Specification for portable fire extinguishers, dry powder (cartridge type)

IS 2171:1999 specifies the requirements for portable dry powder fire extinguishers of cartridge type used for Class A, B, and C fires. It covers materials, construction, chemical charges, anti-corrosive treatments, performance tests, and marking requirements to ensure reliable and effective fire suppression. This standard is essential for manufacturers, quality controllers, and safety engineers involved in producing or specifying portable dry powder fire extinguishers in India.

13Sections
114Clauses Indexed
AI Search Ready
1999Edition
Fire FightingCategory
Alternative search terms: IS 2171 PDF, IS 2171 pdf free download, IS 2171 free download pdf, IS2171 PDF, IS-2171 PDF, IS 2171 1999 PDF, IS 2171:1999 PDF, IS 2171-1999 PDF, IS 2171 (1999) PDF, IS 2171 1999 edition PDF, IS 2171 edition 1999 PDF

What This Standard Covers

IS 2171:1999 specifies the requirements for portable dry powder fire extinguishers of cartridge type used for Class A, B, and C fires. It covers materials, construction, chemical charges, anti-corrosive treatments, performance tests, and marking requirements to ensure reliable and effective fire suppression. This standard is essential for manufacturers, quality controllers, and safety engineers involved in producing or specifying portable dry powder fire extinguishers in India.

Who Uses This Standard

  • Fire safety engineers
  • Fire extinguisher manufacturers
  • Quality assurance professionals
  • Safety compliance officers
  • Procurement specialists in safety equipment
  • Fire protection consultants
  • Maintenance technicians

Key Topics Covered

Materials of construction for extinguisher components
Body shape and dimensions
Welding and brazing requirements
Anti-corrosive coatings and treatments
Chemical composition and environmental considerations
Performance testing including discharge and pressure tests
Marking and labeling requirements
Sampling and conformity criteria
Ageing and UV exposure tests
Burst pressure and hydraulic pressure tests
Nozzle and discharge fitting specifications
Safety features such as piercing mechanism and safety clips

Table of Contents

1Scope

IS 2171: Scope - Key Specifications & Tables

1. Scope Overview

  • Covers cylindrical body shape for fire extinguisher containers.
  • Specifies dimensions for extinguisher capacities.
  • References multiple Indian Standards (Annex A) for materials, welding, testing, and coatings.

2. Body Dimensions (Clause 6.1)

Capacity (kg)Outside Diameter (mm)Filler Opening Size (mm)
175 - 80≥ 35
2100 - 110≥ 45
5150 - 160ID 65 - 68, OD 77 - 80
10175 - 185ID 75 - 78, OD 87 - 90
  • ID = Inside Diameter, OD = Outside Diameter

3. Referenced Indian Standards (Annex A)

  • IS 2062: Steel for general structural purposes
  • IS 2190: Installation and maintenance of fire extinguishers
  • IS 4947: Gas cartridges for fire extinguishers
  • IS 1239 (Part 1): Mild steel tubes
  • IS 5382: Rubber sealing rings
  • IS 6240: Hot rolled steel plates for gas cylinders
  • Others covering welding, coatings, plastics, and powders.

4. Additional Notes

  • Sampling and conformity criteria detailed in Annex B.
  • Encouraged to use latest editions of referenced standards.

flowchart LR
    A[Fire Extinguisher Body] --> B[Cylindrical Shape]
    B --> C{Capacity}
    C -->|1 kg| D[Diameter: 75-80 mm]
    C -->|2 kg| E[Diameter: 100-110 mm]
    C -->|5 kg| F[Diameter: 150-160 mm]
    C -->|10 kg| G[Diameter: 175-185 mm]
    C --> H[Filler Opening Size]
    H -->|1 kg| I[≥ 35 mm]
    H -->|2 kg| J[≥ 45 mm]
    H -->|5 kg| K[ID 65-
2Referenced Indian Standards

IS 2171 Referenced Indian Standards Summary

  • Clause 2.1 & Annex A: IS 2171 references multiple Indian Standards (IS) that form integral provisions of this code. These cover materials, welding, testing, and safety related to pressure vessels and structural steel.

Key Referenced IS Standards (Samples)

IS No.TitleRemarks
2062Steel for general structural purposes (4th rev.)Structural steel specification
1239 (Part 1)Mild steel tubes (5th rev.)Tubular steel fittings
819Code of practice for resistance spot weldingWelding guidelines
6912Copper and copper alloy forging stock and forgingsForging specifications
6240Hot rolled steel plate & strip for gas cylindersMaterial for pressure vessels
4454 (Part 1)Steel wires for cold formed springsSpring wire specification

Important Notes

  • Thickness calculation (Clause 7.2): Minimum shell thickness = 1.4 mm; use modified formula with factor 300 (not 360).
  • Certification & Sampling: Details in Annex B, with criteria for conformity.
  • Standards are subject to revision; always check for latest editions.

Typical Thickness Formula (Clause 7.2 Amendment)

[ t = \frac{P \times D}{2 \times \sigma \times E} \quad \text{with } \sigma = \text{allowable stress}, E = \text{joint efficiency} ]

Where factor 300 replaces 360 in design calculations.


Diagram: IS 2171 Referenced Standards Integration

graph LR
A[IS 2171] --> B[Material Specs (IS 2062, IS 1239)]
A --> C[Welding Codes (IS 819)]
A --> D[Testing Methods (IS 3203, IS 5762)]
A --> E[Fire Safety (IS 2190, IS 4308)]
A --> F[Certification & Sampling (Annex B)]

Summary: IS 2171 integrates multiple IS codes covering materials, welding, testing, and safety. Always verify the latest versions for compliance.

5Materials of Construction

IS 2171: Materials of Construction for Fire Extinguishers

Key Materials (Table 1, Clause 5.1)

ComponentMaterial(s)Indian Standard (IS)
BodyMild steel sheet / Stainless steel sheetIS 513, IS 2062, IS 6240, IS 6911
Inner shellMild steel sheet / PlasticIS 513 / IS 7328
Neck ringLeaded tin bronze / Brass forging / Mild steel pipeIS 318 (LTB 2), IS 6912, IS 1239
CapLeaded tin bronze / Brass / Plastic / Stainless steelIS 318, IS 6912, Annex B, IS 6529
SpringCarbon steelIS 4454 (Part 1)
Syphon tubeMild steel / Brass / PlasticIS 3601, IS 407, IS 7328
Nozzle & fittingAluminium alloy / Leaded tin bronze / Brass / PlasticIS 617, IS 318, IS 291, Annex B
CartridgeSteelIS 4947
HoseBraided PVC/rubber, bursting pressure ≥ 50 kgf/cm²IS 14933
Safety clipSteel / PlasticIS 2507, IS 7328

Shell Thickness Calculation (Clause 7.2)

  • Minimum thickness: 1.4 mm

  • Formula for Carbon Steel Body:

[ t = \frac{P \times D}{300 \times \sigma} + 0.7 \text{ mm} ]

  • Where:
    • ( t ) = minimum thickness (mm)
    • ( P ) = design pressure (N/mm²)
    • ( D ) = external diameter (mm)
    • ( \sigma ) = allowable stress (N/mm²)

Note: Use 300 instead of 360 as per Amendment No. 3.


Welding Standards (Clause 7.2.1)

  • Oxy-acet
6Shape and Dimensions

IS 2171 Key Specifications for Shape and Dimensions of Fire Extinguisher Body

1. Shape

  • The body shall be cylindrical (Clause 6.1).

2. Dimensions (Clause 6.1, Table 6)

Capacity (kg)Outside Diameter (mm)Filler Opening Size (mm)
175 - 80Not less than 35
2100 - 110Not less than 45
5150 - 160ID: 65 - 68, OD: 77 - 80
10175 - 185ID: 75 - 78, OD: 87 - 90

3. Thickness of Shell (Clause 7.2)

  • Minimum thickness = 1.4 mm.
  • Thickness shall be calculated by formula (with substitution of 300 for 360 in bursting pressure formula):

[ t = \frac{P \times d}{2 \times \sigma \times \eta} ]

Where:

  • ( t ) = thickness (mm)

  • ( P ) = design pressure (kgf/cm²)

  • ( d ) = diameter (mm)

  • ( \sigma ) = allowable stress (kgf/cm²)

  • ( \eta ) = joint efficiency (usually ≤ 1)

  • Minimum thickness also governed by ( t \geq \frac{d}{100} ).

4. Construction

  • Welded type body.
  • Thickness:
    • Up to 5 kg capacity: ≥ 1.6 mm
    • 10 kg capacity: ≥ 2.0 mm (Clause 1.6, Annex B)

flowchart TD
    A[Extinguisher Capacity] --> B{Diameter & Thickness}
    B -->|1 kg| C[Diameter: 75-80 mm]
    B -->|2 kg| D[Diameter: 100-110 mm]
    B -->|5 kg| E[Diameter: 150-160 mm]
    B -->|10 kg| F[Diameter: 175-185 mm]
    C
7Construction Requirements

IS 2171: Construction Requirements Summary

1. General Requirements (Clause 12.1)

  • Construction must ensure mechanical strength, durability, and safety under operating conditions.
  • Materials must be compatible with the extinguishing agent.
  • Dimensions and tolerances should follow specified standards for interchangeability.

2. Specific Requirements (Clause 12.2)

  • Design must prevent leakage and withstand internal pressure.
  • Joints and welds should be leak-proof and corrosion-resistant.
  • Valve and nozzle fittings must ensure reliable operation.

3. Materials (Clause 5.1, Table 1 excerpt)

PartMaterial Specification
Cylinder BodyMild Steel / Seamless Steel
Valve BodyBrass / Bronze
HoseRubber / Synthetic
Handle / LeverSteel / Aluminum Alloy

4. Paint (Clause 10.4)

  • Paint must conform to IS 2932 for fire extinguisher finish.
  • Typically, red enamel paint for visibility and corrosion protection.

5. Testing (Clause 11)

  • Hydrostatic pressure test to verify strength.
  • Leak test on joints and valves.
  • Functional test for valve operation.

Key Formula: Hydrostatic Test Pressure

[ P_{test} = 1.5 \times P_{working} ]

  • Where ( P_{working} ) = Maximum working pressure.

flowchart TD
    A[Material Selection] --> B[Fabrication]
    B --> C[Painting (IS 2932)]
    C --> D[Assembly]
    D --> E[Testing (Hydrostatic, Leak)]
    E --> F[Final Inspection]

This ensures safe, durable, and reliable fire extinguisher construction per IS 2171.

8Chemical Charges

IS 2171: Key Specifications for Chemical Charges in Dry Powder Extinguishers

1. Chemical Charge Capacity (Clause 4.1)

Nominal Capacity (kg)Dry Powder Content (kg) ±5% Tolerance
11
22
55
1010

2. Chemical Properties (Clause 1.1, Table B-1)

PropertyTest MethodRequirement
Specific GravityIS 8543 Part 1/Sec 21.25 ± 0.02
Melting PointIS 5762215°C - 225°C
Ash ContentIS 718815 ± 2%

3. Chemical Type and Environmental Compliance

  • Use BC or ABC class dry powder conforming to IS 4308 or IS 14609.
  • Chemicals must not have global warming potential (Clause 12.2.3, Annex G).

Summary:

  • Match powder weight exactly to extinguisher capacity ±5%.
  • Ensure powder meets physical properties for performance and safety.
  • Use eco-friendly chemicals compliant with IS standards.
flowchart TD
    A[Extinguisher Capacity] --> B[Dry Powder Charge ±5%]
    B --> C[Chemical Properties Check]
    C --> D[Specific Gravity 1.25 ± 0.02]
    C --> E[Melting Point 215-225°C]
    C --> F[Ash Content 15 ± 2%]
    B --> G[Chemical Type: BC or ABC]
    G --> H[Conforms to IS 4308 or IS 14609]
    G --> I[No Global Warming Potential]
9Anti-Corrosive Treatment

IS 2171: Anti-Corrosive Treatment Key Points

1. Coating Requirements (Clause 9.1)

  • Internal surfaces: Coated with lead-tin alloy (tin ≥ 10%) by hot-dipping.
  • Minimum thickness: 0.012 mm (measured as per IS 3203).
  • External surfaces: Also coated (body, inner shell, siphon tube, spring if mild steel).
  • No visible uncoated areas allowed internally or externally.

2. Alternative Treatment (Clause 9.1.1)

  • Phosphating per IS 3618 can replace lead-tin coating on external surfaces.

3. Dry Powder Coating (Clause 8.1)

  • Use dry powder of BC or ABC Class conforming to IS 4308 or IS 14609.

4. Acid Resistance Test (Clause 3.1)

  • Submerge sample in 10% HCl at 27 ± 5°C for 72 hours.
  • No discoloration, distortion, or deterioration allowed.

Summary Table: Anti-Corrosive Treatment

ParameterSpecification
Lead-Tin Alloy Tin %≥ 10%
Coating Thickness≥ 0.012 mm
Coating MethodHot-dipping
Alternative CoatingPhosphating (IS 3618)
Dry Powder StandardIS 4308 or IS 14609 (BC or ABC Class)
Acid Resistance Test10% HCl, 72h, 27 ± 5°C, no deterioration

flowchart TD
    A[Internal Surface] -->|Hot-dip Lead-Tin Alloy| B(Coating ≥ 0.012 mm)
    C[External Surface] -->|Lead-Tin Alloy or Phosphating| B
    B --> D[No Visible Uncoated Areas]
    E[Dry Powder Coating] --> F[BC or ABC Class per IS 4308/14609]
    G[Acid Resistance Test] --> H[10% HCl, 72h at 27±5°C]
    H --> I[No Dis
10Finish and Marking

IS 2171: Finish and Marking - Key Points

  • Finish (Clause 10.4):
    Paint shall conform to IS 2932 (Specification for paint used on fire extinguishers). This ensures corrosion resistance and durability.

  • Marking (Clause 13.1 & Table 12.2):
    Marking must follow BIS certification requirements. Details on sampling and conformity criteria are provided in Annex B.

  • Bottom Ring (Clause 7.12):
    Mild steel bottom ring/skirting of minimum thickness 3 mm is mandatory for structural protection.

  • Paint Colours:
    Refer IS 5:1994 for colours of ready mixed paints and enamels.

  • Standards Referenced for Finish & Marking:

    • IS 2932: Paint specification
    • IS 5:1994: Paint colours
    • IS 4308 / IS 14609: Powder types for extinguisher filling (Class BC & ABC)

Summary Table: Finish & Marking Requirements

AspectSpecification / ClauseDetails
PaintIS 2932 (Clause 10.4)Corrosion resistant paint
Bottom RingClause 7.12Mild steel, min. 3 mm thick
MarkingClause 13.1, Table 12.2, Annex BBIS certification & conformity
Paint ColoursIS 5:1994Standard paint colours
Powder FillingIS 4308 / IS 14609 (Clause 10.3)For Class BC & ABC extinguishers

flowchart TD
    A[Fire Extinguisher] --> B[Surface Preparation]
    B --> C[Paint Application]
    C --> D{Paint per IS 2932?}
    D -- Yes --> E[Apply Bottom Ring (3 mm mild steel)]
    D -- No --> F[Reject]
    E --> G[Marking per BIS (Clause 13.1)]
    G --> H[Final Inspection & Sampling (Annex B)]

This ensures fire extinguishers have durable finish, correct markings, and meet BIS standards for safety and quality.

11Performance Tests

IS 2171: Performance Tests Key Points (Clause 11.1)

Performance Test Requirements for Dry Powder Fire Extinguishers:

Capacity (kg)Min. Throw as Jet (sec)Max. Period to Discharge ≥85% Rated Capacity (sec)Range of Throw (m)
1 and 2810≥ 2
51520≥ 4
102330≥ 6
  • The extinguisher must discharge ≥ 85% by mass of rated capacity.
  • Test conducted at 27 ± 5°C with nozzle at 45° above horizontal.
  • Discharge must be continuous and meet throw duration and range.
  • Expansion space and other parameters per Clause 7.3 must be verified on a sample.

Additional Notes:

  • The test ensures operational reliability and efficiency.
  • Refer Annex B for sampling and conformity criteria.
  • Related standards for materials and components are listed in Annex A.

flowchart LR
    A[Start Performance Test] --> B{Check Capacity}
    B -->|1 or 2 kg| C[Min throw 8s, Max discharge 10s, Range ≥ 2m]
    B -->|5 kg| D[Min throw 15s, Max discharge 20s, Range ≥ 4m]
    B -->|10 kg| E[Min throw 23s, Max discharge 30s, Range ≥ 6m]
    C --> F[Discharge ≥ 85% mass?]
    D --> F
    E --> F
    F -->|Yes| G[Test Passed]
    F -->|No| H[Test Failed]

For detailed design and testing, always cross-check with IS 2171 full text and related standards.

12Marking and Labeling

IS 2171: Marking and Labeling Key Points

Clause 12.1: Mandatory Markings on Extinguishers Each extinguisher must be clearly and permanently marked with:

  • Manufacturer's name or trademark
  • Method of operation (prominently displayed)
  • Words: "Dry Powder Extinguisher"
  • Capacity of extinguisher (in kg)
  • Capacity of gas cartridge

Clause 10.3: Fire Class Marking

  • Letters A, B, C indicate suitability for respective fire classes (per IS 2190).
  • Letter size and background dimensions:
Capacity (kg)Letter Size (cm)Square Size (cm)Circle Radius (cm)Color of Square & Circle
≥ 32.5 ± 0.54 ± 0.52 ± 0.5Blue (IS 5 Shade No.166)
1 to 21.5 ± 0.22 ± 0.21 ± 0.2Blue (IS 5 Shade No.166)
  • Letters are white, centrally contained in the square and circle.

Clause 12.2.1: Use of BIS Standard Mark

  • Governed by BIS Act 1986 and related rules.
  • License conditions available from BIS.

Summary Table for Marking Dimensions

Marking ElementSize for ≥3 kgSize for 1-2 kgColor Details
Letter (A/B/C)2.5 ± 0.5 cm1.5 ± 0.2 cmWhite
Square4 ± 0.5 cm2 ± 0.2 cmBlue (IS 5 Shade No.166)
Circle Radius2 ± 0.5 cm1 ± 0.2 cmBlue (IS 5 Shade No.166)

flowchart LR
    A[Extinguisher] --> B[Markings]
    B --> C[Manufacturer
13Sampling and Criteria for Conformity

IS 2171: Sampling and Criteria for Conformity - Key Points

Sampling Procedure (Clause 1.2.1 & Annex C)

  • Samples are taken randomly from a lot as per C-1.2.2 and C-1.2.3 (details in Annex B).
  • Fire extinguishers require high reliability; hence strict sampling and testing are mandatory.
  • Samples undergo accelerated aging:
    • 100 min exposure to XERON ARC U.V. at 27 ± 5°C
    • Followed by 20 min at 62 ± 5°C and 60 ± 5% RH
    • Repeat cycle 60 times (Clause 3.3)
  • Post aging, samples must pass internal hydraulic pressure tests (B-3.3).

Criteria for Conformity (Annex B)

  • Sampling size and acceptance criteria are based on lot size and defect limits (details in Annex B Table 1).
  • Fire extinguisher samples must meet physical and performance tests to confirm conformity.

BIS Certification (Clause 12.2.1)

  • Use of Standard Mark governed by BIS Act, 1986.
  • Licensing conditions available from BIS.

Summary Table: Sampling & Testing Cycle

Test StageConditionsDurationCycles
UV Exposure (XERON ARC U.V.)27 ± 5°C100 min60
Heat & Humidity Exposure62 ± 5°C, 60 ± 5% RH20 min60
Hydraulic Pressure TestAs per B-3.3-After cycles

Note:

Refer Annex B for detailed sampling numbers and acceptance criteria tables.

flowchart TD
    A[Random Sampling from Lot] --> B[UV Exposure 27±5°C, 100 min]
    B --> C[Heat & Humidity 62±5°C, 60±5% RH, 20 min]
    C --> D{Repeat 60 Cycles}
    D -->|Yes| B
    D -->|No| E[Hydraulic Pressure Test]
    E --> F{Pass/Fail}
    F -->|Pass| G[Con
Annex AList of Referenced Standards

IS 2171 - List of Referenced Standards & Key Specifications

1. Referenced Indian Standards (Annex A Highlights)

IS No.Title
IS 5 : 1994Colours for ready mixed paints and enamels
IS 2062 : 1992Steel for general structural purposes
IS 819 : 1957Code of practice for resistance spot welding
IS 1323 : 1982Code of practice for oxy-acetylene welding
IS 1239 (Part 1) : 1990Mild steel tubes and fittings
IS 6912 : 1985Copper and copper alloy forging
IS 7328 : 1992High density polyethylene materials
IS 5382 : 1985Rubber sealing rings for gas mains, water mains
IS 4454 (Part 1) : 1981Steel wires for cold formed springs

Note: These standards cover materials, welding, testing, and components used in fire extinguisher manufacturing.


2. Materials of Construction (Annex B, Table 1)

ComponentMaterial(s)Reference IS No.
BodyMild steel sheetIS 513, IS 2062, IS 6240
Inner ShellMild steel sheet / PlasticIS 513 / IS 7328
Neck ringLeaded tin bronze / Brass forging / Steel pipeIS 318 / IS 6912 / IS 1239(Part 1)
CapLeaded tin bronze / Brass forging / Plastic / Stainless steelIS 318 / IS 6912 / Annex B / IS 6529
SpringCarbon steelIS 4454 (Part 1)
CartridgeSteelIS 4947
HoseBraided PVC/rubber (burst pressure ≥ 50 kgf/cm²)Specified in Annex B

3. Welding Specifications (Clause 7.2.1)

  • Oxy-acetylene welding: As per IS 1323.
  • Resistance spot welding: For fittings, as
Annex DCommittee Composition

IS 2171: Committee Composition - Key Details

Committee Composition is detailed in Annex D (Foreword) of IS 2171, covering the Fire Fighting Sectional Committee, CED 22.

Key Points:

  • Chairman: Shri Om Prakash (Fire Adviser), Ministry of Home Affairs, New Delhi.
  • Members: Representatives from various government departments, fire services, industries, research institutes, and private companies.
  • Alternate Members: Each main member has an alternate to ensure continuity.
  • Ex-officio Member: Shri Vinod Kumar, Director (Civil Engineering), Director General, BIS.
  • Member Secretary: Shri Sanjeev Chaturvedi, Joint Director (Civil Engineering), BIS.

Committee Representation Includes:

  • Ministry of Home Affairs, Defence, Railways, Police Departments.
  • Fire Services from Delhi, West Bengal, Maharashtra, Andhra Pradesh.
  • Industrial representatives from Steel Authority of India, Oil & Natural Gas Commission, and private fire safety companies.
  • Research organizations like CSIR, Bhabha Atomic Research Centre.
  • Standardization and quality assurance bodies.

Summary Table of Key Roles

RoleRepresentativeOrganization
ChairmanShri Om PrakashMinistry of Home Affairs
MembersMultiple (Govt., Industry, Research)Various (listed above)
Ex-officio MemberShri Vinod KumarDirector General, BIS
Member SecretaryShri Sanjeev ChaturvediBIS

This composition ensures multi-sectoral expertise for standard development in fire fighting equipment.

graph LR
A[Chairman] --> B[Members]
B --> C[Government Departments]
B --> D[Fire Services]
B --> E[Industry Representatives]
B --> F[Research Institutes]
B --> G[Private Companies]
A --> H[Member Secretary]
H --> I[BIS]

Note: For detailed names and affiliations, refer to Annex D of IS 2171.

Popular Questions About IS 2171

?What materials are specified for the construction of dry powder fire extinguishers?

Materials for Dry Powder Fire Extinguisher Construction (IS 2171 Clause 5.1, Table 1):

ComponentMaterial(s) & Relevant IS Standards
BodyMild steel sheet (IS 513, IS 2062, IS 6240)
Inner ShellMild steel sheet (IS 513) or Plastic (IS 7328)
Neck RingLeaded tin bronze (IS 318 Grade LTB 2), Brass forging (IS 6912 Grade FLB), or Seamless mild steel pipe (IS 1239 Part 1)
CapLeaded tin bronze (IS 318 Grade LTB 2), Brass forging (IS 6912 Grade FLB), Plastic (Annex B), Stainless steel (IS 6529)
Cap WasherRubber (acid/alkali resistant, hardness per IS 5382 Type 3)
PlungerBrass (IS 291 Grade 2 or IS 391 Type 1), Stainless steel (IS 6528)
Cartridge HolderLeaded tin bronze (IS 318 Grade LTB 2), Brass (IS 291 Grade 2 or IS 319 Type 1)
PiercerStainless steel (IS 6528)
SpringCarbon steel (IS 4454 Part 1 Grade 1)
Syphon TubeMild steel (IS 3601), Brass (IS 407 Alloy No. 2), or Plastic (IS 7328)
Nozzle & DischargeAluminium alloy (IS 617 Grades 4450 or 4225), Leaded tin bronze (IS 318 Grade LTB 2), Brass (IS 291 Grade 2 or IS 319 Type 1), Plastic (Annex B)
CartridgeSteel (IS 4947)
HoseBraided PVC/rubber, bursting pressure ≥ 50 kgf/cm² (IS 14933)
Safety ClipSteel (IS 2507 Grade 1) or Plastic (IS 7328)

**

?What are the required performance tests for cartridge type dry powder extinguishers?

Required Performance Tests for Cartridge Type Dry Powder Extinguishers (IS 2171):

  1. Discharge Test (Clause 11.1):
    • Must discharge ≥85% by mass of rated dry powder at 27 ± 5℃, nozzle at 45° above horizontal.
    • Continuous discharge with minimum throw duration and range as per capacity:
Capacity (kg)Min. Throw Duration (sec)Max. Discharge Time (sec)Min. Throw Range (m)
1 & 28102
515204
1023306
  1. Hydraulic Pressure Test (Clause 11.2):

    • Body and cap assembly tested at 3.0 MN/m² (30 kgf/cm²) for 2 minutes, no leakage allowed.
  2. Thread Durability & Pressure Cycle Test (Clause 3.3):

    • Screw/unscrew sample 100 times without damage.
    • Internal hydraulic pressure test at 45 kgf/cm² for 1 min (pressure built over 30 s), no leakage.
    • Thermal cycling: 72 h at 60 ± 1ºC, then 72 h at 5 ± 1ºC, repeated 3 times with 24 h gaps.
    • After cycles, no discoloration, distortion or leakage allowed.
  3. Internal Pressure Safety (Clause 1.5):

    • Space above powder ensures pressure ≤1.5 MN/m² (15 kgf/cm²) at 27 ± 5℃ without leakage.

Loading diagram...
?How should the extinguisher body be coated to prevent corrosion?

According to IS 2171 Clause 9, the extinguisher body must be protected against corrosion as follows:

  • Internal surfaces:

    • Coated with lead-tin alloy (tin ≥ 10%) by hot-dipping, thickness ≥ 0.012 mm (measured per IS 3203).
    • Alternatively, coated with epoxy polyester powder with thickness ≥ 0.050 mm, or lined with plastic/rubber coating ≥ 0.5 mm thick.
  • External surfaces and components (inner shell, siphon tube, springs if mild steel):

    • Same anti-corrosive treatment as internal surfaces (lead-tin alloy or epoxy powder coating).
    • No visible uncoated areas allowed.

Summary Table

SurfaceCoating TypeMinimum Thickness
InternalLead-tin alloy (hot-dip)0.012 mm
InternalEpoxy polyester powder0.050 mm
InternalPlastic/rubber lining0.5 mm
External & ComponentsSame as internalSame as internal

This ensures comprehensive corrosion protection of extinguisher bodies.

?What marking and labeling information must be displayed on the extinguisher?

According to IS 2171, the following marking and labeling must be clearly and permanently displayed on a dry powder extinguisher:

  • Manufacturer's name or trademark
  • Method of operation in prominent letters
  • The words "Dry Powder Extinguisher"
  • Capacity of extinguisher (in kg)
  • Capacity of gas cartridge
  • Letters 'A', 'B', 'C' indicating fire class suitability, with size and color as per IS 2190:
    • For >2 kg: Letters 2.5 ± 0.5 cm, white color, inside blue square (4 ± 0.5 cm) and circle (2 ± 0.5 cm radius)
    • For 1-2 kg: Letters 1.5 ± 0.2 cm, inside smaller blue square (2 ± 0.2 cm) and circle (1 ± 0.2 cm radius)
  • Declaration of pressure test: Body tested to 3.0 MN/m² (30 kgf/cm²)
  • Year of manufacture
  • A pictorial instruction showing correct operation of the extinguisher

This ensures clear identification, usage guidance, and safety compliance.

Loading diagram...
?What environmental requirements apply to the chemical charges used in these extinguishers?

According to IS 2171, the environmental requirements for chemical charges in fire extinguishers are:

  • No Ozone Depleting Substances (ODS): Clause 12.2.1 prohibits use of any ODS listed under the Montreal Protocol (Annex E), e.g., Halons, CFCs with ODPs from 0.1 to 10.0.
  • Gas-based agents atmospheric life: Clause 12.2.2 states gas agents must have an atmospheric lifetime ≤ 1 year (Annex F), minimizing long-term environmental impact.
  • Global Warming Potential (GWP): Annex G lists GWP values; preference should be for agents with low or no GWP.
  • No toxic heavy metals in coatings: Clause 12.2.5 forbids mercury, lead, cadmium, chromium VI in metallic coatings.

Key Tables Summary:

RequirementDetails
ODS bannedHalon 1211, 1301, CFC-11, 12, etc. (Annex E)
Max atmospheric life≤ 1 year for gas agents (Annex F)
GWP considerationPrefer agents with low GWP (Annex G)
Coating restrictionsNo mercury, lead, cadmium, chromium VI

This ensures the extinguisher chemicals are environmentally safe and compliant with international protocols.