IS 2556 Part 16:2002 specifies the requirements for vitreous china wash down wall mounted water closets, focusing on construction patterns, dimensions, tolerances, performance tests, and installation criteria. It applies to manufacturers, designers, and engineers involved in the production, selection, and installation of wall mounted water closets to ensure hygienic, durable, and standardized sanitary fixtures in buildings.
Overview
IS 2556 Part 16:2002 specifies the requirements for vitreous china wash down wall mounted water closets, focusing on construction patterns, dimensions, tolerances, performance tests, and installation criteria. It applies to manufacturers, designers, and engineers involved in the production, selection, and installation of wall mounted water closets to ensure hygienic, durable, and standardized sanitary fixtures in buildings.
Audience
Contents
Structure
IS 2556 (Part 16) : 2002 — Scope & Key Specifications for Wall Mounted Water Closets
| Description | Pattern 1 | Pattern 2 |
|---|---|---|
| Height (A) | 350 | 350 |
| Depth of water seal, Min (H) | 50 | 50 |
| Width (J) | 360 ± 10 | 360 ± 10 |
| Seat bolt hole to front (K) | 415 to 445 | 415 to 445 |
| Seat bolt hole to flush rim back, Max (L) | 80 | 80 |
| Width of opening, Min (P) | 240 | 240 |
| Length of opening, Min (Q) | 290 | 290 |
| Overall length (S) | 500 to 575 | 500 to 575 |
| Trap inlet depth, Min (T) | 75 | 75 |
| Water surface (Back to front W) | ≥150 | ≥150 |
| Water surface (Side to side W) | ≥110 | ≥110 |
| Description | Pattern 1 | Pattern 2 |
|---|---|---|
| Internal dia of inlet (E) | 55 +3/-1 | 50 ± 3 |
| Depth of socket, Min (F) | 25 | 25 |
| Internal dia of outlet, Min (D) | 80 | 80 |
| External dia of outlet (DI) | 102 ± 5 | 102 ± 5 |
| Free space around outlet (D2/2) | 75 | 75 |
| Distance from supply plane (f) | 15 | 15 |
| Distance between fixing holes center-line (n) | 230 ± 5 | 180 ± 5 |
| Size of fixing hole | Circular 20 ± 2 mm | Oval (30×25)±3 or (20×12)±2 |
| Diameter of seat bolt hole (M) | 15 ± 2 | 15 ± 2 |
| Angle |
IS 2556 (Part 16) - General Requirements & Key Specifications for Wall Mounted Water Closets
| Description | Pattern 1 | Pattern 2 |
|---|---|---|
| Height (A) | 350 | 350 |
| Depth of water seal, Min (H) | 50 | 50 |
| Width of water closet (J) | 360 ± 10 | 360 ± 10 |
| Seat bolt hole to front (K) | 415 to 445 | 415 to 445 |
| Seat bolt hole to flush rim back, Max (L) | 80 | 80 |
| Vertical line from back plate tip to rim, Max (O) | 70 | 70 |
| Width of opening, Min (P) | 240 | 240 |
| Length of opening, Min (Q) | 290 | 290 |
| Overall length (S) | 500 to 575 | 500 to 575 |
| Trap inlet depth, Min (T) | 75 | 75 |
| Water surface: Back to front (W₁) | 150 min | 150 min |
| Water surface: Side to side (W₂) | 110 min | 110 min |
| Description | Pattern 1 | Pattern 2 |
|---|---|---|
| Internal dia of inlet (E) | 55 +3/-1 | 50 ± 3 |
| Depth of socket, Min (F) | 25 | 25 |
| Internal dia of outlet, Min (D) | 80 | 80 |
IS 2556 Part 16 — Wall Mounted Water Closets: Key Patterns, Dimensions & Specifications
| Description | Pattern 1 | Pattern 2 |
|---|---|---|
| Height (A) | 350 | 350 |
| Depth of water seal, Min (H) | 50 | 50 |
| Width of WC (J) | 360 ± 10 | 360 ± 10 |
| Seat bolt hole to front (K) | 415–445 | 415–445 |
| Seat bolt hole to inside flush rim (L), Max | 80 | 80 |
| Vertical line from back plate tip to rim (O), Max | 70 | 70 |
| Width of opening, Min (P) | 240 | 240 |
| Length of opening, Min (Q) | 290 | 290 |
| Overall length (S) | 500–575 | 500–575 |
| Trap inlet depth, Min (T) | 75 | 75 |
| Water surface back to front (W₁), Min | 150 | 150 |
| Water surface side to side (W₂), Min | 110 | 110 |
| Description | Pattern 1 | Pattern 2 |
|---|---|---|
| Internal dia of inlet (E) | 55 +3/-1 | 50 ± 3 |
| Depth of socket, Min (F) | 25 | 25 |
| Internal dia of outlet, Min (D) | 80 | 80 |
| External dia of outlet (D₁) | 102 ± 5 | 102 ± 5 |
| Free space around outlet center up to 40 mm (D₂/2) | 75 | 75 |
| Distance to face of |
IS 2556 (Part 16): Dimensions & Tolerances for Wall Mounted Water Closets
| Description | Pattern 1 | Pattern 2 |
|---|---|---|
| Height (A) | 350 | 350 |
| Depth of water seal, Min (H) | 50 | 50 |
| Width of water closet (J) | 360 ± 10 | 360 ± 10 |
| Distance seat bolt hole to front (K) | 415 to 445 | 415 to 445 |
| Distance seat bolt hole to inside flush rim (L) | Max 80 | Max 80 |
| Distance vertical line from back plate tip to rim (O) | Max 70 | Max 70 |
| Width of opening, Min (P) | 240 | 240 |
| Length of opening, Min (Q) | 290 | 290 |
| Overall length (S) | 500 to 575 | 500 to 575 |
| Trap inlet depth, Min (T) | 75 | 75 |
| Water surface (Back to front W₁) | Min 150 | Min 150 |
| Water surface (Side to side W₂) | Min 110 | Min 110 |
| Description | Pattern 1 | Pattern 2 |
|---|---|---|
| Internal dia of inlet (E) | 55 +3 / -1 | 50 ± 3 |
| Depth of socket, Min (F) | 25 | 25 |
| Internal dia of outlet, Min (D) | 80 | 80 |
| External dia of outlet (D₁) | 102 ± 5 | 102 ± 5 |
| Free space around outlet center up to 40 mm (D₂/2) | Min 75 | Min 75 |
| Distance to face of supply supporting plane (f₁) | Min 15 | Min 15 |
| Horizontal distance from supporting plane (f₂ |
IS 2556 (Part 16): Construction & Fixing Arrangements for Wall Mounted Water Closets
| Description | Pattern 1 | Pattern 2 |
|---|---|---|
| Height (A) | 350 | 350 |
| Depth of water seal, Min (H) | 50 | 50 |
| Width of WC (J) | 360 ± 10 | 360 ± 10 |
| Seat bolt hole to front (K) | 415 to 445 | 415 to 445 |
| Seat bolt hole to flush rim back (L) | Max 80 | Max 80 |
| Width of opening, Min (P) | 240 | 240 |
| Length of opening, Min (Q) | 290 | 290 |
| Overall length (S) | 500 to 575 | 500 to 575 |
| Trap inlet depth, Min (T) | 75 | 75 |
| Description | Pattern 1 | Pattern 2 |
|---|---|---|
| Internal dia of inlet (E) | 55 +3/-1 | 50 ± 3 |
| Depth of socket, Min (F) | 25 | 25 |
| Internal dia of outlet, Min (D) | 80 | 80 |
| External dia of outlet (DI) | 102 ± 5 | 102 ± 5 |
| Distance between fixing holes center-line (n) | 230 ± 5 | 180 ± 5 |
| Diameter of seat bolt hole (M) | 15 ± 2 | 15 ± 2 |
| Angle of outlet (X) | 90 ± 3° | 104 ± 3° |
| Distance between seat bolt holes center (N) | 155 ± 10 | 165 +10/-5 |
IS 2556 (Part 16): Flushing and Performance Tests Summary
| Parameter | Pattern 1 & 2 | Unit (mm) |
|---|---|---|
| Height (A) | 350 | mm |
| Min Water Seal Depth (H) | 50 | mm |
| Width (J) | 360 ± 10 | mm |
| Distance seat bolt to front (K) | 415 to 445 | mm |
| Trap inlet depth (T) | 75 | mm |
| Water surface back-front (W) | ≥ 150 | mm |
| Water surface side-side (W) | ≥ 110 | mm |
| Parameter | Pattern 1 | Pattern 2 | Unit (mm) |
|---|---|---|---|
| Internal dia of inlet (E) | 55 +3/-1 | 50 ± 3 | mm |
| Depth of socket (F) | ≥ 25 | ≥ 25 | mm |
| Internal dia of outlet (D) | ≥ 80 | ≥ 80 | mm |
| External dia of outlet (DI) | 102 ± 5 | 102 ± 5 | mm |
| Distance between fixing holes (n) | 230 ± 5 | 180 ± 5 | mm |
| Diameter of seat bolt hole (M) | 15 ± 2 | 15 ± 2 | mm |
| Angle of outlet (X) | 90 ± 3° | 104 ± 3° | degrees |
IS 2556 Part 16: Load and Stability Test Key Points
| Parameter | Value |
|---|---|
| Load | 400 ± 15 kg (≈ 4 ± 0.15 kN) |
| Load Application Beam | 100 mm × 100 mm cross-section |
| Load Duration | 1 hour |
| Surface Preparation | Smooth wall + mortar pointing |
flowchart LR
A[Wall Mounted WC] --> B[Mortar Bed on Smooth Wall]
B --> C[Load Application]
C --> D[Wooden Beam 100x100 mm]
D --> E[Load 400 ± 15 kg for 1 hour]
E --> F[Check for Stability & Damage]
Note: Follow IS 2:1960 for rounding off test values as per specified precision.
Sampling, Process Inspection, and Lot Inspection as per IS 2556 (Part 16):
| Inspection Type | Purpose | Basis of Acceptance |
|---|---|---|
| Sampling | Select representative samples | Random or systematic sampling |
| Process Inspection | Control during production | Continuous monitoring & corrective action |
| Lot Inspection | Final batch acceptance | Based on acceptance quality level (AQL) |
flowchart TD
A[Start Production] --> B[Process Inspection]
B --> |If OK| C[Continue Production]
B --> |If Not OK| D[Correct Process]
C --> E[Sampling]
E --> F[Lot Inspection]
F --> |Accept| G[Dispatch Lot]
F --> |Reject| H[Rework or Reject Lot]
For detailed sampling plans and acceptance criteria, refer directly to IS 9140.
IS 2556 (Part 16): 2002 - Marking and Certification Key Points
| Aspect | Details |
|---|---|
| Applicable Products | Wall-mounted water closets |
| Governing Law | BIS Act, 1986 |
| Licensing Authority | Bureau of Indian Standards |
| Purpose | Quality assurance and standard compliance |
| Marking Location | On the product (visible marking) |
flowchart LR
A[Manufacturer] --> B[Apply for BIS License]
B --> C{BIS Evaluation}
C -->|Compliant| D[License Granted]
C -->|Non-Compliant| E[License Denied]
D --> F[Use Standard Mark on Product]
F --> G[Market Product with BIS Certification]
Note: No specific formulas or tables for marking are provided in IS 2556 (Part 16). The focus is on compliance and licensing for use of the BIS Standard Mark.
| Description | Pattern 1 | Pattern 2 |
|---|---|---|
| Height (A) | 350 | 350 |
| Depth of water seal, Min (H) | 50 | 50 |
| Width of water closet (J) | 360 ± 10 | 360 ± 10 |
| Distance seat bolt hole to front (K) | 415 to 445 | 415 to 445 |
| Distance seat bolt hole to flush rim back (L) Max | 80 | 80 |
| Width of opening, Min (P) | 240 | 240 |
| Length of opening, Min (Q) | 290 | 290 |
| Overall length (S) | 500 to 575 | 500 to 575 |
| Trap inlet depth, Min (T) | 75 | 75 |
| Description | Pattern 1 | Pattern 2 |
|---|---|---|
| Internal dia of inlet (E) | 55 +3/-1 | 50 ± 3 |
| Depth of socket, Min (F) | 25 | 25 |
| Internal dia of outlet, Min (D) | 80 | 80 |
| External dia of outlet (DI) | 102 ± 5 | 102 ± 5 |
| Distance between fixing holes center-line (n) | 230 ± 5 | 180 ± 5 |
| Distance between seat bolt holes (N) | 155 ± 10 | 165 +10/-5 |
| Size of fixing hole (D3) | Circular 20±2 | Oval (30×25)±3 |
| Dia of seat bolt hole (M |
Frequently Asked
IS 2556 Part 16: Wall Mounted Water Closets (WC) Patterns & Construction
| Parameter | Pattern 1 (mm) | Pattern 2 (mm) |
|---|---|---|
| Height (A) | 350 | 350 |
| Depth of water seal (H) | ≥ 50 | ≥ 50 |
| Width (J) | 360 ± 10 | 360 ± 10 |
| Seat bolt hole to front (K) | 415 to 445 | 415 to 445 |
| Overall length (S) | 500 to 575 | 500 to 575 |
| Parameter | Pattern 1 (mm) | Pattern 2 (mm) |
|---|---|---|
| Internal dia of inlet (E) | 55 +3/-1 | 50 ± 3 |
| Internal dia of outlet (D) | ≥ 80 | ≥ 80 |
| Distance between fixing holes (n) | 230 ± 5 | 180 ± 5 |
| Seat bolt hole diameter (M) | 15 ± 2 | 15 ± 2 |
| Angle of outlet (X) | 90 ± 3° | 104 ± 3° |
Loading diagram...
According to IS 2556 (Part 16): 2002, manufacturers must adhere to the following dimensional tolerances for inlet and outlet connections of wall mounted water closets:
| Parameter | Pattern 1 | Pattern 2 |
|---|---|---|
| Internal diameter of inlet (E) | 55 mm +3 / -1 | 50 mm ± 3 |
| Depth of socket (F), Min | 25 mm | 25 mm |
| Internal diameter of outlet, Min (D) | 80 mm | 80 mm |
| External diameter of outlet (DI) | 102 mm ± 5 | 102 mm ± 5 |
| Free space around outlet center (D2/2), Min | 75 mm | 75 mm |
| Distance from supply supporting plane to face (f) | 15 mm | 15 mm |
| Horizontal distance from supporting plane to outlet face (f2), Min | 15 mm | 15 mm |
| External cylindrical part of outlet (R), Min | 40 mm | 40 mm |
| Distance between centre-line of fixing hole (n) | 230 mm ± 5 | 180 mm ± 5 |
| Size of fixing hole | Circular 20 ± 2 mm or Oval (30×25) ± 3 mm | Oval (20×12) ± 2 mm or Circular 15 ± 2 mm |
| Diameter of seat bolt hole (M) | 15 mm ± 2 | 15 mm ± 2 |
| Angle of outlet (X) | 90° ± 3 | 104° ± 3 |
This ensures interchangeability and proper fitment with drainage and installation fixtures.
Loading diagram...
Performance Tests for Flushing Efficiency & Discharge Capability (IS 2556 Part 16)
Toilet Paper Test (Clause 8.1):
Holding Capacity Test (Clause 8.3):
General Requirements (Clause 8.3 and 6.3):
| Test Name | Requirement | Acceptance Criteria |
|---|---|---|
| Toilet Paper Test | 6 paper pieces, 4 flushes | 3 flushes must clear paper fully |
| Holding Capacity Test | WC sealed, holds water | ≥10 litres without leakage |
Loading diagram...
These tests ensure WC flushing efficiency and discharge capability per IS 2556 Part 16.
Installation and Load-Bearing Requirements for Wall Mounted Water Closets (IS 2556 Part 16):
Construction: Must be one-piece with integral flushing rim (box/open rim or combination) and self-draining flushing inlet with weep-hole.
Fixing: Minimum two fixing holes for secure installation using corrosion-resistant bolts/nuts and an independent concealed support frame (metal hanger/carrier). The frame must be anchored to structural members to avoid strain on plumbing.
Mounting Surface: Fixed on a smooth surface with a mortar or facing material layer between WC back and wall.
Load Test: Must withstand a load of 400 ± 15 kg (approx. 4 ± 0.15 kN) applied for 1 hour via a 100 mm × 100 mm wooden beam across the WC top opening without damage.
Support Frame Patterns: Refer to Fig. 3 & 4 for support frame/carrier details ensuring stability.
Loading diagram...
This ensures secure installation, durability, and compliance with IS 2556 Part 16.
According to IS 2556 Part 16, the finishing of water closet (WC) surfaces and flushing rims must adhere to these key points:
Summary Table:
| Feature | Requirement |
|---|---|
| Interior surface finish | Quartz powder smudged & flushed, no residue |
| Surface smoothness | Uniform and smooth inside surface and trap |
| Outlet finish | Glazed if no serration; serrated may be unglazed |
| Flushing rim | Integral, box/open/combined rim with holes |
| Flushing rim & inlet | Self-draining with weep-hole |
This ensures hygiene, durability, and effective flushing performance.