IS 2556 Part 82004AI Search Enabled✦ AI Generated

Vitreous Sanitary Appliances (Vitreous China) -, Part 8: Specific Requirements of Pedestal Close Coupled Washdown and Symphonic Water Closets

IS 2556 Part 8:2004 specifies the requirements for pedestal close-coupled washdown and syphonic water closets made of vitreous china. It covers design patterns, construction, dimensions, tolerances, materials, and performance tests to ensure durability, functionality, and water efficiency. This standard is essential for manufacturers, designers, and quality inspectors involved with vitreous sanitary appliances in India.

12Sections
65Clauses Indexed
AI Search Ready
2004Edition
Sanitary Appliances and Water FittingsCategory
Alternative search terms: IS 2556 Part 8 PDF, IS 2556 Part 8 pdf free download, IS 2556 Part 8 free download pdf, IS2556Part8 PDF, IS-2556-Part-8 PDF, IS 2556 Part 8 2004 PDF, IS 2556 Part 8:2004 PDF, IS 2556 Part 8-2004 PDF, IS 2556 Part 8 (2004) PDF, IS 2556 Part 8 2004 edition PDF, IS 2556 Part 8 edition 2004 PDF

What This Standard Covers

IS 2556 Part 8:2004 specifies the requirements for pedestal close-coupled washdown and syphonic water closets made of vitreous china. It covers design patterns, construction, dimensions, tolerances, materials, and performance tests to ensure durability, functionality, and water efficiency. This standard is essential for manufacturers, designers, and quality inspectors involved with vitreous sanitary appliances in India.

Who Uses This Standard

  • Sanitaryware Manufacturers
  • Civil and Plumbing Engineers
  • Quality Control Inspectors
  • Architects and Interior Designers
  • Building Contractors
  • Water Efficiency Consultants
  • Regulatory Authorities

Key Topics Covered

Design patterns of water closets (syphonic and washdown)
Functional and connecting dimensions
Material and construction requirements
Integral flushing rim and trap types (S-trap, P-trap, concealed S-trap, horizontal outlet)
Water saving system specifications
Performance tests including flushing, holding capacity, sawdust, smudge, splash, and load bearing
Flushing cistern compatibility and requirements
Marking and certification requirements
Sampling and inspection procedures
Tolerance limits for dimensions
Surface glazing and finish quality
Installation and fixing provisions

Table of Contents

1Scope

Scope & Key Specifications from IS 2556 Part 8 (Clause 6.1 & Table 2):

This part covers functional and connecting dimensions of WC pans and outlets critical for plumbing compatibility.

Connecting Dimensions (All in mm)

ParameterSymbolSyphonic, P or S OutletWashdown P or S OutletWashdown Concealed S-trapWashdown Horizontal Outlet
Internal diameter of outletd₁80 Min80 Min80 Min80 Min
External diameter of outletd₂102 ± 5102 ± 5102 ± 5102 ± 5
Height of centre line of outlet from floor (P-trap only)h₁180 ± 10180 ± 10180 ± 10180 ± 10
Distance from end of trap to floor (S-trap only)h₂20 ± 520 ± 5--
Length of grooved part of outletl40 Min40 Min--
Distance between centre of seat bolt holesn160 to 175160 to 175160 to 175160 to 175
Diameter of seat bolt holesd₃15 ± 215 ± 215 ± 215 ± 2
Distance between back of cistern and outlet (P-trap) or centre line of outlet (S-trap)g70 Min / 85 Min70 Min / 85 Min- / 85 Min70 Min / -
Radius of free space from outlet centred₄75757575
Angle of outlete104°104°-90°

Notes:

  • Ovality is permissible within internal/external diameter limits.
  • Dimensions ensure compatibility with plumbing fixtures and traps.
  • Rounding of test values must follow IS 2:1960 rules.

Summary:

  • Internal outlet diameter: ≥ 80 mm
  • Outlet angle: Typically 104° or
2References

IS 2556 Part 8: Key References, Tables & Specifications


1. References (Table 2)

  • IS 774:1984 — Flushing cisterns (non-plastic)
  • IS 2556 (Parts 1 & 7) — Vitreous sanitary appliances specifications
  • IS 7231:1994 — Plastic flushing cisterns
  • IS 9140:1996 — Sampling methods for vitreous/fire clay appliances

2. Connecting Dimensions (Clause 6.1, Table 2)

All dimensions in mm

ParameterSyphonic, P or S OutletWashdown P or S OutletWashdown Concealed S-trapWashdown Horizontal Outlet
Internal diameter (d1)80 Min80 Min80 Min80 Min
External diameter (d2)102 ± 5102 ± 5102 ± 5102 ± 5
Height of centre line from floor (h1)180 ± 10180 ± 10180 ± 10180 ± 10
Distance from trap end to floor (S-trap only, h2)20 ± 520 ± 5--
Length of grooved outlet (l)40 Min40 Min--
Distance between seat bolt holes (n)160 to 175160 to 175160 to 175160 to 175
Diameter of seat bolt holes (d3)15 ± 215 ± 215 ± 215 ± 2
Distance back of cistern to outlet (g)70 Min / 85 Min70 Min / 85 Min- / 85 Min70 Min / -
Radius of free space (d4)75757575
Angle of outlet (e)104°104°-90°
Length of straight glazed outlet (l4)---40 Min
Distance end of outlet to floor
3General Requirements

IS 2556 Part 8: General Requirements Summary

  • Functional and Connecting Dimensions:

    • Functional dimensions (non-connecting) and connecting dimensions (critical for plumbing) are specified in Table 1 and Table 2 respectively.
    • These dimensions ensure compatibility and proper installation.
  • Compliance with IS 2556 Part 1:

    • Terminology, materials, manufacturing, glazing, defects, minimum thickness, performance, and testing methods must comply with IS 2556 Part 1.
    • This ensures uniform quality and performance standards.

Key Points:

AspectReference/Requirement
Functional DimensionsAs per Table 1 in IS 2556 Part 8
Connecting DimensionsAs per Table 2 in IS 2556 Part 8
Materials & ManufactureIS 2556 Part 1
Minimum ThicknessIS 2556 Part 1
Performance & TestsIS 2556 Part 1

Note:

  • Always refer to IS 2556 Part 1 for detailed specifications on materials and testing.
  • Tables 1 & 2 provide critical dimensional data for design and installation.
flowchart LR
    A[General Requirements] --> B[Functional Dimensions (Table 1)]
    A --> C[Connecting Dimensions (Table 2)]
    A --> D[Materials & Manufacturing (IS 2556 Part 1)]
    A --> E[Performance & Testing (IS 2556 Part 1)]

This ensures all components meet plumbing and structural compatibility per IS standards.

4Patterns and Construction

IS 2556 Part 8: Patterns and Construction of Pedestal Closets

Patterns (Clause 4.1)

Pedestal closets with close-coupled cisterns shall be one of these patterns:

Pattern No.DescriptionTrap TypeReference Figures
1Double trap syphonic'S' trap or 'P' trapFig. 1A, Fig. 1B
2Single trap syphonic'S' trap or 'P' trapFig. 1A, Fig. 1B
3Washdown'P' trap or 'S' trap or concealed 'S' trapFig. 2A, 2B, 3A, 3B
4Washdown with horizontal outletHorizontal outletFig. 4A, Fig. 4B

Key Specifications

  • Functional and connecting dimensions must comply with Table 1 and Table 2 (Clause 6.1).
  • Pattern 4 requires special connectors for horizontal outlet; outlet must be grooveless on the straight part (Clause 5.4).
  • Other patterns must follow standard trap configurations and dimensions.

Typical Dimension Tables (Summary)

Dimension TypeDescriptionReference Table
Functional DimensionsSeat height, bowl size, etc.Table 1
Connecting DimensionsInlet/outlet sizes, trap distancesTable 2

Notes:

  • Alternative patterns allowed only if manufacturer and purchaser agree.
  • All other IS code requirements apply strictly except functional dimensions for custom patterns.
flowchart TD
    A[Pedestal Closets] --> B[Pattern 1: Double Trap Syphonic]
    A --> C[Pattern 2: Single Trap Syphonic]
    A --> D[Pattern 3: Washdown (P or S trap)]
    A --> E[Pattern 4: Washdown with Horizontal Outlet]
    E --> F[Special Connector Required]

For exact dimensions, refer to IS 2556 Part 8 Tables 1 & 2.

5Design and Fixing Requirements

IS 2556 Part 8: Design and Fixing Requirements

Key Specifications from Clause 6.1 & Table 2 (Connecting Dimensions)

ParameterSymbolSyphonic, P or S OutletWashdown P or S OutletWashdown Concealed S-trapWashdown Horizontal Outlet
Internal diameter of outletd₁80 mm Min80 mm Min80 mm Min80 mm Min
External diameter of outletd₂102 ± 5 mm102 ± 5 mm102 ± 5 mm102 ± 5 mm
Height of centre line of outlet from floor (P-trap only)h₁180 ± 10 mm180 ± 10 mm180 ± 10 mm180 ± 10 mm
Distance from end of trap to floor (S-trap only)h₂20 ± 5 mm20 ± 5 mm--
Length of grooved part of outletl40 mm Min40 mm Min--
Distance between centre of seat bolt holesn160 to 175 mm160 to 175 mm160 to 175 mm160 to 175 mm
Diameter of seat bolt holesd₃15 ± 2 mm15 ± 2 mm15 ± 2 mm15 ± 2 mm
Distance between back of cistern and outlet (P-trap) or centre line (S-trap)g70 Min to 85 Min mm70 Min to 85 Min mm- to 85 Min mm70 Min to - mm
Radius of free space from outlet centerd₄₂75 mm75 mm75 mm75 mm
Angle of outlete104°104°-90°
  • Ovality is permissible within internal and external diameter limits.
  • Dimensions are critical for plumbing fit and functional performance.

Additional Notes

  • Clause 9.4.2 specifies a Fifty Ball Test for durability (details not fully provided here).
  • Refer to IS
6Dimensions and Tolerances

IS 2556 Part 8: Dimensions and Tolerances Summary

1. Functional Dimensions (Table 1, Clause 6.1)

ParameterSyphonic P/S OutletWashdown P/S OutletWashdown Horizontal Outlet
Height (H)390 ± 10 mm390 ± 10 mm390 ± 10 mm
Width (W)360 ± 10 mm360 ± 10 mm360 ± 10 mm
Depth of water seal (DI)≥ 50 mm≥ 50 mm≥ 50 mm
Water surface (Back to front)-≥ 150 mm≥ 150 mm
Water surface (Side to side)-≥ 110 mm≥ 110 mm
Distance center seal bolt holes to front (D2)415 to 445 mm415 to 445 mm415 to 445 mm
Length of opening (P)≥ 290 mm≥ 290 mm≥ 290 mm
Width of opening (Q)≥ 240 mm≥ 240 mm≥ 240 mm

2. Connecting Dimensions (Table 2, Clause 6.1)

ParameterSyphonic, P or S OutletWashdown P or S OutletWashdown Concealed S-trapWashdown Horizontal Outlet
Internal diameter of outlet (d1)≥ 80 mm≥ 80 mm≥ 80 mm≥ 80 mm
External diameter of outlet (d2)102 ± 5 mm102 ± 5 mm102 ± 5 mm102 ± 5 mm
Height of outlet center from floor (h1)180 ± 10 mm180 ± 10 mm180 ± 10 mm180 ± 10 mm
Distance from end of trap to floor (h2)20 ± 5 mm20 ± 5 mm--
Length of grooved part of outlet (l)≥ 40 mm≥ 40 mm--
Distance between seat bolt holes (
7Materials and Surface Finish

IS 2556 Part 8: Materials and Surface Finish – Key Specifications

1. Materials

  • Vitreous china is the standard material for sanitary appliances.
  • Refer IS 2556 (Part 1 & 7) for general and detailed material specifications.
  • Materials must comply with durability, non-absorbency, and chemical resistance criteria.

2. Surface Finish

  • The surface must be smooth, glossy, and free from defects such as cracks or blisters.
  • Surface finish is verified by the Fifty Ball Test (Clause 9.4.2):
    • Fifty non-absorbent balls of specified mass are used to check surface durability.

3. Connecting Dimensions (Clause 6.1, Table 2)

ParameterSymbolSyphonic/P or S OutletWashdown P or S OutletWashdown Concealed S-trapWashdown Horizontal Outlet
Internal diameter of outlet (mm)d₁80 Min80 Min80 Min80 Min
External diameter of outlet (mm)d₂102 ± 5102 ± 5102 ± 5102 ± 5
Height of centre line from floor (mm)h₁180 ± 10180 ± 10180 ± 10180 ± 10
Length of grooved part of outlet (mm)l40 Min40 Min--
Distance between seat bolt holes (mm)n160 to 175160 to 175160 to 175160 to 175
Diameter of seat bolt holes (mm)d₃15 ± 215 ± 215 ± 215 ± 2
Angle of outlet104°104°-90°

Ovality tolerance applies to internal and external diameters.


Summary Diagram of Outlet Dimensions

flowchart LR
    A[Outlet] -->|Internal Diameter d₁| B((80 mm Min))
    A -->|External Diameter d₂| C((102 ± 5 mm))
   
8Flushing Cistern Requirements

IS 2556 Part 8: Flushing Cistern Requirements Summary

1. General Requirements

  • Flushing cisterns shall be low-level coupled type.
  • Must conform to IS 774 or IS 7231 (except inlet & overflow may be from bottom).
  • No separate flush pipe needed if inlet & overflow are bottom-mounted.
  • Discharge rate test is not applicable for all patterns.

2. Functional Dimensions (Table 1, Clause 6.1)

ParameterPattern 1 & 2 (Syphonic P/S Outlet)Pattern 3 (Washdown P/S Outlet)Pattern 4 (Washdown Horizontal Outlet)
Height (H)390 ± 10 mm390 ± 10 mm390 ± 10 mm
Width (W)360 ± 10 mm360 ± 10 mm360 ± 10 mm
Depth of water seal (DI)≥ 50 mm≥ 50 mm≥ 50 mm
Water surface (Back to front)-≥ 150 mm≥ 150 mm
Water surface (Side to side)-≥ 110 mm≥ 110 mm
Distance from seal bolt hole center to front (D2)415–445 mm415–445 mm415–445 mm
Length of opening (P)≥ 290 mm≥ 290 mm≥ 290 mm
Width of opening (Q)≥ 240 mm≥ 240 mm≥ 240 mm
Trap inlet depth (T)-≥ 75 mm≥ 75 mm

3. Connecting Dimensions (Table 2, Clause 6.1)

ParameterSyphonic P/S OutletWashdown P/S OutletWashdown Concealed S-trapWashdown Horizontal Outlet
Internal diameter of outlet (d1)≥ 80 mm≥ 80 mm≥ 80 mm≥ 80 mm
External diameter of outlet (d2)102 ± 5 mm102 ± 5 mm102 ±
9Performance Tests

IS 2556 Part 8: Performance Tests Key Points

1. Single Ball Test (Clause 9.4.1)

  • Used to check water seal integrity.
  • Procedure: Charge WC with colored water to design water seal level.
  • Activate flush; observe splashes.
  • Up to 10 isolated droplets splashing onto floor allowed without rejection.

2. Fifty Ball Test (Clause 9.4.2)

  • Uses 50 balls of non-absorbent material (mass not specified here).
  • Tests trap seal performance by counting balls retained.
  • Ensures trap does not allow passage of foreign objects.

3. Load Bearing Test (Clause 10)

  • WC fixed securely on floor.
  • Apply a load of 400 ± 5 kg (or 4 ± 0.5 kN) on a 100 mm × 100 mm wooden beam across the top opening.
  • Load held for 1 hour.
  • No damage or defects allowed.

4. Connecting Dimensions (Table 2, Clause 6.1)

ParameterSyphonic/P or S OutletWashdown P or S OutletWashdown Concealed S-trapWashdown Horizontal Outlet
Internal diameter of outlet (d1)80 mm Min80 mm Min80 mm Min80 mm Min
External diameter of outlet (d2)102 ± 5 mm102 ± 5 mm102 ± 5 mm102 ± 5 mm
Height of outlet center line from floor (h1)180 ± 10 mm180 ± 10 mm180 ± 10 mm180 ± 10 mm
Length of grooved part of outlet (l)40 mm Min40 mm Min--
Distance between seat bolt holes (n)160 to 175 mm160 to 175 mm160 to 175 mm160 to 175 mm

5. Functional Dimensions (Table 1, Clause 6.1)

  • Height (H): 390 ± 10 mm
  • Width (W): 360 ± 10 mm
  • Depth of water seal (DI):
10Load Bearing Test

IS 2556 Part 8: Load Bearing Test & Related Specifications

1. Load Bearing Test (Clause 10)

  • Load Applied: 400 ± 5 kg (equivalent to 4 ± 0.05 kN)
  • Duration: 1 hour
  • Setup: Load applied via a wooden beam (100 mm × 100 mm cross-section) placed across the WC top opening.
  • Acceptance: No damage or defect shall occur.

2. Splash Test (Clause 9.6.1 - Procedure)

  • WC is charged with coloured water to design water seal level.
  • Flush valve/cistern activated.
  • Observe water splash on floor; up to 10 isolated droplets allowed without rejection.

3. Connecting Dimensions (Table 2, Clause 6.1)

ParameterSymbolValue (mm)
Internal diameter of outletd180 Min
External diameter of outletd2102 ± 5
Height of outlet centre line (P-trap)h1180 ± 10
Distance from end of trap to floor (S-trap)h220 ± 5
Length of grooved part of outletl40 Min
Distance between seat bolt holesn160 to 175
Diameter of seat bolt holesd315 ± 2
Radius of free space from outlet centred475
Angle of outlete104° (Syphonic/P/S) or 90° (Horizontal)

Summary Diagram: Load Bearing Test Setup

graph TD
    A[Wooden Beam 100x100 mm] -->|Load 400±5 kg| B[WC Top Opening]
    B --> C[WC Fixed on Floor]
    C --> D[No Damage Allowed]

Note: Sampling & inspection follow IS 9140. The test ensures structural integrity and usability of WC under load and operational conditions.

11Sampling and Inspection

IS 2556 (Part 8): Sampling and Inspection Key Points

1. Rounding Off (IS 2:1960)

  • Final test values must be rounded off matching the significant digits of the specified values.
  • Ensures consistency in reporting test results.

2. Fifty Ball Test (Clause 9.4.2)

  • Uses 50 balls of non-absorbent material (mass not specified here).
  • Purpose: To check surface finish or defects.
  • Details in Table 9.4.2 (not fully provided).

3. Connecting Dimensions (Clause 6.1, Table 2)

ParameterSymbolSyphonic, P or S OutletWashdown P or S OutletWashdown Concealed S-trapWashdown Horizontal Outlet
Internal diameter of outletd₁≥ 80 mm≥ 80 mm≥ 80 mm≥ 80 mm
External diameter of outletd₂102 ± 5 mm102 ± 5 mm102 ± 5 mm102 ± 5 mm
Height of centre line from floor (P-trap only)h₁180 ± 10 mm180 ± 10 mm180 ± 10 mm180 ± 10 mm
Distance from end of trap to floor (S-trap only)h₂20 ± 5 mm20 ± 5 mm--
Length of grooved part of outletl≥ 40 mm≥ 40 mm--
Distance between seat bolt holesn160 to 175 mm160 to 175 mm160 to 175 mm160 to 175 mm
Diameter of seat bolt holesd₃15 ± 2 mm15 ± 2 mm15 ± 2 mm15 ± 2 mm
Distance back of cistern to outlet (P-trap) or centre line (S-trap)gMin 70 to 85 mmMin 70 to 85 mm- to 85 mm70 mm -
Radius of free space from outlet centred₄₂75
12Marking and Certification

IS 2556 Part 8: Marking and Certification - Key Points

BIS Certification Marking (Clause 12.2)

  • Standard Mark Usage: Products may be marked with the BIS Standard Mark as per Clause 12.2.1.
  • Regulation: Use of the Standard Mark is governed by the Bureau of Indian Standards Act, 1986 (Clause 12.2.2).
  • Licensing: Manufacturers must obtain a license from BIS to use the Standard Mark.
  • Copyright: BIS holds copyright of all publications; reproduction requires prior permission except for necessary implementation details.

Important Contacts for BIS Licensing and Queries

RegionAddress & Contact Details
CentralManak Bhavan, 9 Bahadur Shah Zafar Marg, New Delhi 110002 <br>Tel: 2323 7617, 2323 3841
Eastern1/14 C.I.T. Scheme VII M, V.I.P. Road, Kolkata 700054 <br>Tel: 2337 8499, 2337 8561
NorthernSCO 335-336, Sector 34-A, Chandigarh 160022 <br>Tel: 260 3843, 260 9285
SouthernC.I.T. Campus, IV Cross Road, Chennai 600113 <br>Tel: 2254 1216, 2254 1442
WesternManakalaya, E9 MIDC, Marol, Andheri (East), Mumbai 400093 <br>Tel: 2832 9295, 2832 7858

Summary:

  • Marking: BIS Standard Mark indicates conformity to IS 2556 Part 8.
  • Certification: Must be licensed by BIS.
  • Legal Framework: Governed by BIS Act, 1986.
  • Contact BIS for licensing and detailed conditions.
flowchart LR
    A[Manufacturer] --> B{Apply for BIS License}
    B -->|Approved| C[Use BIS Standard Mark]
    B -->|Rejected| D[No Marking Allowed]
    C --> E[Product Market]
    D --> E

For detailed licensing conditions, contact the nearest BIS regional office.

Popular Questions About IS 2556 Part 8

?What are the specific design patterns covered for pedestal close-coupled water closets?

IS 2556 Part 8 specifies the following design patterns for pedestal close-coupled water closets:

  • Pattern 1: Double trap syphonic pattern with 'S' trap or 'P' trap
    (Refer Fig. 1A & 1B)

  • Pattern 2: Single trap syphonic pattern with 'S' trap or 'P' trap
    (Refer Fig. 1A & 1B)

  • Pattern 3: Washdown pattern with 'P' trap or 'S' trap, including concealed 'S' trap
    (Refer Fig. 2A, 2B, 3A & 3B)

  • Pattern 4: Washdown pattern with horizontal outlet
    (Refer Fig. 4A & 4B)

Key Functional Dimensions (all in mm):

ParameterPattern 1 & 2 (Syphonic)Pattern 3 (Washdown)Pattern 4 (Washdown Horizontal)
Height (H)390 ± 10390 ± 10390 ± 10
Width (W)360 ± 10360 ± 10360 ± 10
Depth of water seal (DI)≥ 50≥ 50≥ 50
Water surface (Back to front)-≥ 150≥ 150
Water surface (Side to side)-≥ 110≥ 110
Distance from seal bolt holes to front (D2)415 to 445415 to 445415 to 445
Length of opening (P)≥ 290≥ 290≥ 290
Width of opening (Q)≥ 240≥ 240≥ 240

Additional Notes:

  • Inside surfaces and traps must be uniformly glazed and smooth.
  • Pattern 4 outlets must not have grooves or serrations and must be glazed outside.
  • Flushing cisterns are low-level coupled type conforming to IS 774 or IS 7231.
Loading diagram...
?Which trap types and outlet configurations are permitted under this standard?

According to IS 2556 Part 8:

Permitted Trap Types & Outlet Configurations (Clause 5.2):

  • Integral traps must be either:
    • 'S' trap (Fig. 1)
    • 'P' trap (Fig. 2)
    • Concealed 'S' trap (Fig. 3)
    • Horizontal outlet (Fig. 4)

Key Dimensions (Table 2, Clause 6.1):

Outlet TypeInternal Dia. (d1)Outlet Angle (e)Height of Outlet Center (h1)Other Notes
Syphonic P or S Outlet80 mm min104°180 ± 10 mm (P-trap only)S-trap end to floor: 20±5 mm
Washdown P or S Outlet80 mm min104°180 ± 10 mm
Washdown Concealed S-trap80 mm min-180 ± 10 mmOutlet extends 32 ± 5 mm into floor
Washdown Horizontal Outlet80 mm min90°180 ± 10 mmStraight glazed outlet length 40 mm min

Additional Notes:

  • Water seal depth minimum: 50 mm (Clause 4B)
  • Outlet surfaces must be uniformly glazed and smooth.
  • Washdown patterns require 'P' or 'S' traps or concealed 'S' trap (Clause 4.3).
  • Seat bolt hole spacing: 160 to 175 mm.

Loading diagram...

Summary: IS 2556 Part 8 permits 'S', 'P', concealed 'S' traps, and horizontal outlets with specified dimensions and glazing for water closets.

?What performance tests must a water closet pass to comply with IS 2556 Part 8?

According to IS 2556 Part 8 (2004), a water closet (WC) must pass the following performance tests:

1. Flushing Test (Clause 9.5 & 9.6.1)

  • WC fixed to a low-level coupled cistern (IS 774 or IS 7231 compliant).
  • WC charged with coloured water to design water seal level.
  • Flush activated; observe splash.
  • Acceptable splash: Isolated droplets ≤ 10 on floor; more leads to rejection.

2. Load Bearing Test (Clause 10)

  • WC fixed firmly on floor.
  • Apply a load of 400 ± 5 kg (or force of 4 ± 0.5 kN) on a 100 mm × 100 mm wooden beam across WC opening.
  • Load maintained for 1 hour.
  • No damage or defects allowed.

3. Additional Requirements

  • WC must be one-piece with at least two floor fixing holes (≥ 6.5 mm diameter).
  • Flushing rim and inlet must be self-draining and weep-hole provided.
  • Inside surfaces must be glazed smooth and uniform.

Summary Table

Test TypeParametersAcceptance Criteria
Flushing TestFlush with coloured water≤ 10 isolated droplets splash allowed
Load Bearing400 ± 5 kg / 4 ± 0.5 kN for 1 hourNo damage or defect

These ensure functional efficiency and structural integrity of the WC per IS 2556 Part 8.

?How are dimensions and tolerances defined for functional and connecting parts?

IS 2556 Part 8: Dimensions and Tolerances for Functional & Connecting Parts

1. Functional Dimensions (Clause 6.1, Table 1)

  • These include all dimensions except connecting parts, critical for WC function.
  • Key dimensions (all in mm) for different WC patterns (Syphonic, Washdown):
    • Height (H): 390 ± 10
    • Width (W): 360 ± 10
    • Depth of water seal (DI): Minimum 50
    • Distance from seal bolt hole center to front (D2): 415 to 445
    • Length & Width of opening (P & Q): Minimum 290 & 240 respectively
    • Other parameters like water surface dimensions, trap inlet depth, seat bolt hole distances are specified per pattern.

2. Connecting Dimensions (Clause 6.1, Table 2)

  • Critical for plumbing connections.
  • Key dimensions (all in mm):
    • Internal diameter of outlet (d1): Minimum 80
    • External diameter of outlet (d2): 102 ± 5
    • Height of outlet center from floor (h1): 180 ± 10 (P-trap)
    • Length of grooved outlet part (l): Minimum 40 (where applicable)
    • Distance between seat bolt holes (n): 160 to 175
    • Diameter of seat bolt holes (d3): 15 ± 2
    • Angle of outlet (e): Typically 104° or 90° depending on type

3. Tolerances (Clause 6.2)

  • If not specified, tolerances follow IS 2556 Part 1.
  • Ovality of outlet diameters is permissible within given limits.

Summary Table Snippet (Functional Dimensions)

ParameterValue (mm)Notes
Height (H)390 ± 10All patterns
Width (W)360 ± 10All patterns
Water Seal Depth (DI)≥ 50Minimum
Seal Bolt Hole to Front (D2)415-445Critical for seat fixing

Summary Table Snippet (

?What are the requirements for flushing cistern compatibility and installation?

IS 2556 Part 8: Flushing Cistern Compatibility & Installation Requirements

  • Cistern Type: Must be low-level coupled type conforming to IS 774 or IS 7231.
  • Capacity: Use the flushing cistern capacity for which the WC appliance is designed.
  • Connection: Provide a resilient gasket at the back inlet to ensure a leak-proof joint (Clause 5.3).
  • Positioning: The cistern and lid should be entirely below a plane passing through the seat fixing holes, inclined at ≥ 8° to vertical for seat stability (see Fig. 5).
  • Testing: WC must pass flushing tests (Clauses 9.1 to 9.6) when connected in normal working position to the specified cistern.
  • Design: Inlet and overflow may be from the bottom of the cistern; no separate flush pipe needed if so designed.
  • Surface Finish: Inside surfaces must be smooth and uniformly glazed for efficient flushing.

Key Functional Dimensions (mm)

ParameterValue
Height (H)390 ± 10
Width (W)360 ± 10
Water Seal Depth (DI)≥ 50
Seat Bolt Hole to Flush Rim (D4)≤ 80
Seat Fixing Angle≥ 8°
Loading diagram...

Summary: Use a low-level coupled cistern with specified capacity and leak-proof connection; position cistern below seat fixing plane for stability; ensure smooth WC surfaces; and conduct flushing tests per IS 2556 Part 8.

Need Detailed Clause Answers?

Ask AI about any clause, requirement, or provision in IS 2556 Part 8. Get instant, clause-cited responses powered by our indexed library.