IS 13716:1993 is the Indian Standard code of practice for fire safety in hotels, providing comprehensive guidelines to minimize fire risks and ensure life safety and property protection. It applies to all hotel buildings, including high-rise and low-rise, covering fire prevention, containment, means of egress, emergency power, and firefighting equipment. This standard is essential for hotel management, engineers, and fire safety professionals to implement effective fire safety measures in compliance with Indian regulations.
Overview
IS 13716:1993 is the Indian Standard code of practice for fire safety in hotels, providing comprehensive guidelines to minimize fire risks and ensure life safety and property protection. It applies to all hotel buildings, including high-rise and low-rise, covering fire prevention, containment, means of egress, emergency power, and firefighting equipment. This standard is essential for hotel management, engineers, and fire safety professionals to implement effective fire safety measures in compliance with Indian regulations.
Audience
Contents
Structure
IS 13716: Scope Summary
Scope: This standard covers fire safety requirements for buildings, focusing on construction types, fire protection systems, and management responsibilities.
Key References:
The standard is supplemented by related IS codes for comprehensive fire safety:
| IS Code | Title | Year | Focus Area |
|---|---|---|---|
| IS 1641 | Fire safety - General principles | 1988 | Fire grading & classification |
| IS 1642 | Fire safety - Construction details | 1989 | Construction details for fire safety |
| IS 1644 | Fire safety - Exit requirements | 1988 | Exit design & personal hazard |
| IS 2189 | Fire detection & alarm systems | 1988 | Selection, installation, maintenance |
| IS 2190 | Portable fire extinguishers | 1992 | Selection, installation, maintenance |
| IS 3844 | Internal hydrants & hose reels | 1989 | Installation & maintenance |
| SP 7 | National Building Code (Part IV) | 1983 | Fire protection requirements |
Type of Construction (Clause 6.2): Specifies construction types relevant for fire safety design.
Access & Approach Roads (Clause 4.2): Width, hardness, and distance of approach roads for fire engines must comply with NBC 1983 (Part IV).
IS 13716 integrates fire safety design with other IS codes and NBC provisions to ensure comprehensive fire protection covering construction, equipment, and emergency access.
graph LR
A[IS 13716: Fire Safety] --> B[Construction Types (6.2)]
A --> C[Fire Safety Codes]
C --> D[IS 1641, 1642, 1644]
C --> E[IS 2189, 2190, 3844]
A --> F[Access Roads (4.2) - NBC Part IV]
A --> G[Management Responsibility (5)]
This diagram shows the scope and linked standards under IS 13716.
IS 13716: Fire Safety in Hotels — Referenced Standards & Key Specifications
| IS No. | Title | Year |
|---|---|---|
| IS 1641 | Fire safety: General principles of fire grading and classification | 1988 |
| IS 1642 | Fire safety: Details of construction | 1989 |
| IS 1644 | Fire safety: Exit requirements and personal hazard | 1988 |
| IS 2189 | Selection, installation & maintenance of automatic fire detection & alarm systems | 1988 |
| IS 2190 | Selection, installation & maintenance of portable first-aid fire extinguishers | 1992 |
| IS 3844 | Installation & maintenance of internal hydrants and hose reels | 1989 |
| SP 7 | National Building Code of India | 1983 |
| System Type | IS Code | Key Function |
|---|---|---|
| Internal Hydrant/Sprinkler | IS 3844 | Fire suppression |
| Fire Detection & Alarm | IS 2189 | Early fire detection & alarm |
| Portable Fire Extinguishers | IS 2190 | Immediate fire fighting |
| Exit & Construction Details | IS 1642, 1644 | Safe evacuation & fire-resistance |
flowchart LR
A[Fire Safety in Hotels] --> B[Fire Detection (IS 2189)]
A --> C[Fire Suppression (IS 3844)]
A --> D[Portable Extinguishers (IS 219
Classification of Hotels as per IS 13716
Definition (Clause 3.1):
Construction Type (Fire Safety):
| Hotel Type | Building Height | Construction Type | Reference Clause |
|---|---|---|---|
| High Rise Hotel | ≥ 15 m | Type I (NBC 1983 Part IV) | 3.1, 6.2.1 |
| Low Rise Hotel | < 15 m | Minimum Type II (IS 1642) | 3.1, 6.2.2 |
flowchart TD
A[Hotel Building] --> B{Height ≥ 15 m?}
B -- Yes --> C[High Rise Hotel]
B -- No --> D[Low Rise Hotel]
C --> E[Type I Construction (NBC 1983 Part IV)]
D --> F[Minimum Type II Construction (IS 1642:1989)]
This classification guides fire safety design and construction requirements for hotels under IS 13716.
IS 13716: General Fire Safety Principles - Key Points
Fire safety is achieved by addressing:
All hotel buildings must have:
| IS Code | Subject |
|---|---|
| IS 1641 | Fire grading and classification |
| IS 1642 | Details of construction for fire safety |
| IS 1644 | Exit requirements and personal hazard |
| IS 2189 | Fire detection and alarm systems |
| IS 2190 | Portable fire extinguishers |
| IS 3844 | Internal hydrants and hose reels |
graph TD
A[Fire Safety in Hotels] --> B[Management Responsibility]
A --> C[Smoke/Fire Containment]
A --> D[Safety Escape Routes]
A --> E[Emergency Power & Lighting]
A --> F[Fire Safety Equipment]
F --> G[Hydrant/Sprinkler System]
F --> H[Fire Detection & Alarm]
F --> I[Portable Extinguishers]
F --> J[Public Address System]
F --> K[Kitchen Fire Protection]
Note: Halon systems are deleted from the latest amendment (2005). Always refer to the latest IS codes for updated practices.
IS 13716 - Management Responsibility (Clause 5)
Key points on Management Responsibility in fire safety for hotels:
Written Fire Safety Policy (Clause 5.1):
Management must issue a clear, written fire safety and fire loss control policy to all employees. (Refer Annex A for a sample statement.)
Preventive Programs (Clause 5.9):
Management shall establish and maintain a preventive inspection, testing, and maintenance program for:
Coordination with NBC (Clause 4.2):
Management must ensure compliance with National Building Code (Part IV) provisions regarding:
| Responsibility Area | Action Required |
|---|---|
| Fire Safety Policy | Issue written policy to employees |
| Inspection & Maintenance | Schedule regular preventive checks and tests |
| Compliance with NBC Fire Access | Ensure approach roads and open spaces meet NBC |
| Employee Training & Awareness | Conduct fire safety training and drills |
flowchart TD
A[Management Responsibility] --> B[Written Fire Safety Policy]
A --> C[Preventive Inspection & Maintenance]
A --> D[Compliance with NBC Fire Access]
A --> E[Employee Training & Awareness]
This structured approach ensures effective fire safety management in hotels as per IS 13716.
Containment of Smoke and Fire as per IS 13716 focuses on compartmentation and fire-resistive construction to restrict fire/smoke spread.
Clause 6.1:
Use fire-resistive materials and compartmentation to contain smoke/fire.
Clause 6.3:
Restrict fire/smoke spread by design and materials.
Clause 5.11:
Escape routes must be unobstructed and safe:
| Aspect | Specification |
|---|---|
| Floor Occupancy | Max 60% area occupied, 40% free |
| Escape Route Obstruction | None allowed (doors, signs, equipment) |
| Fire-resistive Construction | As per IS 1641, 1642, 1644 |
| Fire Detection & Extinguishers | As per IS 2189, 2190, 3844 |
| IS Code | Description |
|---|---|
| IS 1641 | Fire grading and classification |
| IS 1642 | Details of fire-resistant construction |
| IS 1644 | Exit requirements and personal hazard |
| IS 2189 | Fire detection and alarm systems |
| IS 2190 | Portable fire extinguishers |
| IS 3844 | Internal hydrants and hose reels |
| SP 7 | National Building Code of India (Fire safety provisions) |
flowchart LR
A[Fire Origin] --> B[Fire-Resistive Wall]
B --> C[Compartment 1]
B --> D[Compartment 2]
C --> E[Smoke Barrier]
D --> E
E --> F[Escape Route]
F --> G[Exit]
Summary:
Contain smoke/fire by creating fire-resistant compartments, ensuring escape routes are unobstructed, and controlling occupancy
Means of Egress as per IS 13716
50 persons: ≥ 2.0 m
| Area Type | Occupancy | Minimum Corridor Width (m) |
|---|---|---|
| General corridors | All | 1.5 |
| Banquet/Dance halls | > 50 persons | 2.0 |
| Banquet/Dance halls | ≤ 50 persons | 1.8 |
flowchart LR
A[Any Point in Building] --> B[Exit Access]
B --> C[Exit]
C --> D[Exit Discharge]
D --> E[Public Way]
This ensures a continuous, unobstructed path from any location inside the hotel to safety outside.
IS 13716: Emergency Power Supply and Lighting - Key Points
| Location | Minimum Illumination (lux) | Remarks |
|---|---|---|
| Exits and exit signage | 10 lux | Continuous during emergency |
| Corridors and staircases | 10 lux | Uniform lighting |
| Basements | 10 lux | Mechanical ventilation load considered |
| Fire pump & firefighting | As per equipment rating | Included in generator sizing |
[ \text{Generator Capacity (kVA)} = \frac{\text{Total Emergency Load (kW)}}{\text{Power Factor (usually 0.8)}} ]
flowchart LR
A[Normal Power Supply] -->|Failure| B[Stand-by Diesel Generator]
B --> C[Emergency Lighting]
B --> D[Mechanical Ventilation]
B --> E[Fire Water Pump]
B --> F[Firefighting Systems]
Summary:
Ensure emergency lighting is redundant and continuous with an independent diesel generator sized for all critical emergency loads per IS 13716 clauses.
IS 13716: Fire Safety & Fighting Equipment - Key Points
All hotel buildings must have:
Must support:
| IS Code | Focus Area |
|---|---|
| IS 1641:1988 | Fire grading & classification |
| IS 1642:1989 | Fire safety construction details |
| IS 1644:1988 | Exit requirements & personal hazard |
| IS 2189:1988 | Fire detection & alarm systems |
| IS 2190:1992 | Portable fire extinguishers |
| IS 3844:1989 | Internal hydrants & hose reels |
| SP 7:1983 | National Building Code |
Focus on:
| Equipment | Standard | Application |
|---|---|---|
| Internal Hydrant/Sprinkler | IS 3844:1989 | Fire suppression inside building |
| Fire Detection & Alarm | IS 2189:1988 | Early fire detection & alarm |
| Portable Extinguishers | IS 2190:1992 | First-aid fire fighting |
| Emulsifier/Halon System | - | Automatic suppression |
| Public Address System | - | Emergency communication |
| Kitchen Fire Protection | - | Fire suppression in kitchen hoods |
flowchart TD
IS 13716: Key Points on Written Fire Safety Policy & Equipment
All hotel buildings, regardless of height, must have:
| Equipment Type | IS Code Reference |
|---|---|
| Internal hydrant/sprinkler system | IS 3844 : 1989 |
| Automatic detection & alarm system | IS 2189 : 1988 |
| Automatic emulsifier/Halon system | - |
| Portable fire extinguisher | IS 2190 : 1992 |
| Public address system | Coupled or independent |
| Kitchen hood fire protection | Automatic/manual Halon, CO2, or dry powder extinguisher |
graph TD
A[Hotel Management] --> B[Written Fire Safety Policy]
B --> C[Employee Awareness & Responsibility]
A --> D[Fire Safety Equipment Installation]
D --> E[Internal Hydrants & Sprinklers (IS 3844)]
D --> F[Detection & Alarm Systems (IS 2189)]
D --> G[Portable Extinguishers (IS 2190)]
D --> H[Kitchen Fire Protection]
C --> I[Fire Prevention & Loss Control]
Use this policy and equipment framework to ensure compliance and safety in hotel buildings as per IS 13716.
Key Points:
The committee includes representatives from various sectors:
Member Secretary: Shri Hemant Kumar, Joint Director (Civil Engineering), BIS
Ex-officio Member: Shri Y. R. Taneja, Director General, BIS
| Role | Representation |
|---|---|
| Chairperson | Shri J. N. Vakil (Tariff Advisory Committee) |
| Members | Engineers, Fire Officers, Govt. Ministries, Industry Experts |
| Member Secretary | Shri Hemant Kumar (BIS) |
| Ex-officio Member | Shri Y. R. Taneja (Director General, BIS) |
| IS Code | Description |
|---|---|
| IS 3844 | Internal hydrant and hose reel installation |
| IS 2189 | Automatic fire detection and alarm system |
| IS 2190 | Portable fire extinguisher selection and maintenance |
| IS 1641 | Fire grading and classification |
| IS 1642 | Details of construction for fire safety |
| IS 1644 | Exit requirements and personal hazard |
| SP 7 | National Building Code of India (Fire Protection) |
This committee ensures the standard's technical robustness by involving multidisciplinary experts, aligning with national fire safety codes and practices.
Frequently Asked
According to IS 13716:1993 referencing IS 1644:1988, the minimum requirements for fire exits and staircases in hotels are:
| Area Type | Occupancy | Minimum Corridor Width |
|---|---|---|
| General corridors | Any | 1.5 m |
| Banquet/Dance halls | > 50 persons | 2.0 m |
| Banquet/Dance halls | ≤ 50 persons | 1.8 m |
These requirements ensure safe evacuation routes in hotels, considering occupant load and usage.
Loading diagram...
IS 13716 (Fire Safety in Hotels) emphasizes the importance of fire detection and alarm systems but does not detail their installation and maintenance explicitly. Based on standard fire safety practices and relevant codes (like NBC and IS 2189):
| Aspect | Requirement |
|---|---|
| Detector Type | Smoke and heat detectors |
| Coverage | Guest rooms, corridors, basements |
| Power Supply | Normal + Stand-by (Diesel Gen) |
| Alarm | Audible + Visual |
| Testing Frequency | Monthly |
| Inspection Frequency | Annually |
This ensures early fire detection, occupant warning, and compliance with IS 13716 and related standards.
Fire-Resistant Materials & Finishes for Hotel Interiors as per IS 13716:
Wall Panels, Draperies, Furniture & Decor: Must have Class I flame spread rating per NBC India 1983 (Part IV). This ensures low combustibility and slow flame propagation.
Construction Types:
| Class | Flame Spread Index | Typical Materials |
|---|---|---|
| I | 0 - 25 | Gypsum board, treated fabrics |
| II | 26 - 75 | Untreated wood, plywood |
| III | 76 - 200 | Some plastics, untreated fabrics |
Loading diagram...
Summary: Use Type I/II construction per height, and ensure all interior finishes meet Class I flame spread rating for fire safety compliance.
Emergency Power & Lighting Provisions per IS 13716
Stand-by Power Supply (Clause 8.1):
Emergency Illumination (Clause 7.4 & 7.4.1):
Summary:
| Requirement | Source Clause | Description |
|---|---|---|
| Stand-by power source | 8.1 | Diesel generator, independent supply |
| Emergency lighting coverage | 8.1, 7.4.1 | Corridors, stairs, basements, exit signs |
| Fail-safe illumination | 7.4.4 | No total darkness on bulb/connection failure |
| Mechanical ventilation | 8.1 | For basements or central AC buildings |
| Fire water pump operation | 8.1 | Powered by standby or separate diesel pump |
Loading diagram...
Ensure all emergency lighting and power systems are regularly tested for reliability and compliance.
IS 13716 addresses fire safety management and employee training in hotels as follows:
Written Fire Safety Policy (Clause 5.1): Hotel management must issue a written statement of its fire safety and fire loss control policy to all employees. Annex A provides a suggested example.
Employee Familiarization (Clause 5.6): All employees should be trained and made familiar with:
Objective: The standard aims to minimize life and property loss by ensuring employees understand fire risks and their responsibilities.
Supplementary to Statutory Requirements: The code complements laws like the Indian Factory Act and Indian Electricity Rules.
This ensures a proactive fire safety culture through clear policy communication and comprehensive employee training.