IS 3058:1990 provides a comprehensive code of practice for fire safety specific to industrial buildings involved in the manufacture of viscose rayon yarn and staple fibre. It addresses fire prevention, storage, and handling of hazardous materials like carbon disulphide, sulphur, and fuel oil, as well as safety measures for electrical and mechanical equipment. This standard is essential for engineers, safety officers, and plant managers working in viscose rayon production facilities to ensure compliance with fire safety regulations and minimize fire risks.
Overview
IS 3058:1990 provides a comprehensive code of practice for fire safety specific to industrial buildings involved in the manufacture of viscose rayon yarn and staple fibre. It addresses fire prevention, storage, and handling of hazardous materials like carbon disulphide, sulphur, and fuel oil, as well as safety measures for electrical and mechanical equipment. This standard is essential for engineers, safety officers, and plant managers working in viscose rayon production facilities to ensure compliance with fire safety regulations and minimize fire risks.
Audience
Contents
Structure
Scope (Clause 2.1 & 3.0):
IS 3058 covers specifications related to fire safety equipment and installations. Definitions (Clauses 3.1 to 3.12) clarify terms used in the standard.
Key Points:
| IS No. | Title |
|---|---|
| 941:1985 | Blower and exhauster for fire fighting |
| 1642:1989 | Fire safety of buildings: Materials and construction details |
| 3844:1989 | Installation of internal fire hydrants in multistorey buildings |
| 2190:1979 | Selection, installation & maintenance of portable fire extinguishers |
| 3034:1981 | Fire safety of industrial buildings: Electrical stations |
| 3594:1989 | Fire safety of industrial buildings: Storage & warehousing |
| 12459:1988 | Fire protection of cable runs |
flowchart LR
A[IS 3058 Scope] --> B[Definitions (3.1 to 3.12)]
A --> C[Annex A: Referenced IS Codes]
C --> D[Fire Extinguishers (IS 2190)]
C --> E[Fire Hydrants (IS 3844)]
C --> F[Fire Safety Materials (IS 1642)]
C --> G[Industrial Fire Safety (IS 3034, 3594)]
For detailed formulas or tables, consult the specific IS codes referenced under Annex A.
IS 3058: Referenced Indian Standards Summary
Clause 2.1 & Annex A list essential Indian Standards (IS) related to fire safety equipment and practices. These form the technical backbone for IS 3058 compliance.
| IS No. | Title |
|---|---|
| 941 : 1985 | Blower and exhauster for fire fighting (2nd revision) |
| 1642 : 1989 | Fire safety of buildings (materials & construction) |
| 2190 : 1979 | Portable first-aid fire extinguisher (selection, installation, maintenance) |
| 3034 : 1981 | Fire safety of industrial buildings: Electrical stations |
| 3594 : 1989 | Fire safety of industrial buildings: Storage & warehousing |
| 3844 : 1989 | Installation of internal fire hydrants in multistorey buildings |
| 4262 : 1967 | Safety code for sulphuric acid |
| 5685 : 1970 | Safety code for carbon disulphide |
| 10658 : 1983 | Higher capacity dry powder fire extinguisher (trolley mounted) |
| 12056 : 1987 | Safety requirements for automotive fuel tank assemblies |
| 12459 : 1988 | Fire protection of cable runs (installation & maintenance) |
graph LR
A[IS 3058: Fire Extinguishers] --> B[IS 2190: Fire Extinguisher Selection & Maintenance]
A --> C[IS 941: Fire Fighting Blowers]
A --> D[IS 3844: Internal Fire Hydrants]
A --> E[IS 10658: Dry Powder Extinguishers]
A --> F[IS 12459: Cable Run Fire Protection]
A --> G[IS 1642: Fire Safety of Buildings]
For detailed design, installation, and safety requirements, refer
IS 3058 - Definitions (Clause 3.0 to 3.12)
| IS No. | Title |
|---|---|
| 1642 | Fire safety of buildings (materials & details) |
| 3844 | Installation of internal fire hydrants |
| 2190 | Portable first-aid fire extinguishers |
| 941 | Blower and exhauster for firefighting |
| 3034 | Fire safety of industrial buildings (electrical) |
| 3594 | Fire safety of industrial buildings (storage) |
For exact definitions, consult clauses 3.1 to 3.12 of IS 3058 directly.
IS 3058: Location and Site Selection – Key Points
Site Area Requirements (Clause 5.1 & 5.2):
Preferred Location (Clause 4.2):
Gate Specifications (Clause 5.4):
| Parameter | Minimum Dimension | Remarks |
|---|---|---|
| Compound built-up area | ≤ 50% of total area | To allow future expansions |
| Main gate clear width | 4.5 m | For entry/exit |
| Main gate headroom | 4.5 m | For vehicle clearance |
| Emergency gate | Same as main gate | For emergency access |
graph LR
A[Perennial Water Source] --> B[Plant Site]
B --> C[Main Plant]
B --> D[Service Buildings]
B --> E[Auxiliary Plants]
B --> F[Open Storage Area]
B --> G[Main Gate (4.5m width & height)]
B --> H[Emergency Gate (4.5m width & height)]
Note: Ensure sufficient open space for storage and future expansion as per IS 3058 guidelines.
IS 3058 Key Specifications for Factory Compound & Building Layout
| Location | Minimum Illumination (Lux) |
|---|---|
| Godowns | 100 |
| Rayon plant | 100 |
| Carbon disulphide & sulphuric acid plants | 100 |
| Open compound under use | 50 |
graph LR
A[Main Gate (4.5m width & height)] --> B[Factory Compound]
B --> C[Main Plant]
B --> D[Service Buildings]
B --> E[Auxiliary Plants]
B --> F[Storage Areas (Charcoal, Coal, Sulphur)]
B --> G[Open Spaces for Expansion]
B --> H[Additional Emergency Gate (4.5m width & height)]
Note: For detailed minimum distances between units, refer to Clause 5.1 of IS 3058.
IS 3058: Storage Arrangements - Key Points
| Parameter | Minimum Dimension |
|---|---|
| Gate Width | 4.5 m |
| Headroom | 4.5 m |
| Number of Gates | At least 2 (1 main + 1 emergency) |
flowchart LR
A[Factory Compound] --> B[Main Gate]
A --> C[Emergency Gate]
B & C --> |Width & Headroom ≥ 4.5 m| D[Access for vehicles & personnel]
For detailed storage design, consult the specific IS codes mentioned for material-specific safety and structural requirements.
| IS No. | Title |
|---|---|
| IS 941 : 1985 | Blower & exhauster for firefighting |
| IS 1642 : 1989 | Fire safety of buildings: materials & construction |
| IS 3844 : 1989 | Internal fire hydrants in multistorey buildings |
| IS 2190 : 1979 | Portable fire extinguishers: selection & maintenance |
| IS 3034 : 1981 | Fire safety of industrial buildings: electrical stations |
| Condition | Max Plinth Area | Max Distance to Hydrant |
|---|---|---|
| Without sprinkler | 5,000 m² | 30 m |
| With automatic sprinkler | 10,000 m² | 30 m |
flowchart TD
A[Check building plinth area] --> B{Is area > 5,000 m²?}
B -- No sprinkler --> C[Max area 5,000 m²]
B -- Sprinkler installed --> D{Is area > 10,000 m²?}
D -- Yes --> E[Compartmentation or reduce area]
D -- No --> F[Allowed]
C --> G[Max distance to hydrant ≤ 30 m?]
G -- Yes --> F
G -- No --> H[Provide internal hydrant system]
Note: For detailed fire-resistance
IS 3058 - Separating Walls (Clause 8)
Purpose: To segregate hazardous or different functional areas (e.g., viscose, spinning, packaging, godowns) to prevent fire spread.
Key Sections Requiring Separating Walls:
Compliance: Separating walls should conform to IS 1642:1989 — Fire-resisting construction for industrial buildings.
Fire Resistance: Typically, separating walls require a minimum fire resistance period (e.g., 2-4 hours), depending on hazard classification.
Thickness & Material:
| Parameter | Sprinklered Building | Non-sprinklered Building |
|---|---|---|
| Max plinth area (single bldg) | 10,000 m² | 5,000 m² |
| Max distance from fire hydrant | 30 m | 30 m |
| Internal hydrant system needed | If distance > 30 m | If distance > 30 m |
flowchart LR
A[Viscose Section] ---|Separating Wall| B[Spinning Section]
B ---|Separating Wall| C[After-treatment Section]
C ---|Separating Wall| D[Packaging Section]
D ---|Separating Wall| E[Godowns]
F[Boiler House] ---|Separating Wall| G[Rayon Yarn Plant]
H[Xanthation Area] ---|Separating Wall per IS 1642| I[Adjoining Blocks]
Summary:
Separating walls per IS 3058 must be fire-resistant, comply with IS 1642, and isolate hazardous sections to limit fire spread. Fire safety provisions like sprinkler systems and hydrant distances
IS 3058 - Key Points on Storage of Sulphur and Chemicals
| Chemical | Minimum Distance from Other Storage (m) | Reference IS Code |
|---|---|---|
| Sulphur | 30 (except 15 from CS2 & H2SO4 plants) | IS 3058, IS 3097 |
| Carbon Disulphide | Per IS 5685:1970 | IS 5685:1970 |
graph LR
A[Sulphur Storage Area]
B[Other Storage Areas]
C[CS2 & H2SO4 Plants]
A -- 30m --> B
A -- 15m --> C
Note: Always consult the latest IS codes and local regulations for detailed safety and storage design.
IS 3058 – Process Plants and Equipment Safety: Key Points
Clause 10.3.1 (Carbon Disulphide Plant):
Machinery must comply with IS 5685:1970 — covers design, materials, and safety requirements specific to carbon disulphide plant machinery.
Clause 10.2 (Boiler Plants):
Boiler plants should follow relevant IS codes (e.g., IS 2825, IS 10496) ensuring safety in pressure vessels, steam generation, and operation.
Clause 10.4 & 10.4.1 (Sulphuric Acid Plant):
Machinery must comply with IS 4262:1967 — addresses corrosion-resistant materials, safe design, and operational safety for sulphuric acid plants.
Clause 11 (Electrical Installation):
Electrical equipment must conform to IS 732 and IS 3043 for wiring, grounding, and explosion-proof requirements in hazardous areas.
| Plant Type | Relevant IS Code | Key Safety Focus |
|---|---|---|
| Carbon Disulphide | IS 5685:1970 | Explosion resistance, materials |
| Sulphuric Acid | IS 4262:1967 | Corrosion resistance, safety |
| Boiler Plants | IS 2825, IS 10496 | Pressure vessel safety |
| Electrical Install. | IS 732, IS 3043 | Wiring, grounding, hazardous area protection |
[ t = \frac{P \times D}{2 \times \sigma \times E + P} ]
flowchart LR
A[Process Plant] --> B[Machinery]
B --> C{Type}
C -->|Carbon Disulphide| D[IS 5685:1970]
C -->|Sulphuric Acid| E[IS 4262:1967]
C -->|Boiler| F[
IS 3058 - Electrical Installations: Key Points & References
Clause 11.1: Electrical installations must comply with IS 1646 : 1982 – this standard covers general requirements for electrical wiring, materials, and safety.
Clause 11.5.5: Electric wiring requires periodic inspection to ensure safety and functionality.
Related Standards:
| Parameter | Specification |
|---|---|
| Wiring Type | PVC insulated cables or armored cables |
| Voltage Rating | Typically up to 660 V |
| Conductor Material | Copper or Aluminum |
| Earthing | Must comply with IS 3043 |
| Inspection Frequency | At least once annually or as per usage |
flowchart TD
A[Design Electrical Layout] --> B[Select Wiring & Equipment per IS 1646]
B --> C[Install Wiring & Earthing]
C --> D[Connect Switchgear & Protective Devices]
D --> E[Conduct Inspection & Testing]
E --> F[Periodic Maintenance & Re-inspection]
For detailed formulas (e.g., cable sizing, voltage drop), refer IS 732 and IS 3043 alongside IS 1646.
IS 3058 - Mechanical Installations and Maintenance: Key Points
| IS No. | Title |
|---|---|
| IS 941 | Blower and exhauster for fire fighting (second revision) |
| IS 1642 | Code of practice for fire safety of buildings: Materials and construction details |
| IS 2190 | Code of practice for selection, installation, and maintenance of portable fire extinguishers |
| IS 3034 | Fire safety of industrial buildings: Electrical generating and distributing stations |
| IS 3844 | Installation of internal fire hydrants in multistorey buildings |
| IS 12459 | Fire protection of cable runs for installation and maintenance |
| Equipment Type | Relevant IS Code | Maintenance Focus |
|---|---|---|
| Fire Blowers | IS 941 | Functional testing, lubrication |
| Fire Extinguishers | IS 2190, IS 10658 | Pressure checks, refilling |
| Fire Hydrants | IS 3844 | Valve operation, water supply |
| Cable Runs | IS 12459 | Fire protection integrity |
flowchart TD
A[Mechanical Equipment] --> B[Inspection]
B --> C{Condition}
C -->|Good| D[Continue Operation]
C -->|Needs Repair| E[Maintenance]
E -->
IS 3058 - Fire Fighting Arrangements: Key Points
Clause 13.1:
First aid fire fighting equipment and maintenance must comply with IS 2190:1979 (Portable Fire Extinguishers).
Clause 13.5:
Strictly follow laid down fire procedure protocols for operators and fire fighting squads.
Clause 13.7:
Provide large capacity dry powder fire extinguishers as per IS 10658:1983 in high fire-risk zones.
| Aspect | IS Code Reference | Key Details |
|---|---|---|
| First Aid Fire Fighting Equip. | IS 2190:1979 | Types, capacities, maintenance of extinguishers |
| Dry Powder Extinguishers | IS 10658:1983 | Design & capacity for large fire hazard areas |
| Emergency Lighting | IS 3058 Clause 12.2 | Adequate capacity to ensure visibility during fire |
| Fire Class | Recommended Extinguisher Type |
|---|---|
| Class A | Water, Foam |
| Class B | Foam, Dry Powder, CO₂ |
| Class C | Dry Powder |
| Class D | Special Dry Powder (Metal fires) |
flowchart LR
A[Fire Outbreak] --> B[Operator Alert]
B --> C[Activate Fire Alarm]
C --> D[Fire Fighting Squad Mobilizes]
D --> E[Use Suitable Extinguisher]
E --> F[Evacuate if Fire Spreads]
Summary: Follow IS 2190 for extinguisher specs, IS 10658 for dry powder types in high-risk areas, and maintain emergency lighting per IS 3058 Clause 12.2. Strict procedural adherence (Clause 13.5) is critical for safety.
IS 3058: General Safety Provisions & Housekeeping (Fire Safety)
Fire Extinguishers:
Fire Safety Signage:
| Area Type | Extinguisher Type | Capacity (kg) |
|---|---|---|
| High-risk industrial zones | Dry Powder | 9-12 kg |
| General industrial areas | Carbon Dioxide (CO2) | 4-6 kg |
flowchart LR
A[High Fire Risk Areas] --> B[Install Dry Powder Extinguishers]
B --> C[Capacity as per IS 10658]
D[Fire Safety Orders] --> E[Display at Conspicuous Places]
F[Housekeeping] --> G[Clear Access & Cleanliness]
G --> H[Safe Storage of Flammables]
Summary: IS 3058 emphasizes dry powder extinguishers in high-risk zones and mandates visible fire safety signage, combined with good housekeeping for fire prevention.
Frequently Asked
Fire Safety Requirements for Carbon Disulphide Storage (IS 3058 & IS 5685:1970)
Summary Table:
| Parameter | Requirement |
|---|---|
| Ventilation | Adequate natural/mechanical |
| Temperature Control | Cool storage, avoid heat sources |
| Electrical Equipment | Explosion-proof |
| Fire Extinguishing | Foam or dry chemical systems |
| Separation Distance | As per IS 5685 guidelines |
Loading diagram...
For detailed specifications, refer to IS 5685:1970 alongside IS 3058.
According to IS 3058, for electrical equipment in hazardous areas:
Loading diagram...
This ensures safety and compliance in explosive atmospheres.
Recommended Distances for Sulphur Storage (IS 3058):
Sulphur storage areas:
Additional related distances:
| From / To | Minimum Distance (m) |
|---|---|
| Sulphur storage to other storage | 30 |
| Sulphur storage to CS₂ / H₂SO₄ | 15 |
| CS₂ plant to H₂SO₄ plant | 30 |
| Main plant to CS₂ / H₂SO₄ plants | 75 |
This ensures safe separation to minimize risk of fire or chemical hazards.
According to IS 3058 (1990) for viscose rayon manufacturing buildings:
Recommendation: For enhanced safety and compliance with modern fire codes, consider installing automatic sprinkler systems even if not explicitly mandated.
Safety Measures for Fuel Oil and Coal Storage (IS 3058):
Fuel Oil Storage (Clause 6.5.1):
Follow IS 12056:1987 and IS 3594:1989 for detailed safety provisions, which include:
Coal Storage (Clauses 6.2 & 9.3):
Loading diagram...
Summary: Maintain clear separation distances, clean and hard storage surfaces for coal, and comply with relevant IS codes for fuel oil tank safety.
Ask AI about any clause, requirement, or provision in IS 3058. Get instant, clause-cited responses powered by our indexed library.