 3594: Referenced Indian Standards (Clause 2.1 & Annex A)

This standard refers to essential Indian Standards related to fire safety, air conditioning, refrigeration, and fire-fighting equipment:

IS No.Title
IS 659:1964Safety code for air conditioning (revised)
IS 660:1963Safety code for mechanical refrigeration (revised)
IS 1641:1988Code of practice for safety of buildings: Fire grading and classification (1st revision)
IS 1642:1989Code of practice for fire safety of buildings: Details of construction (1st revision)
IS 1646:1982Code of practice for fire safety of buildings: Electrical installations (1st revision)
IS 2189:1988Code of practice for automatic fire detection and alarm system (2nd revision)
IS 2190:1979Code of practice for portable first-aid fire extinguisher (2nd revision)
IS 3614(Part1):1966Specification for fire check doors: Plate, metal covered and rolling type
IS 9668:1980Code of practice for provision and maintenance of water supplies for fire fighting

Key Notes:

  • These standards complement IS 3594 for comprehensive fire safety and mechanical system safety.
  • Compliance with these referenced IS codes ensures adherence to best practices in design, installation, and maintenance.
  • For detailed requirements, refer to each IS document individually.

flowchart LR
    A[IS 3594] --> B[IS 659: Air Conditioning Safety]
    A --> C[IS 660: Mechanical Refrigeration Safety]
    A --> D[IS 1641/1642/1646: Fire Safety of Buildings]
    A --> E[IS 2189: Fire Detection & Alarm]
    A --> F[IS 2190: Fire Extinguishers]
    A --> G[IS 3614: Fire Check Doors]
    A --> H[IS 9668: Water Supply for Fire Fighting]

For full compliance, consult the latest editions of these standards from BIS.

3Definitions

IS 3594 - Definitions & Key Specifications

  • Clause 3.0: Defines terms used in the code for clarity and uniformity.
  • Annex A (Clause 2.1): Lists related Indian Standards essential for comprehensive application:
    • IS 659: Safety code for air conditioning
    • IS 660: Safety code for mechanical refrigeration
    • IS 1641, 1642, 1646: Fire safety codes for buildings (general)
    • IS 2189, 2190: Fire detection, alarm systems, and portable fire extinguishers
    • IS 3614 (Part 1): Fire check doors specification
    • IS 9668: Water supplies for fire fighting

Important Notes:

  • These referenced standards complement IS 3594 for holistic safety and fire protection design.
  • Definitions ensure consistent interpretation across these standards.
  • Contact BIS regional offices for detailed code clarifications or updates.

Summary Table of Key Referenced IS Codes

IS No.Title
659:1964Safety code for air conditioning (revised)
660:1963Safety code for mechanical refrigeration (revised)
1641:1988Fire grading & classification (first revision)
1642:1989Fire safety of buildings - construction details
1646:1982Fire safety - electrical installations
2189:1988Fire detection and alarm systems
2190:1979Portable fire extinguisher maintenance
3614 (Pt1)Fire check doors specification
9668:1980Water supplies for fire fighting

For practical engineering use, always cross-reference these IS codes for detailed definitions and safety provisions when applying IS 3594.

4Site Selection and Layout

IS 3594: Site Selection and Layout - Key Points

1. Site Distance from Railways (Clause 4.2)

  • Buildings and open storage must be ≥ 50 m away from railway lines, sidings, or yards with locomotives to avoid vibration and safety hazards.

2. Compound Area (Clause 5.1 & 8)

  • When storage buildings have their own compound, the compound area should meet the specifications in Clause 8 (refer to IS 3594 for detailed area requirements based on storage type and capacity).

3. Floor Areas (Clause 6.1.1)

  • Floor areas must be designed considering:
    • Storage capacity
    • Handling equipment
    • Movement space for loading/unloading

4. Cold Storage Buildings (Clause 6.2)

  • Special layout considerations include:
    • Thermal insulation zones
    • Air circulation paths
    • Proximity to power and water supply

Summary Table: Minimum Distances and Areas

ParameterMinimum Distance / Area
Distance from Railway Lines≥ 50 m
Compound Area (per Clause 8)As per storage capacity & type
Floor AreaBased on storage and handling

flowchart LR
    A[Site Selection] --> B[Distance from Railway ≥ 50m]
    A --> C[Compound Area as per Clause 8]
    A --> D[Floor Area per Storage Needs]
    A --> E[Cold Storage Layout Considerations]
    E --> F[Thermal Insulation]
    E --> G[Air Circulation]
    E --> H[Utility Proximity]

For detailed dimensions and layout, refer directly to IS 3594 Clause 8 and related sub-clauses.

5Building Construction and Compartmentation

IS 3594: Building Construction & Compartmentation Key Points

1. Compartmentation (Clauses 6.1.1.2, 6.2.3)

  • Max compartment area per floor:
    • Storeyed floors: As per 6.1.1.1 (not specified here)
    • Basement floors: ≤ 500 m²
    • Individual compartment (divided by separating walls): ≤ 750 m²
  • Floors must have 2-hour fire resistance.
  • Openings in floors must be protected to maintain 2-hour fire resistance.

2. Roadways & Access (Clause 5.2)

  • Roadways alongside godowns: ≥ 5 m wide (for fire engine manoeuvring).
  • Compound gates: ≥ 4.5 m wide with sufficient headroom.

3. Fire Protection Systems (Clause 6.2.7)

  • If no automatic sprinklers, install automatic fire alarm system per IS 2189:1988.
  • Alarm system should cover area above false ceilings and walls.

Summary Table

ParameterRequirement
Max compartment areaStoreyed: per 6.1.1.1
Basement: ≤ 500 m²
Individual compartment≤ 750 m²
Floor fire resistance2 hours
Opening fire resistanceEqual to floor (2 hours)
Roadway width≥ 5 m
Compound gate width≥ 4.5 m
Fire alarm systemAs per IS 2189:1988

flowchart TD
    A[Storeyed Floor] -->|Compartmented| B[Compartment ≤ 750 m²]
    A --> C[Floor Fire Resistance 2 hrs]
    D[Basement Floor] -->|Compartment ≤ 500 m²| E[Compartment]
    F[Roadway] -->|≥ 5 m wide| G[Fire Engine Access]
    H[Compound Gate] -->|≥ 4.5 m wide| I[Fire Engine Passage]
    J[Fire Protection] -->|No sprinklers| K[Automatic Fire Alarm (IS 2189)]
6Fire Resistance and Separating Walls

IS 3594: Fire Resistance & Separating Walls - Key Points

Fire Resistance & Separating Walls (Clauses 3.5, 7, 15.0)

  • Separating Walls must comply with IS 1642:1989 specifications.
  • For facing godowns:
    • Distance > 15 m between walls.
    • One wall must be a separating wall: fully blank (no openings).
    • Openings in facing walls require:
      • Fire check doors or wired glass (approved type).
      • A drencher system for fire protection.
  • Storage compartments formed by separating walls should not exceed 750 m³ floor area.

Fire Alarm & Sprinkler Systems (Clause 6.2.7)

  • If automatic sprinklers are not mandatory, install an automatic fire alarm system per IS 2189:1988, covering areas above false ceilings.

Summary Table

ParameterRequirement
Min distance between godowns> 15 m
Separating wallMust be blank, no openings
Openings protectionFire check doors/wired glass + drencher system
Max storage compartment volume750 m³
Fire alarm systemIS 2189 compliant if no sprinklers

flowchart TD
    A[Facing Godowns] -->|Distance > 15m| B[Separating Wall (Blank)]
    B --> C[Storage Compartments ≤ 750 m³]
    A --> D[Openings in walls]
    D --> E[Fire Check Doors/Wired Glass + Drencher System]
    F[Fire Alarm System] -->|If no sprinklers| G[IS 2189 compliant]

This ensures compartmentalization and fire safety per IS 3594.

7Storage Arrangements and Segregation

IS 3594 - Storage Arrangements and Segregation (Clause 9.5)

Key Points on Segregation of Materials:

  • 9.5.1: Hazardous & extra-hazardous materials must be segregated from each other and from non-hazardous materials.

  • 9.5.2: Materials hazardous in combination must be stored separately in segregated areas to prevent dangerous reactions.

  • 9.5.7: Fire hazard characteristics of materials should be identified in advance. If unknown, assume materials are hazardous and segregate accordingly.


Practical Guidelines:

Material TypeSegregation Requirement
Hazardous + Extra-hazardousSeparate storage zones with physical barriers
Incompatible materialsMinimum distance or fire-resistant partitions
Unknown hazard materialsTreat as hazardous; segregate accordingly

Additional Notes:

  • Specific commodities like rubber, gases, acids, flammable liquids require special safety codes (not covered here).
  • Segregation reduces risk of fire, explosion, or chemical reaction.
  • Use fire-resistant walls, distance, and ventilation to enhance safety.

graph LR
A[Hazardous Materials] -->|Separate| B[Extra-Hazardous Materials]
A -->|Separate| C[Non-Hazardous Materials]
D[Incompatible Materials] -.->|Physical Barrier/Distance| A
E[Unknown Hazard] -->|Assume Hazardous| A

For detailed design, consult IS 15905 (flammable liquids), IS 14687 (chemical storage), and relevant fire safety codes.

8Outdoor Storage and Clearance Requirements

IS 3594: Outdoor Storage and Clearance Requirements

Key Specifications

  • Minimum clearance from godown/warehouse:

    • 15.0 m if outdoor storage faces doors/windows without fire protection.
    • 6.0 m minimum clearance in any case to avoid obstruction of access.
  • Fire protection requirements if within 15.0 m:

    • Doorways must have fire-resistant doors/shutters or a drencher system.
    • Windows/openings must be protected with wired glass or a drencher system.
  • Exception: Clearance rules can be waived if stored materials are non-combustible (subject to authority approval).

Summary Table

ConditionMinimum ClearanceFire Protection Required?
Outdoor storage near godown≥ 15.0 mNo (if clearance maintained)
Outdoor storage < 15.0 m≥ 6.0 mYes (fire-resistant doors/shutters, wired glass or drencher system)
Obstruction of accessNot allowed < 6.0 mN/A
Non-combustible materials storageAs per authorityMay be waived

Visual Concept

flowchart LR
    A[Godown/Warehouse] -->|≥ 15 m| B[Outdoor Storage (No fire protection needed)]
    A -->|< 15 m & ≥ 6 m| C[Outdoor Storage (Fire protection required)]
    A -->|< 6 m| D[No outdoor storage allowed (Access blocked)]

Note: Always verify local authority approvals for exceptions and specific fire safety systems.

9Fire Detection and Alarm Systems

Key Specifications for Fire Detection & Alarm Systems (IS 3594 referencing IS 2189:1988):

  • Automatic Fire Alarm System is mandatory unless the godown has an automatic sprinkler system.
  • For large open areas, a well-designed manual fire alarm system is acceptable.
  • When sprinklers are not required, install an automatic fire alarm system covering areas above false ceilings and walls.
  • Fire compartments should not exceed 750 m²; can increase to 2250 m² if sprinklers are installed.

Relevant IS Code Reference Table

IS No.Title
2189:1988Code of practice for selection, installation and maintenance of automatic fire detection and alarm system
2190:1979Portable first-aid fire extinguisher
9668:1980Provision and maintenance of water supplies for firefighting

Fire Alarm System Design Considerations:

  • Early detection reduces damage.
  • Cover all compartments, especially above false ceilings.
  • Use automatic detection where possible.
  • Manual alarm systems for large open spaces without sprinklers.

Simplified Fire Alarm System Layout

flowchart TD
    A[Fire Detection Sensors] --> B[Fire Alarm Control Panel]
    B --> C[Alarm Sounders & Visual Indicators]
    B --> D[Sprinkler System (if installed)]
    B --> E[Manual Call Points]

Summary:
Use IS 2189:1988 for detailed design. Automatic fire alarms are essential unless sprinklers exist. Compartment size limits ensure effective alarm coverage. Manual alarms suffice for large open areas without sprinklers.

10Mechanical and Electrical Equipment Safety

IS 3594: Mechanical & Electrical Equipment Safety - Key Points

Mechanical Equipment Safety (Clause 10)

  • Mechanical Handling Equipment (10.1): Must follow safety practices to prevent accidents.
  • Refrigeration Equipment (10.2.1):
    • Must comply with IS 660:1963 (Safety code for mechanical refrigeration).
    • Electrical wiring per IS 659:1964 (Safety code for air conditioning).
  • Refrigerants (10.2.2): Use only non-combustible refrigerants for safety.

Electrical Installations (Clause 11)

  • Refer to IS 1646:1982 for fire safety of electrical installations.
  • Follow IS 659:1964 for wiring safety in mechanical refrigeration and air conditioning.
  • Ensure compliance with fire grading, classification, and fire fighting provisions from IS 1641, IS 1642, IS 9668.

Important IS Codes for Safety Compliance

IS No.Title
IS 659:1964Safety code for air conditioning (revised)
IS 660:1963Safety code for mechanical refrigeration (revised)
IS 1641:1988Fire grading and classification (general)
IS 1642:1989Fire safety of buildings (details of construction)
IS 1646:1982Fire safety of buildings (electrical installations)
IS 9668:1980Provision and maintenance of water supplies for fire fighting

Summary Diagram: Safety Compliance Flow

flowchart TD
    A[Mechanical Equipment] --> B[IS 660:1963]
    A --> C[IS 659:1964 (Wiring)]
    D[Refrigerants] --> E[Non-combustible only]
    F[Electrical Installations] --> G[IS 1646:1982]
    F --> H[Fire Safety Codes (IS 1641,1642,9668)]

Note: Always cross-check equipment and installation with the relevant IS codes listed above for detailed safety requirements.

11Fire Fighting Arrangements and Water Supply

IS 3594: Fire Fighting Arrangements & Water Supply – Key Points

Water Supply System (Clause 13.1.2)

  • Storage Area > 750 m² (indoor) or > 2000 m² (outdoor):
    Provide a water supply system with fire hydrants & static water tanks per IS 9668:1980.
  • Smaller premises (>8 km from fire station):
    At least one self-fed static water tank ≥ 125,000 litres with access & hardstanding for fire engines.

Fire Brigade (Clause 13.5)

  • For large, hazardous, or critical storage installations:
    Provide a full-time Fire Brigade with major firefighting equipment.
    Details to be worked out case-by-case.

Equipment Location (Clause 13.6)

  • Mark locations of hydrant valves, landing valves, hand appliances on building plans.
  • Display prominently at godown entrances.

Maintenance (Clause 13.4)

  • Fixed fire protection systems must undergo periodical inspection and maintenance, possibly via approved maintenance contracts.

Summary Table: Water Tank Capacity Requirements

Premises TypeArea ThresholdWater Tank Capacity
Indoor storage> 750 m²Per IS 9668:1980 standards
Outdoor storage> 2000 m²Per IS 9668:1980 standards
Smaller premises (>8 km fire station)Any size≥ 125,000 litres

flowchart LR
    A[Storage Premises] --> B{Area & Location}
    B -->|Indoor > 750 m² or Outdoor > 2000 m²| C[Fire Hydrants + Static Tanks (IS 9668)]
    B -->|Smaller & >8 km from fire station| D[Self-fed Static Tank ≥125,000 L]
    B -->|Large Hazardous Installations| E[Full-time Fire Brigade]
    C & D & E --> F[Maintenance & Inspection]
    F --> G[Marked Equipment Locations]

Note: Refer IS 9668:1980 for detailed tank sizing, hydrant spacing, and pipe sizing.

12Illumination Requirements

IS 3594 - Illumination Requirements Summary

  • Minimum Illumination:
    Clause 12.1 specifies that all godowns must have a minimum illumination of 50 lux to ensure safe and efficient operations.

  • Lighting Fixture Clearance:
    Per Clause 11.2.3.1, all light fittings must maintain a minimum clearance of 75 cm from the highest stacking level to prevent damage and ensure uniform lighting.

  • Wiring Requirements:
    Clause 11.4.4 mandates that all wiring (except for bars, copper collectors, or trolley wires) must be enclosed in screwed steel conduits for safety and durability.


Typical Illumination Levels (IS 3646 & IS 3647 reference)

Area TypeMinimum Illumination (lux)
Godowns50
Workbenches300
Offices200

Key Formula for Illumination (E):

[ E = \frac{I \times \cos \theta}{d^2} ]

Where:

  • (E) = illuminance (lux)
  • (I) = luminous intensity (candela)
  • (\theta) = angle of incidence
  • (d) = distance from light source (meters)

flowchart LR
    A[Godown Lighting] --> B[Minimum 50 lux]
    A --> C[Light fittings ≥ 75 cm from stacks]
    A --> D[Wiring in steel conduits]

Summary: Ensure godown lighting ≥ 50 lux, maintain 75 cm clearance for fixtures, and use steel conduits for wiring as per IS 3594.

13Special Provisions for Cold Storage

IS 3594: Special Provisions for Cold Storage

Key Clauses Summary:

  • Clause 3.1 & 6.2 (Cold Storage Buildings):

    • Structures must accommodate low temperatures and high humidity.
    • Design for thermal insulation, moisture control, and condensation prevention.
    • Structural elements must resist temperature-induced stresses.
  • Clause 3.4 (Insulation Boards):

    • Use materials with low thermal conductivity (e.g., expanded polystyrene, polyurethane).
    • Thickness depends on temperature difference and insulation material properties.
    • Typical thermal conductivity: 0.02 - 0.04 W/m·K.
  • Clause 10.2.1 (Refrigeration Equipment):

    • Equipment must comply with IS 660:1963.
    • Electrical wiring per IS 659:1964.
    • Ensure compatibility with cold storage environment.

Typical Design Formula for Insulation Thickness (t):

[ t = \frac{k \times (T_i - T_o)}{Q} ]

Where:

  • ( t ) = insulation thickness (m)
  • ( k ) = thermal conductivity of insulation (W/m·K)
  • ( T_i, T_o ) = inside and outside temperatures (°C)
  • ( Q ) = allowable heat flux (W/m²)

Important Considerations:

  • Structural load: Account for frost, snow, and equipment loads.
  • Condensation control: Vapor barriers and proper sealing.
  • Material durability: Resistant to moisture and low temperatures.

flowchart TD
    A[Cold Storage Building] --> B[Structural Design]
    A --> C[Insulation Boards]
    A --> D[Refrigeration Equipment]
    B --> E[Temperature Stress Analysis]
    C --> F[Material Selection]
    D --> G[IS 660 & IS 659 Compliance]

For detailed design, refer to IS 3594 clauses and IS 660/659 for equipment and wiring standards.

14Inspection, Maintenance and Operational Safety

IS 3594: Inspection, Maintenance & Operational Safety - Key Points

1. Inspection & Maintenance

  • Fixed fire protection systems must undergo periodical inspections and maintenance to ensure readiness in emergencies (Clause 13.4).
  • Maintenance contracts with approved agencies are recommended for reliability.
  • All switchgears and fuses should be enclosed in iron cases; an emergency isolation switch must be provided for safe inspection/repair (Clause 11.4.2).

2. Operational Safety

  • For large storage installations with hazardous or valuable goods, provision of a full-time Fire Brigade with major fire-fighting equipment is advised (Clause 13.5).
  • Locations of all fire-fighting equipment (hydrant valves, landing valves, hand appliances) must be marked on building plot plans and displayed prominently at entrances (Clause 13.6).

3. Referenced IS Codes for Safety & Maintenance

IS No.Title
659:1964Safety code for air conditioning
660:1963Safety code for mechanical refrigeration
2189:1988Automatic fire detection and alarm system
2190:1979Portable first-aid fire extinguisher
3614 (Part 1):1966Fire check doors specification
9668:1980Water supplies for fire fighting

Summary Table: Maintenance & Safety Checklist

ItemRequirement
Fire Protection SystemsPeriodic inspection & maintenance
Switchgear & FusesEnclosed in iron cases; emergency switch
Fire Brigade (large sites)Full-time with major equipment
Fire Equipment LocationMarked on plans & displayed at entrances

flowchart TD
    A[Fire Protection System Installed] --> B{Periodic Inspection?}
    B -- Yes --> C[Maintain & Repair]
    B -- No --> D[Risk of Failure]
    C --> E[Emergency Ready]
    D --> F[Operational Risk]
    E --> G[Safe Operation]
    F --> G

This ensures safe operational conditions and compliance with IS 3594 safety provisions.

15Right to Information and Compliance

IS 3594: Right to Information & Compliance - Key Points

IS 3594 emphasizes transparency and public access to safety standards under the Right to Information Act, promoting accountability in public authorities.

Key Specifications & References:

  • Disclosure: Timely dissemination of standards to the public, especially disadvantaged groups.
  • Copyright: BIS publications are copyrighted; reproduction requires permission except for implementation details.
  • Safety & Fire Codes Referenced:
IS No.Title
659:1964Safety code for air conditioning (revised)
660:1963Safety code for mechanical refrigeration (revised)
1641:1988Fire safety of buildings: general principles of fire grading
1642:1989Fire safety of buildings: construction details
1646:1982Fire safety of buildings: electrical installations
2189:1988Automatic fire detection and alarm system
2190:1979Portable fire extinguisher selection & maintenance
3614 (Pt 1):1966Fire check doors specification
9668:1980Water supply for firefighting

Compliance Guidance:

  • Follow referenced IS codes for design, installation, and maintenance of safety systems.
  • Ensure public access to standards as per RTI Act.
  • Maintain records and documentation for audits and transparency.

Summary Diagram: Compliance Flow

flowchart TD
    A[Public Authority] --> B[Maintain Safety Standards]
    B --> C[Implement IS Codes (e.g. IS 1641, IS 2190)]
    C --> D[Documentation & Records]
    D --> E[Provide Information under RTI]
    E --> F[Public Access & Transparency]

For detailed formulas or tables, refer to individual IS codes listed above.

Popular Questions About IS 3594

?What are the minimum separation distances required between godowns according to IS 3594?

According to IS 3594, the minimum separation distances between godowns are:

  • Minimum distance between any two facing godowns:
    12 m (Clause 8.4)

  • If the distance between facing godowns exceeds 15 m, then the following conditions apply (Clause 15.0):

    • One wall must be a separating wall, blank with no openings.
    • Openings in facing walls must be protected by fire check doors, wired glass, or both, with an approved drencher system.
  • For outdoor storage near godowns (Clause 8.1):

    • No outdoor storage within 15 m of a godown unless all doorways/windows facing the storage are protected by fire-resistant doors/shutters, wired glass, or drencher systems.
  • Roadways alongside godowns should be at least 5 m wide for fire engine access (Clause 5.2).


Summary Table

ConditionMinimum DistanceAdditional Requirements
Between facing godowns12 m-
Between facing godowns (with fire protection)> 15 mSeparating wall, fire doors, wired glass, drencher system
Outdoor storage near godown15 mFire-resistant protection on openings
Roadway width for fire engines5 m-
Loading diagram...

This ensures fire safety and accessibility per IS 3594.

?How should hazardous and extra-hazardous goods be stored to minimize fire risk?

To minimize fire risk when storing hazardous and extra-hazardous goods as per IS 3594:

  • Building Structure: Use preferably single-storeyed buildings, and in no case exceed 2 storeys (Clause 6.1.3.1).
  • Segregation: Hazardous and extra-hazardous materials must be segregated from each other and from non-hazardous materials (Clause 9.5.1).
  • Fire Hazard Assessment: Ascertain fire hazard characteristics of materials beforehand. If unknown, assume hazardous and segregate accordingly (Clause 9.5.7).
  • Special Commodities: Note that specific safety requirements for items like gases, acids, flammable liquids, etc., are not covered under this code and need separate consideration.

Summary:

AspectRequirement
Building HeightMax 2 storeys, preferably single
Material SegregationHazardous from non-hazardous & each other
Hazard IdentificationAscertain or assume hazardous

This approach limits fire spread, eases firefighting, and reduces risk of explosion or toxic release.

?What fire detection and alarm systems are mandated for warehouses exceeding certain sizes?

Fire Detection and Alarm Systems for Warehouses as per IS 3594:

  • Automatic Fire Alarm System (IS 2189:1988):
    Mandatory unless the warehouse is protected by an automatic sprinkler system.

  • Manual Fire Alarm System:
    For large open area sites without sprinklers, a well-designed manual fire alarm system should be provided.

  • Automatic Sprinkler Protection:
    All warehouses exceeding 750 m³ in floor area must have automatic sprinkler protection.

  • Compartment Size Limits:

    • Max compartment floor area without sprinklers: 750 m²
    • With sprinklers: up to 2250 m²

Summary Table:

Warehouse SizeFire Alarm System RequiredSprinkler Requirement
≤ 750 m³Automatic fire alarm system (IS 2189)Not mandatory
> 750 m³Automatic fire alarm system + sprinklersMandatory
Large open area sites (no sprinklers)Manual fire alarm systemNot applicable

This ensures early fire detection, crucial for warehouses often unoccupied during non-working hours.

Loading diagram...

Note: This complements statutory fire safety laws and special storage conditions.

?Are automatic sprinkler systems required for all storage buildings under this standard?

IS 3594: Automatic Sprinkler System Requirements for Storage Buildings

  • Clause 13.3: Automatic sprinkler systems are mandatory for all godowns and warehouses exceeding 750 m² floor area.
  • For storage buildings below 750 m², sprinklers are not compulsory but a well-designed automatic fire alarm system (per IS 2189:1988) must be installed (Clause 6.2.7).
  • Water supply system with fire hydrants and static tanks (per IS 9668:1980) is required for storage buildings >750 m² or outdoor storage >2000 m² (Clause 13.1.2).
  • Outdoor storage near warehouses must have fire-resistant protections or drencher systems (Clause 8.1).

Summary:

Storage AreaSprinkler System Required?Fire Alarm System Required?
> 750 m² (godowns)YesYes
≤ 750 m²No (sprinkler not mandatory)Yes (automatic fire alarm system)
Loading diagram...

Conclusion: Automatic sprinklers are required only for storage buildings above 750 m² floor area under IS 3594.

?What special fire safety considerations apply to cold storage warehouses?

Fire Safety Considerations for Cold Storage Warehouses (IS 3594)

  • Compartment Size: Maximum floor area per compartment should not exceed 750 m² without sprinklers; can be increased to 2250 m² if sprinklers are installed (Clause 6.2.3).

  • Combustible Materials: Includes cork, expanded plastic insulation, wood dunnage, pallets, boxes, fireboard, and paper wrappings. Despite low temperatures (-5°C to 20°C), fire hazards remain significant.

  • Fire Detection & Control: Early detection and automatic fire alarm/protection systems are critical due to low occupancy during non-working hours.

  • Fire Resistive Construction & Compartmentation: Use fire-resistant walls and subdivide large storage areas to limit fire spread.

  • Fire Brigade: For large or high-value cold storages, a full-time fire brigade with major firefighting equipment may be necessary (Clause 13.5).

  • Fire Equipment Location: Hydrant valves, landing valves, and hand appliances must be clearly marked on site plans and at entrances (Clause 13.6).


Summary Table: Compartment Size vs Sprinkler Provision

Sprinkler ProvisionMax Compartment Area (m²)
No Sprinklers750
With Sprinklers2250

Loading diagram...

Key takeaway: Cold storage warehouses require the same stringent fire safety standards as normal warehouses, with special attention to compartment sizes and automatic fire protection due to unique fire risks posed by insulation and low temperatures.