IS 2440:1975 provides comprehensive guidance on the principles and methods for effective daylighting in buildings such as dwellings, offices, and hospitals. It establishes minimum illumination levels, correction factors for glazing and obstructions, and design recommendations to optimize natural light while minimizing glare. This standard is essential for architects, engineers, and designers aiming to enhance indoor lighting quality through daylighting strategies tailored to Indian climatic and site conditions.
Overview
IS 2440:1975 provides comprehensive guidance on the principles and methods for effective daylighting in buildings such as dwellings, offices, and hospitals. It establishes minimum illumination levels, correction factors for glazing and obstructions, and design recommendations to optimize natural light while minimizing glare. This standard is essential for architects, engineers, and designers aiming to enhance indoor lighting quality through daylighting strategies tailored to Indian climatic and site conditions.
Audience
Contents
Structure
IS 2440 - Scope: Sky Component Tables & Calculations
The code provides tables and methods to calculate the Sky Component (SC) for daylighting analysis through vertical windows under a tropical clear sky.
Scope:
Applies to unglazed openings illuminated by the clear tropical design sky.
Tables Included (Appendix A):
Calculation Method (Appendix B):
Use the tables to find percentage SC values based on window orientation and plane of interest.
[ SC = \frac{E_{i}}{E_{o}} \times 100 ]
| Plane Type | Table No. | Description |
|---|---|---|
| Horizontal | 5 | SC % due to vertical window |
| Vertical (Perpendicular) | 6 | SC % on plane perpendicular to window |
| Vertical (Parallel) | 7 | SC % on plane parallel to window |
flowchart LR
A[Start: Identify Window Orientation] --> B{Select Plane}
B --> C[Horizontal Plane (Table 5)]
B --> D[Vertical Perpendicular Plane (Table 6)]
B --> E[Vertical Parallel Plane (Table 7)]
C --> F[Find % SC from Table 5]
D --> G[Find % SC from Table 6]
E --> H[Find % SC from Table 7]
F & G & H --> I[Calculate SC & Apply in Daylighting Design]
Use these tables and methods to accurately estimate daylight availability through vertical openings under tropical sky conditions.
IS 2440: Definitions & Key Tables for Sky Component Calculation
| Table No. | Description | Plane Type | Orientation to Window |
|---|---|---|---|
| 5 | Percentage sky components on horizontal plane | Horizontal | Due to vertical window |
| 6 | Percentage sky components on vertical plane | Vertical (perpendicular) | Perpendicular to vertical window |
| 7 | Percentage sky components on vertical plane | Vertical (parallel) | Parallel to vertical window |
[ SC = \frac{\text{Visible sky area through window}}{\text{Total sky hemisphere}} \times 100% ]
graph TD
A[Observer Point] -->|Horizontal Plane| B(Horizontal Plane)
A -->|Vertical Plane Perpendicular| C(Vertical Plane ⟂ Window)
A -->|Vertical Plane Parallel| D(Vertical Plane || Window)
E[Vertical Window] --> C
E --> D
This framework helps determine daylight availability and solar exposure through windows as per IS 2440.
IS 2440: Factors Affecting Vision – Key Points & Formulas
| Condition | Adjustment Factor to DF |
|---|---|
| Clear glazing | 1.0 |
| Tinted glazing | 0.7 - 0.9 |
| External obstruction | 0.5 - 0.8 |
| Window bars present | 0.6 - 0.9 |
flowchart LR
A[Daylight Factor (DF)] --> B[Window Size from Appendix A]
B --> C[Width & Height]
A --> D[Adjust for Glazing/Obstruction]
D --> E[Effective DF]
E --> F[Visual Comfort]
F --> G[Central 2° Brighter & Contrasting]
Use these guidelines to optimize window design for adequate vision and glare control per IS 2440.
IS 2440: Sources of Daylighting – Key Points & Formulas
[ DF = \frac{E_i}{E_o} \times 100% ]
| Parameter | Source/Clause | Notes |
|---|---|---|
| Primary daylight source | 4.1 | Sky radiation only |
| Glare control methods | 3.2.3 | Louvers, reveals, cross-light |
| Window design basis | 7.1.1 | Daylight factor & penetration |
| PSC variation | Fig. 2 | Distance from window sill |
flowchart LR
Sunlight -->|Direct solar (excluded)| NoInteriorLight
Sunlight -->|Sky radiation (used)| InteriorLight
InteriorLight --> WindowDesign
WindowDesign -->|
IS 2440: Daylight Components and Corrections
Daylight Factor (DF) = Sum of three components, each expressed as % of simultaneous external horizontal illumination:
| Mean Angle of Elevation | Correction Factor |
|---|---|
| 5° | 0.086 |
| 15° | 0.086 |
| 25° | 0.142 |
| 35° | 0.192 |
| 45° | 0.226 |
| 55° | 0.274 |
| 65° | 0.304 |
| 75° | 0.324 |
| 85° | 0.334 |
flowchart LR
A[External Horizontal Illumination] --> B[Sky Component (SC)]
A --> C[Externally Reflected Component (ERC)]
B & C --> D[Window]
D --> E[Internal Reflected Component (IRC)]
E --> F[Daylight Factor = SC + ERC + IRC]
Summary:
Use the three daylight components with correction factors for ERC and IRC based on surface reflectances
IS 2440: Daylight Factor & Illumination Levels
Daylight Factor (DF):
[
DF = \frac{\text{Indoor illuminance at a point}}{\text{Outdoor illuminance under overcast sky}} \times 100%
]
(Clause 2.7)
Design External Illumination:
Assumed as 8,000 lux for India (Clause 4.3).
Increase by 25% in hazy conditions.
| Location | Daylight Factor (%) |
|---|---|
| Dwellings | |
| Kitchen | 2 – 5 |
| Living room | 0 – 6.25 |
| Study | 1.9 |
| Circulation | 0 – 3.13 |
| Schools | |
| Classroom | 1.9 |
| Lecture theatre | 2.0 – 2.5 |
| Study hall | 2.0 – 2.5 |
| Laboratory | 1.9 – 3.8 |
| Offices | |
| General | 1 – 9 |
| Drawing | 3.75 |
| Enquiry | 0.625 – 1.9 |
| Hospitals | |
| General ward | 1.25 |
| Pathological lab | 2.5 – 3.75 |
| Libraries | |
| Stack room | 0.9 – 1.9 |
| Reading room | 1.9 – 3.75 |
| Counter area | 2.5 – 3.75 |
| Catalogue room | 1.9 – 2.5 |
[ E_{inside}
IS 2440: General Principles of Window Design for Good Daylighting
Example: For a point 300 cm from window sill, window width 180 cm, height 150 cm:
[ SC = f(l/d, h/d) ]
where (f) is obtained from tables/graphs in Appendix A.
flowchart LR
A[Window Width = 180 cm] -->|Half width = 90 cm| B(l)
C[Distance from point to window sill = 300 cm] --> D(d)
E[Window Height = 150 cm] --> F(h)
B --> G[l/d = 0.3]
F --> H[h/d = 0.5]
D --> G
D --> H
Note: Always correct sky component values for glazing and external obstructions for accurate daylight factor estimation.
IS 2440: Key Points on Siting of Buildings (Clause 8)
| Separation Distance (S) | Infinitely Long Parallel Blocks | Parallel Blocks Facing Each Other (Length = 2 × H) | Parallel Blocks Facing Gaps (Length = 2 × H) |
|---|---|---|---|
| 0.5 H | 0.15 | 0.15 | 0 - 0.25 |
| 1.0 H | 0.30 | 0.32 | 0.38 |
| 1.5 H | 0.40 | 0.50 | 0.55 |
| 2.0 H | 0.50 | 0.60 | 0.68 |
[ S \geq k \times H ]
where (k) is a factor (typically 1.5 to 2.0) depending on layout and daylight requirements.
flowchart LR
A[Building Height (H)] --> B[Determine Separation (S)]
B --> C{Type of Block Layout}
C -->|Parallel Blocks| D[Use Table values for daylight]
C -->|Facing Each Other| E[Use Table values for daylight]
C -->|Facing Gaps| F[Use Table values for daylight]
D & E & F --> G[Optimize spacing for daylight]
This ensures adequate daylight, ventilation, and comfort in building siting per IS 2440.
IS 2440: Calculation of Sky Component (Clause 5.4, Appendix B)
Given:
Calculate ratios: [ l/d = \frac{90}{300} = 0.3, \quad h/d = \frac{150}{300} = 0.5 ]
Use these ratios to locate the sky component % from Table 5 (horizontal plane).
| Parameter | Symbol | Value | Unit |
|---|---|---|---|
| Half window width | ( l ) | 90 | cm |
| Distance from window | ( d ) | 300 | cm |
| Window height | ( h ) | 150 | cm |
| Ratio ( l/d ) | - | 0.3 | - |
| Ratio ( h/d ) | - | 0.5 | - |
flowchart TD
A[Input Window Dimensions] --> B[Calculate l/d and h/d]
B --> C[Refer to Table 5 (Horizontal Plane)]
C --> D[Read % Sky Component]
D --> E[Use in Daylighting Calculations]
This method ensures accurate daylight factor estimation per IS 2440.
IS 2440: Sky Component Tables Key Points
[ SC = f(\text{window size}, \text{point location}, \text{orientation}) ]
Where (f) is obtained by combining values from Tables 5, 6, and 7.
flowchart LR
A[Point Location] --> B[Table 5: Horizontal Plane]
A --> C[Table 6: Vertical Plane Perpendicular]
A --> D[Table 7: Vertical Plane Parallel]
B & C & D --> E[Combine Values]
E --> F[Sky Component in Any Plane]
For detailed interpolation and usage, refer to Appendix B of IS 2440.
IS 2440: Calculation of Sky Component (Appendix B & A)
For a point P at distance d from the window, with window half-width l and height h:
[ l/d = \frac{\text{half window width}}{\text{distance to point}} \quad,\quad h/d = \frac{\text{window height}}{\text{distance to point}} ]
Example:
flowchart TD
A[Start: Point P distance d from window] --> B[Calculate l/d and h/d]
B --> C{Use Table 5?}
C -- Yes --> D[Find sky component from Table 5]
C -- No --> E[Use Tables 6 & 7 for complex cases]
D --> F[Apply sky component in daylight calculations]
E --> F
This method ensures accurate daylight factor estimation per IS 2440.
IS 2440: General Notes on Daylighting
Scope (Clause 1.1):
Applies to dwellings, offices, hospitals; recommends minimum daylight illumination levels.
Window Design Principles (Clause 7.2):
Window dimensions (width & height) are selected based on:
Daylight Factor (DF):
[
\text{DF} = \frac{\text{Indoor illuminance due to daylight}}{\text{Outdoor illuminance under overcast sky}} \times 100%
]
Percentage Sky Component (PSC):
PSC curves (Fig. 2) show how sky visibility changes with distance from window sill on the working plane.
flowchart TD
A[Select Space Type] --> B[Choose Desired Daylight Factor (DF)]
B --> C[Decide Depth of Daylight Penetration]
C --> D[Refer Appendix A for Window Size]
D --> E[Check Percentage Sky Component (PSC) Curves]
E --> F[Finalize Window Design]
Summary: IS 2440 guides daylighting by linking window size to desired daylight factor and penetration depth, ensuring adequate natural illumination inside buildings.
Frequently Asked
Correction Factors for Glazed Windows and External Obstructions (IS 2440)
Glazing Correction (Clause 5.3.4):
External Obstructions (Clause 5.3.5):
| Condition | Correction Factor on Sky Components |
|---|---|
| Clear glazed windows | Reduce by 10% to 20% |
| Frosted glazed windows | Reduce by 15% to 30% |
| External obstructions | Use unobstructed window area only |
Loading diagram...
Note: Always combine these corrections with those for window bars and other obstructions as per Clause 5.3.2.
IS 2440 Definition and Calculation of Daylight Factor (DF):
Definition (Clause 2.7):
Daylight Factor is the ratio (or percentage) of indoor illumination at a point on a plane to the simultaneous outdoor illumination on a horizontal plane under a clear sky, excluding direct sunlight.
Components (Clause 5.2 & 5.2.1):
DF is the sum of three components:
Formula (Clause 5.2.3):
[
\boxed{
DF = SC + ERC + IRC
}
]
This approach ensures a comprehensive measure of daylight reaching an indoor point, accounting for all light paths except direct sunlight.
Loading diagram...
According to IS 2440, the recommended minimum illumination levels on the working plane are guided by:
| Visual Task Type | Recommended Illumination (lux) |
|---|---|
| Fine work | 500 - 1000 |
| Medium work | 200 - 500 |
| Coarse work | 100 - 200 |
Ensure lighting design respects these levels and brightness ratios for optimal visual comfort.
According to IS 2440, glare can be minimized by:
Shielding bright sky views through windows using:
Cross lighting the surrounding wall to balance brightness levels, reducing contrast.
Ensuring a gradual transition of brightness within the field of vision to avoid abrupt changes that cause discomfort.
Loading diagram...
Summary: Use shading devices and balanced lighting to reduce contrast and glare, enhancing visual comfort indoors.
IS 2440 Guidelines on Building Siting for Daylight Optimization
Clause 8.1 & 8.2: Proper layout and orientation of building masses significantly reduce mutual obstruction and enhance daylight penetration. Table 4 quantifies daylight availability for different block orientations and separations.
Clause 8.4: Building height and spacing must be balanced to optimize daylight for any site density (floor area to site area ratio).
| Separation (× Height) | Infinitely Long Parallel Blocks | Parallel Blocks Facing Each Other (Length = 2× Height) | Parallel Blocks Facing Gaps |
|---|---|---|---|
| 0.5 | 0.15 | 0.15 | 0.25 |
| 1.0 | 0.30 | 0.32 | 0.38 |
| 1.5 | 0.40 | 0.50 | 0.55 |
| 2.0 | 0.50 | 0.60 | 0.68 |
Loading diagram...
This approach ensures good daylighting per IS 2440 for multistorey buildings.
Ask AI about any clause, requirement, or provision in IS 2440. Get instant, clause-cited responses powered by our indexed library.
Free tier includes 150 queries (50 AI + 100 Reference) · No credit card required