IS 137161993AI Search Enabled✦ AI Generated

Code of practice for fire safety of hotels

IS 13716:1993 is the Indian Standard code of practice for fire safety in hotels, providing comprehensive guidelines to minimize fire risks and ensure life safety and property protection. It applies to all hotel buildings, including high-rise and low-rise, covering fire prevention, containment, means of egress, emergency power, and firefighting equipment. This standard is essential for hotel management, engineers, and fire safety professionals to implement effective fire safety measures in compliance with Indian regulations.

11Sections
67Clauses Indexed
AI Search Ready
1993Edition
Fire SafetyCategory
Alternative search terms: IS 13716 PDF, IS 13716 pdf free download, IS 13716 free download pdf, IS13716 PDF, IS-13716 PDF, IS 13716 1993 PDF, IS 13716:1993 PDF, IS 13716-1993 PDF, IS 13716 (1993) PDF, IS 13716 1993 edition PDF, IS 13716 edition 1993 PDF

What This Standard Covers

IS 13716:1993 is the Indian Standard code of practice for fire safety in hotels, providing comprehensive guidelines to minimize fire risks and ensure life safety and property protection. It applies to all hotel buildings, including high-rise and low-rise, covering fire prevention, containment, means of egress, emergency power, and firefighting equipment. This standard is essential for hotel management, engineers, and fire safety professionals to implement effective fire safety measures in compliance with Indian regulations.

Who Uses This Standard

  • Hotel Facility Managers
  • Fire Safety Engineers
  • Building Architects
  • Hotel Operations Managers
  • Fire Officers
  • Safety Compliance Inspectors
  • Civil Engineers

Key Topics Covered

Fire safety management responsibilities
Fire containment and compartmentation
Means of egress and exit requirements
Emergency power supply and lighting
Fire detection and alarm systems
Fire suppression systems including hydrants and sprinklers
Fire resistant construction materials and finishes
Air conditioning and ventilation system fire safety
Boiler and electrical equipment safety
Training and evacuation procedures
Fire safety signage and instructions for guests
Special hazards such as LPG and kitchen fire protection

Table of Contents

1Scope

IS 13716: Scope Summary

  • Scope: This standard covers fire safety requirements for buildings, focusing on construction types, fire protection systems, and management responsibilities.

  • Key References:
    The standard is supplemented by related IS codes for comprehensive fire safety:

    IS CodeTitleYearFocus Area
    IS 1641Fire safety - General principles1988Fire grading & classification
    IS 1642Fire safety - Construction details1989Construction details for fire safety
    IS 1644Fire safety - Exit requirements1988Exit design & personal hazard
    IS 2189Fire detection & alarm systems1988Selection, installation, maintenance
    IS 2190Portable fire extinguishers1992Selection, installation, maintenance
    IS 3844Internal hydrants & hose reels1989Installation & maintenance
    SP 7National Building Code (Part IV)1983Fire protection requirements
  • Type of Construction (Clause 6.2): Specifies construction types relevant for fire safety design.

  • Access & Approach Roads (Clause 4.2): Width, hardness, and distance of approach roads for fire engines must comply with NBC 1983 (Part IV).


Key Takeaway:

IS 13716 integrates fire safety design with other IS codes and NBC provisions to ensure comprehensive fire protection covering construction, equipment, and emergency access.

graph LR
A[IS 13716: Fire Safety] --> B[Construction Types (6.2)]
A --> C[Fire Safety Codes]
C --> D[IS 1641, 1642, 1644]
C --> E[IS 2189, 2190, 3844]
A --> F[Access Roads (4.2) - NBC Part IV]
A --> G[Management Responsibility (5)]

This diagram shows the scope and linked standards under IS 13716.

2Referenced Standards

IS 13716: Fire Safety in Hotels — Referenced Standards & Key Specifications

Referenced Indian Standards (Clause 2.1)

IS No.TitleYear
IS 1641Fire safety: General principles of fire grading and classification1988
IS 1642Fire safety: Details of construction1989
IS 1644Fire safety: Exit requirements and personal hazard1988
IS 2189Selection, installation & maintenance of automatic fire detection & alarm systems1988
IS 2190Selection, installation & maintenance of portable first-aid fire extinguishers1992
IS 3844Installation & maintenance of internal hydrants and hose reels1989
SP 7National Building Code of India1983

Fire Safety Equipment Requirements (Clause 9.1)

  • Internal hydrant/sprinkler system per IS 3844
  • Automatic detection-cum-alarm system per IS 2189
  • Portable fire extinguishers per IS 2190
  • Kitchen hoods require automatic/manual extinguishers (dry powder/CO2)
  • Public address system linked or independent of fire alarm

Important Notes:

  • Halon systems are deleted as per Amendment No. 1 (May 2005).
  • Fire safety provisions supplement statutory regulations (Factory Act, Petroleum Rules, etc.).
  • Rounding off values per IS 2:1960.

Summary Table: Fire Safety Systems in Hotels

System TypeIS CodeKey Function
Internal Hydrant/SprinklerIS 3844Fire suppression
Fire Detection & AlarmIS 2189Early fire detection & alarm
Portable Fire ExtinguishersIS 2190Immediate fire fighting
Exit & Construction DetailsIS 1642, 1644Safe evacuation & fire-resistance

flowchart LR
    A[Fire Safety in Hotels] --> B[Fire Detection (IS 2189)]
    A --> C[Fire Suppression (IS 3844)]
    A --> D[Portable Extinguishers (IS 219
3Classification of Hotels

Classification of Hotels as per IS 13716

  • Definition (Clause 3.1):

    • Hotels = Buildings under same management with >15 sleeping accommodations for hire, primarily for transients, with or without meals. Includes inns, motels, clubs, guest houses.
    • High Rise Hotels: Building height ≥ 15 m
    • Low Rise Hotels: Building height < 15 m
  • Construction Type (Fire Safety):

    • High Rise Hotels (≥ 15 m): Must be Type I construction as per NBC India 1983 (Part IV) Fire Protection (Clause 6.2.1)
    • Low Rise Hotels (< 15 m): Minimum Type II construction as per IS 1642:1989 (Clause 6.2.2)

Summary Table

Hotel TypeBuilding HeightConstruction TypeReference Clause
High Rise Hotel≥ 15 mType I (NBC 1983 Part IV)3.1, 6.2.1
Low Rise Hotel< 15 mMinimum Type II (IS 1642)3.1, 6.2.2

Notes:

  • Fire safety provisions aim to minimize life/property loss due to fire hazards in hotels.
  • Halon fire suppression systems are deleted as per Amendment No. 1 (May 2005).
  • Compliance with other statutory rules (Factory Act, Petroleum Rules, etc.) is mandatory alongside this standard.

flowchart TD
    A[Hotel Building] --> B{Height ≥ 15 m?}
    B -- Yes --> C[High Rise Hotel]
    B -- No --> D[Low Rise Hotel]
    C --> E[Type I Construction (NBC 1983 Part IV)]
    D --> F[Minimum Type II Construction (IS 1642:1989)]

This classification guides fire safety design and construction requirements for hotels under IS 13716.

4General Fire Safety Principles

IS 13716: General Fire Safety Principles - Key Points

1. Fire Safety Aspects (Clause 4.1)

Fire safety is achieved by addressing:

  • Management responsibility
  • Containment of smoke/fire
  • Provision of safety escape routes
  • Emergency power and lighting
  • Provision of fire safety/fighting equipment

2. Fire Safety/Fighting Equipment (Clause 9.1)

All hotel buildings must have:

  • Internal hydrant/sprinkler system (IS 3844:1989)
  • Automatic detection-cum-alarm system (IS 2189:1988)
  • Portable fire extinguishers (IS 2190:1992)
  • Efficient public address system
  • Kitchen hood fire protection (automatic/manual dry powder/CO2 extinguisher)

3. Fire Safety Management

  • Written fire safety policy (Annex A)
  • Responsibility assigned to Chief Executive
  • Every employee must contribute to fire prevention

4. Reference Codes for Fire Safety

IS CodeSubject
IS 1641Fire grading and classification
IS 1642Details of construction for fire safety
IS 1644Exit requirements and personal hazard
IS 2189Fire detection and alarm systems
IS 2190Portable fire extinguishers
IS 3844Internal hydrants and hose reels

Summary Diagram of Fire Safety Principles

graph TD
  A[Fire Safety in Hotels] --> B[Management Responsibility]
  A --> C[Smoke/Fire Containment]
  A --> D[Safety Escape Routes]
  A --> E[Emergency Power & Lighting]
  A --> F[Fire Safety Equipment]
  F --> G[Hydrant/Sprinkler System]
  F --> H[Fire Detection & Alarm]
  F --> I[Portable Extinguishers]
  F --> J[Public Address System]
  F --> K[Kitchen Fire Protection]

Note: Halon systems are deleted from the latest amendment (2005). Always refer to the latest IS codes for updated practices.

5Management Responsibility

IS 13716 - Management Responsibility (Clause 5)

Key points on Management Responsibility in fire safety for hotels:

  • Written Fire Safety Policy (Clause 5.1):
    Management must issue a clear, written fire safety and fire loss control policy to all employees. (Refer Annex A for a sample statement.)

  • Preventive Programs (Clause 5.9):
    Management shall establish and maintain a preventive inspection, testing, and maintenance program for:

    • Fire protection and firefighting systems
    • Machinery and equipment that may cause fire hazards
  • Coordination with NBC (Clause 4.2):
    Management must ensure compliance with National Building Code (Part IV) provisions regarding:

    • Approach road width and hardness for fire engine access
    • Open spaces and parking distances from roads

Summary Table: Management Responsibility Actions

Responsibility AreaAction Required
Fire Safety PolicyIssue written policy to employees
Inspection & MaintenanceSchedule regular preventive checks and tests
Compliance with NBC Fire AccessEnsure approach roads and open spaces meet NBC
Employee Training & AwarenessConduct fire safety training and drills

flowchart TD
    A[Management Responsibility] --> B[Written Fire Safety Policy]
    A --> C[Preventive Inspection & Maintenance]
    A --> D[Compliance with NBC Fire Access]
    A --> E[Employee Training & Awareness]

This structured approach ensures effective fire safety management in hotels as per IS 13716.

6Containment of Smoke and Fire

Containment of Smoke and Fire as per IS 13716 focuses on compartmentation and fire-resistive construction to restrict fire/smoke spread.


Key Clauses Summary:

  • Clause 6.1:
    Use fire-resistive materials and compartmentation to contain smoke/fire.

  • Clause 6.3:
    Restrict fire/smoke spread by design and materials.

  • Clause 5.11:
    Escape routes must be unobstructed and safe:

    • No obstruction to exits or escape routes.
    • Notices and extinguishing equipment must be visible and accessible.
    • Avoid mirrors or reflective surfaces on escape routes.
    • Floor/stair coverings must be firmly fixed to prevent slipping.
    • Max floor occupancy = 60% for free movement.

Important Specifications:

AspectSpecification
Floor OccupancyMax 60% area occupied, 40% free
Escape Route ObstructionNone allowed (doors, signs, equipment)
Fire-resistive ConstructionAs per IS 1641, 1642, 1644
Fire Detection & ExtinguishersAs per IS 2189, 2190, 3844

Reference Standards for Fire Safety Design:

IS CodeDescription
IS 1641Fire grading and classification
IS 1642Details of fire-resistant construction
IS 1644Exit requirements and personal hazard
IS 2189Fire detection and alarm systems
IS 2190Portable fire extinguishers
IS 3844Internal hydrants and hose reels
SP 7National Building Code of India (Fire safety provisions)

Conceptual Diagram of Fire Compartmentation

flowchart LR
    A[Fire Origin] --> B[Fire-Resistive Wall]
    B --> C[Compartment 1]
    B --> D[Compartment 2]
    C --> E[Smoke Barrier]
    D --> E
    E --> F[Escape Route]
    F --> G[Exit]

Summary:
Contain smoke/fire by creating fire-resistant compartments, ensuring escape routes are unobstructed, and controlling occupancy

7Means of Egress

Means of Egress as per IS 13716

Key Specifications:

  • Definition (Clause 1.8): Means of egress includes vertical & horizontal travel paths—rooms, corridors, stairs, ramps, lobbies, exits, etc.
  • Minimum Widths:
    • Corridors/passageways to exit stairs: ≥ 1.5 m
    • Corridors from banquet/dance halls:
      • 50 persons: ≥ 2.0 m

      • ≤50 persons: ≥ 1.8 m
  • Occupancy: Floor occupancy limited to 60%, reserving 40% for free movement.
  • Obstructions (Clause 5.11): No obstruction to exits, escape routes, signage, doors; no mirrors or reflective surfaces on escape routes; floor/stair coverings must prevent slipping/tripping.

Means of Egress Components (Clause 7.1):

  • Exit Access: Path from any point to an exit.
  • Exit: The actual exit point from the building.
  • Exit Discharge: Path from exit to public way.

Summary Table of Corridor Widths

Area TypeOccupancyMinimum Corridor Width (m)
General corridorsAll1.5
Banquet/Dance halls> 50 persons2.0
Banquet/Dance halls≤ 50 persons1.8

flowchart LR
    A[Any Point in Building] --> B[Exit Access]
    B --> C[Exit]
    C --> D[Exit Discharge]
    D --> E[Public Way]

This ensures a continuous, unobstructed path from any location inside the hotel to safety outside.

8Emergency Power Supply and Lighting

IS 13716: Emergency Power Supply and Lighting - Key Points

1. Emergency Illumination Requirements (Clauses 7.4, 7.4.1, 7.4.4)

  • Illumination of exits, corridors, staircases, basements, and exit signage must be maintained by emergency power.
  • Failure of any bulb or connection shall not cause total darkness in any area (redundant lighting or multiple lamps recommended).
  • Emergency lighting can be from:
    • Diesel generator-driven power supply, or
    • Self-contained emergency lights.

2. Stand-by Power Supply (Clause 8.1)

  • Must be independent from normal power supply.
  • Diesel generator(s) capacity must cover:
    • Emergency lighting (exits, corridors, staircases, basements).
    • Mechanical ventilation in basements or centrally air-conditioned buildings.
    • Fire water pumps (unless a separate diesel pump is provided).
    • Other emergency automatic firefighting systems.

3. Typical Specification Table for Emergency Lighting Load

LocationMinimum Illumination (lux)Remarks
Exits and exit signage10 luxContinuous during emergency
Corridors and staircases10 luxUniform lighting
Basements10 luxMechanical ventilation load considered
Fire pump & firefightingAs per equipment ratingIncluded in generator sizing

Generator Sizing Formula (Simplified)

[ \text{Generator Capacity (kVA)} = \frac{\text{Total Emergency Load (kW)}}{\text{Power Factor (usually 0.8)}} ]

  • Include all emergency loads: lighting, ventilation, pumps, firefighting systems.
  • Add 10-20% margin for safety.

flowchart LR
    A[Normal Power Supply] -->|Failure| B[Stand-by Diesel Generator]
    B --> C[Emergency Lighting]
    B --> D[Mechanical Ventilation]
    B --> E[Fire Water Pump]
    B --> F[Firefighting Systems]

Summary:
Ensure emergency lighting is redundant and continuous with an independent diesel generator sized for all critical emergency loads per IS 13716 clauses.

9Fire Safety and Fighting Equipment

IS 13716: Fire Safety & Fighting Equipment - Key Points

Essential Fire Safety Systems (Clause 9.1)

All hotel buildings must have:

  • Internal hydrant/sprinkler system per IS 3844:1989
  • Automatic fire detection & alarm system per IS 2189:1988
  • Automatic emulsifier/Halon system
  • Portable fire extinguishers per IS 2190:1992
  • Public address system integrated or independent of fire alarm
  • Kitchen fire protection: Automatic/manual Halon, CO2, or dry powder extinguishers in hoods and ducts

Stand-by Power Supply (Clause 8.1)

Must support:

  • Emergency lighting (corridors, staircases, basements, exit signs)
  • Mechanical ventilation (basements or central AC)
  • Fire water pump (unless diesel pump backup exists)
  • Other emergency fire fighting systems

Related IS Codes (Clause 2.1)

IS CodeFocus Area
IS 1641:1988Fire grading & classification
IS 1642:1989Fire safety construction details
IS 1644:1988Exit requirements & personal hazard
IS 2189:1988Fire detection & alarm systems
IS 2190:1992Portable fire extinguishers
IS 3844:1989Internal hydrants & hose reels
SP 7:1983National Building Code

Fire Safety Management (Clause 4.1)

Focus on:

  • Management responsibility
  • Smoke/fire containment
  • Safe escape routes
  • Emergency power & lighting
  • Fire safety/fighting equipment provision

Summary Table: Fire Fighting Equipment per IS 13716

EquipmentStandardApplication
Internal Hydrant/SprinklerIS 3844:1989Fire suppression inside building
Fire Detection & AlarmIS 2189:1988Early fire detection & alarm
Portable ExtinguishersIS 2190:1992First-aid fire fighting
Emulsifier/Halon System-Automatic suppression
Public Address System-Emergency communication
Kitchen Fire Protection-Fire suppression in kitchen hoods

flowchart TD
Annex ASample Written Fire Safety Policy

IS 13716: Key Points on Written Fire Safety Policy & Equipment

1. Written Fire Safety Policy (Clause 5.1 & Annex A)

  • Management Responsibility: Hotel management must issue a written fire safety and loss control policy to all employees.
  • Policy Highlights:
    • Commitment to fire prevention and property loss control.
    • Life safety of customers and employees is paramount.
    • Fire safety responsibility vested with the Chief Executive.
    • Every employee must contribute actively to fire prevention.

2. Fire Safety Equipment Requirements (Clause 9.1, Table 9)

All hotel buildings, regardless of height, must have:

Equipment TypeIS Code Reference
Internal hydrant/sprinkler systemIS 3844 : 1989
Automatic detection & alarm systemIS 2189 : 1988
Automatic emulsifier/Halon system-
Portable fire extinguisherIS 2190 : 1992
Public address systemCoupled or independent
Kitchen hood fire protectionAutomatic/manual Halon, CO2, or dry powder extinguisher

3. Related Indian Standards (Clause 2.1)

  • IS 1641, 1642, 1644: Fire safety building codes.
  • IS 2189: Fire detection & alarm systems.
  • IS 2190: Portable fire extinguishers.
  • IS 3844: Internal hydrants & hose reels.
  • SP 7: National Building Code of India.

Summary Diagram: Fire Safety Management Framework

graph TD
    A[Hotel Management] --> B[Written Fire Safety Policy]
    B --> C[Employee Awareness & Responsibility]
    A --> D[Fire Safety Equipment Installation]
    D --> E[Internal Hydrants & Sprinklers (IS 3844)]
    D --> F[Detection & Alarm Systems (IS 2189)]
    D --> G[Portable Extinguishers (IS 2190)]
    D --> H[Kitchen Fire Protection]
    C --> I[Fire Prevention & Loss Control]

Use this policy and equipment framework to ensure compliance and safety in hotel buildings as per IS 13716.

Annex BCommittee Composition

IS 13716 - Committee Composition (Fire Safety Sectional Committee, CED 36)

Key Points:

  • The committee includes representatives from various sectors:

    • Government bodies (e.g., Ministry of Defence, Ministry of Home Affairs, Central Public Works Department)
    • Fire authorities (e.g., Chief Fire Officer, Municipal Corporations)
    • Engineering institutions (e.g., Institution of Engineers, Institution of Fire Engineers)
    • Industry experts (e.g., Tata Consulting Engineers, Bharat Heavy Electricals Ltd)
    • Private sector and consultants (e.g., Lloyds Institution, Vijay Fire Protection Systems)
  • Member Secretary: Shri Hemant Kumar, Joint Director (Civil Engineering), BIS

  • Ex-officio Member: Shri Y. R. Taneja, Director General, BIS


Summary Table of Committee Composition:

RoleRepresentation
ChairpersonShri J. N. Vakil (Tariff Advisory Committee)
MembersEngineers, Fire Officers, Govt. Ministries, Industry Experts
Member SecretaryShri Hemant Kumar (BIS)
Ex-officio MemberShri Y. R. Taneja (Director General, BIS)

Related Standards Referenced in IS 13716:

IS CodeDescription
IS 3844Internal hydrant and hose reel installation
IS 2189Automatic fire detection and alarm system
IS 2190Portable fire extinguisher selection and maintenance
IS 1641Fire grading and classification
IS 1642Details of construction for fire safety
IS 1644Exit requirements and personal hazard
SP 7National Building Code of India (Fire Protection)

This committee ensures the standard's technical robustness by involving multidisciplinary experts, aligning with national fire safety codes and practices.

Popular Questions About IS 13716

?What are the minimum requirements for fire exits and staircases in hotels according to IS 13716?

According to IS 13716:1993 referencing IS 1644:1988, the minimum requirements for fire exits and staircases in hotels are:

  • Number and Location of Staircases: Must comply fully with IS 1644:1988 provisions (Clause 7.3.1).
  • Means of Egress: Includes all vertical and horizontal travel paths like rooms, corridors, stairs, ramps, lobbies, etc. (Clause 1.8).
  • Corridor Widths:
    • Minimum 1.5 m for general corridors leading to exit stairways.
    • For floors with dance or banquet halls:
      • ≥ 2 m width if accommodation > 50 persons.
      • ≥ 1.8 m width if accommodation < 50 persons.
  • Fire safety provisions aim to minimize life and property loss, emphasizing clear and adequate exit routes.

Summary Table for Corridor Widths:

Area TypeOccupancyMinimum Corridor Width
General corridorsAny1.5 m
Banquet/Dance halls> 50 persons2.0 m
Banquet/Dance halls≤ 50 persons1.8 m

These requirements ensure safe evacuation routes in hotels, considering occupant load and usage.

Loading diagram...
?How should fire detection and alarm systems be installed and maintained in hotels?

IS 13716 (Fire Safety in Hotels) emphasizes the importance of fire detection and alarm systems but does not detail their installation and maintenance explicitly. Based on standard fire safety practices and relevant codes (like NBC and IS 2189):

Installation of Fire Detection and Alarm Systems in Hotels:

  • Coverage: Install smoke/heat detectors in all guest rooms, corridors, lobbies, service areas, and basements.
  • Type: Use automatic fire detection systems connected to a central alarm panel.
  • Power Supply: Connect to normal and stand-by power supply (Clause 8.1) to ensure operation during power failure.
  • Alarm Devices: Audible alarms and visual indicators must be installed to alert occupants and staff promptly.

Maintenance:

  • Regular Testing: Test detectors and alarms monthly.
  • Inspection: Annual comprehensive inspection by certified professionals.
  • Record Keeping: Maintain logs of tests, inspections, and repairs.
  • Prompt Repairs: Immediate replacement or repair of faulty devices.

Summary Table:

AspectRequirement
Detector TypeSmoke and heat detectors
CoverageGuest rooms, corridors, basements
Power SupplyNormal + Stand-by (Diesel Gen)
AlarmAudible + Visual
Testing FrequencyMonthly
Inspection FrequencyAnnually

This ensures early fire detection, occupant warning, and compliance with IS 13716 and related standards.

?What fire-resistant construction materials and finishes are recommended for hotel interiors?

Fire-Resistant Materials & Finishes for Hotel Interiors as per IS 13716:

  • Wall Panels, Draperies, Furniture & Decor: Must have Class I flame spread rating per NBC India 1983 (Part IV). This ensures low combustibility and slow flame propagation.

  • Construction Types:

    • Hotels ≥ 15 m height: Must be Type I construction (fire-resistive materials like concrete, steel with fireproofing).
    • Hotels < 15 m height: Minimum Type II construction as per IS 1642:1989 (non-combustible or limited combustible materials).

Recommended Materials:

  • Walls: Gypsum boards, cement fiber boards, fire-retardant treated wood panels.
  • Draperies & Upholstery: Fire-retardant fabrics complying with Class I rating.
  • Furniture: Metal, treated wood, or fire-resistant composites.
  • Finishes: Intumescent paints, fire-retardant coatings.

Flame Spread Classification (NBC 1983 Part IV):

ClassFlame Spread IndexTypical Materials
I0 - 25Gypsum board, treated fabrics
II26 - 75Untreated wood, plywood
III76 - 200Some plastics, untreated fabrics

Loading diagram...

Summary: Use Type I/II construction per height, and ensure all interior finishes meet Class I flame spread rating for fire safety compliance.

?What emergency power and lighting provisions are required to ensure safe evacuation?

Emergency Power & Lighting Provisions per IS 13716

  • Stand-by Power Supply (Clause 8.1):

    • Must be independent, typically a diesel generator.
    • Capacity to power:
      • Emergency illumination of corridors, staircases, basements, and exit signs.
      • Mechanical ventilation in basements or central AC buildings.
      • Fire water pumps (unless a separate diesel pump exists).
      • Other automatic fire-fighting systems.
  • Emergency Illumination (Clause 7.4 & 7.4.1):

    • Exits must have emergency lighting powered by the stand-by supply or self-contained emergency lights.
    • Illumination must ensure no total darkness if a bulb or connection fails (Clause 7.4.4).

Summary:

RequirementSource ClauseDescription
Stand-by power source8.1Diesel generator, independent supply
Emergency lighting coverage8.1, 7.4.1Corridors, stairs, basements, exit signs
Fail-safe illumination7.4.4No total darkness on bulb/connection failure
Mechanical ventilation8.1For basements or central AC buildings
Fire water pump operation8.1Powered by standby or separate diesel pump
Loading diagram...

Ensure all emergency lighting and power systems are regularly tested for reliability and compliance.

?How does the standard address fire safety management and employee training in hotels?

IS 13716 addresses fire safety management and employee training in hotels as follows:

  • Written Fire Safety Policy (Clause 5.1): Hotel management must issue a written statement of its fire safety and fire loss control policy to all employees. Annex A provides a suggested example.

  • Employee Familiarization (Clause 5.6): All employees should be trained and made familiar with:

    • Evacuation plans,
    • Their specific roles in assisting guest evacuation,
    • Measures to control fire growth,
    • Actions ensuring life safety.
  • Objective: The standard aims to minimize life and property loss by ensuring employees understand fire risks and their responsibilities.

  • Supplementary to Statutory Requirements: The code complements laws like the Indian Factory Act and Indian Electricity Rules.

This ensures a proactive fire safety culture through clear policy communication and comprehensive employee training.