IS 13045:1991 provides comprehensive fire safety guidelines specifically for flour mills and their associated storage godowns. It addresses fire prevention, building layout, electrical installations, housekeeping, and firefighting arrangements to minimize fire risks inherent in flour milling operations. This code is essential for engineers, safety managers, and facility planners involved in designing, operating, or maintaining flour mill buildings in India.
Overview
IS 13045:1991 provides comprehensive fire safety guidelines specifically for flour mills and their associated storage godowns. It addresses fire prevention, building layout, electrical installations, housekeeping, and firefighting arrangements to minimize fire risks inherent in flour milling operations. This code is essential for engineers, safety managers, and facility planners involved in designing, operating, or maintaining flour mill buildings in India.
Audience
Contents
Structure
IS 13045: Scope & Key Specifications for Fire Safety in Flour Mills
Scope:
This code specifies minimum fire safety requirements for flour mills, including storage godowns, focusing on fire prevention, building layout, and firefighting arrangements.
Illumination Requirements (Clause 11.1):
| Occupancy Area | Minimum Illumination (Lux) | Limiting Glare Index |
|---|---|---|
| Roller purifier, silks, packing floors | 150 | 25 |
| Wetting tables | 300 | 25 |
| Godowns, loading bays, packing, dispatch | 150 | 25 |
| Open compounds | 50 | - |
Dust Bin/Hopper Safety (Clause 14.2):
No openings allowed between adjacent bins/hoppers containing dust or dust-producing materials to prevent fire spread.
Referenced IS Codes (Annex A):
Includes IS 1642, 1644, 1646 (fire safety of buildings), IS 941 (blower & exhauster), IS 9537 (fire extinguisher), IS 3844 (internal hydrants), IS 13039 (external hydrants), etc.
graph LR
A[Building Layout & Construction] --> B[Fire Prevention]
B --> C[Fire Fighting Equipment]
C --> D[Illumination Standards]
D --> E[Storage Safety - Dust Bins]
E --> F[Compliance with IS Codes]
Note: Always cross-check with statutory requirements (Factory Act, Petroleum Rules, etc.) alongside IS 13045.
IS 13045: Location and Site Planning - Key Specifications
Minimum clear distance between factory buildings:
90 m (Clause 3.2)
Factory to railway sidings, yards, high tension lines:
≥ 300 m (Clause 3.3)
Minimum distance between buildings or between building and open storage:
6 m (Clause 6.1)
Compound area:
Should be sufficient to accommodate the mill block, godowns, and open storage (Clause 4.1).
| Parameter | Minimum Distance |
|---|---|
| Between factory buildings | 90 m |
| From railway sidings/yards/HT lines | 300 m |
| Between buildings/open storage | 6 m |
graph LR
A[Factory Building 1] ---|90 m| B[Factory Building 2]
A ---|≥300 m| C[Railway Sidings / HT Lines]
A ---|6 m| D[Open Storage]
B ---|6 m| D
This diagram illustrates minimum clearances for safe site layout.
IS 13045: Factory Compound & Accessibility Key Points
| Occupancy / Area | Minimum Illumination (Lux) | Limiting Glare Index |
|---|---|---|
| Roller purifier, silks, packing floors | 150 | 25 |
| Wetting tables | 300 | 25 |
| Godowns, loading bays, packing, dispatch | 150 | 25 |
| Open compounds | 50 | - |
graph TD
A[Factory Compound] --> B[Mill Block]
A --> C[Godowns]
A --> D[Open Storage]
B ---|90 m| E[Adjacent Factory]
B ---|6 m| C
C ---|6 m| D
subgraph Illumination
I1[Roller purifier, silks, packing floors: 150 Lux]
I2[Wetting tables: 300 Lux]
I3[Godowns, loading bays, packing, dispatch: 150 Lux]
I4[Open compounds: 50 Lux]
end
Use these spacing and illumination specs to ensure safety, accessibility, and fire-fighting effectiveness in factory layouts per IS 13045.
IS 13045: Building Construction and Separation - Key Points
| Item | Minimum Separation / Specification |
|---|---|
| Between buildings/storage | 6 m minimum |
| Storage vs. mill/cleaning | Separation wall mandatory |
| Adjacent dust bins/hoppers | No openings allowed |
flowchart LR
A[Building 1] ---|6 m min| B[Building 2]
A ---|6 m min| C[Open Storage]
D[Grain Storage] ---|Separation Wall| E[Mill/Wheat Cleaning]
F[Bin 1] -. No Openings .-> G[Bin 2]
This ensures safe separation to reduce fire, contamination, and explosion risks per IS 13045.
IS 13045: Key Specifications for Open Spaces and Waste Management
Minimum distance between buildings/storage:
Maintain 6 m clearance between any two buildings, or between buildings and open storage, or between different types of open storage (Clause 6.1).
Compound area:
The factory compound must be large enough to accommodate the mill block, godowns, and open storages (Clause 4.1).
| Occupancy Area | Minimum Illumination (Lux) | Limiting Glare Index |
|---|---|---|
| Roller purifier, silks, packing floors | 150 | 25 |
| Wetting tables | 300 | 25 |
| Godowns, loading bays, packing, dispatch | 150 | 25 |
| Open compounds | 50 | - |
flowchart LR
A[Factory Compound] --> B[Mill Block]
A --> C[Godowns]
A --> D[Open Storage]
B ---|6 m gap| C
C ---|6 m gap| D
B ---|6 m gap| D
Summary: Maintain 6 m spacing for fire safety, avoid open oily waste dumping, and ensure adequate illumination per area for fire-fighting readiness.
IS 13045 – Exit Requirements Summary
Exit Doorway Dimensions (Clause 7.4):
Exit Staircase Landing (Clause 7.3):
General Exit Compliance (Clause 7.1):
| Parameter | Minimum Dimension | Reference Clause |
|---|---|---|
| Exit Doorway Width | 100 cm (1.0 m) | 7.4 |
| Exit Doorway Height | 200 cm (2.0 m) | 7.4 |
| Staircase Landing Size | 1.5 m × 1.5 m | 7.3 |
| Hydrant Location | Staircase landings (each floor) | 7.3 (IS 3844:1989) |
flowchart TD
A[Building Floor] --> B[Exit Doorway]
B --> C[Exit Staircase]
C --> D[Landing (1.5m x 1.5m)]
D --> E[Hydrant Post (Wet Riser)]
E --> F[Exit to Safety]
This ensures safe and compliant egress routes in buildings per IS 13045.
| Parameter | Value |
|---|---|
| Max opening size | 1.2 m × 0.3 m |
| Aperture protection | 12.5 mm mesh |
| Height from ground | ≥ 3 m |
flowchart LR
Roof --> Ventilator[Ventilator Opening]
Ventilator --> Protection[12.5 mm mesh]
Ventilator --> FireDamper[Fire Smoke Damper]
Ventilator --> MechanicalVent[Mechanical Ventilation (IS 941)]
This ensures adequate ventilation with fire safety in storage buildings per IS 13045.
IS 13045: Machinery Installation and Operation - Key Points
| Aspect | Specification |
|---|---|
| Bearings | Ball or roller bearings |
| Dust Control | Prevent dust on moving parts; use cyclone/whirl collectors |
| Dust Rooms | Not allowed inside mill |
| Fire Safety Measures | Proper layout, external stairs, non-combustible materials, firefighting equipment |
flowchart TD
A[Machinery Installation] --> B[Use ball/roller bearings]
A --> C[Prevent dust accumulation]
C --> D[Automatic cyclone/whirl dust collectors]
A --> E[No dust rooms inside mill]
A --> F[Fire safety measures]
F --> G[Good housekeeping]
F --> H[Non-combustible materials]
F --> I[External staircases]
F --> J[Firefighting equipment]
This concise guidance ensures machinery longevity, operational safety, and fire prevention in flour mills per IS 13045.
IS 13045: Electrical Installation Key Points
General Installation:
Follow IS 1646:1982 for electrical installation practices in textile mills.
Wiring:
Use steel conduits as per IS 1653:1972 or rigid non-metallic conduits as per IS 9537 (Part 3):1973 for all wiring.
Switchgear:
Must be dust-tight type when installed in mill houses (Clause 10.5) to prevent dust ingress, ensuring safety and reliability.
Dust Control:
No dust or exhaust rooms inside mills; only automatic cyclone or whirl dust collectors made of metal are allowed for dust collection (Clause 9.6).
| Aspect | IS Code Reference | Specification |
|---|---|---|
| Electrical Installation | IS 1646:1982 | General electrical installation |
| Steel Conduits | IS 1653:1972 | Steel conduit wiring |
| Non-metallic Conduits | IS 9537 (Part 3):1973 | Rigid non-metallic conduit wiring |
| Switchgear | IS 13045 Clause 10.5 | Dust-tight switchgear in mill houses |
| Conduit Type | Material | Application | Protection Level |
|---|---|---|---|
| Steel Conduit | Galvanized Steel | High mechanical strength | Dust & mechanical protection |
| Non-metallic | PVC or similar | Corrosion resistance | Dust protection |
flowchart LR
A[Electrical Installation] --> B[Wiring]
B --> C[Steel Conduit (IS 1653)]
B --> D[Non-metallic Conduit (IS 9537)]
A --> E[Switchgear]
E --> F[Dust-tight Type (Clause 10.5)]
A --> G[Dust Control]
G --> H[No dust rooms inside mills]
G --> I[Automatic cyclone/whirl dust collectors]
For detailed design, consult the respective IS codes for conduit sizes, wiring methods, and switchgear specifications.
IS 13045 - Illumination Requirements for Industrial Buildings
| Occupancy / Process | Minimum Illumination (Lux) | Limiting Glare Index |
|---|---|---|
| Roller purifier, silks & packing floors | 150 | 25 |
| Wetting tables | 300 | 25 |
| Godowns, loading bays, packing & dispatch | 150 | 25 |
| Open compounds | 50 | - |
graph LR
A[Industrial Area] --> B[Lighting Fittings (Dust-tight)]
B --> C[Minimum Lux as per Area]
C --> D[Glare Control (Index ≤ 25)]
D --> E[Safe & Effective Illumination]
Use these values to design lighting systems ensuring safety and operational efficiency in mills per IS 13045.
IS 13045: Fire Fighting Arrangements for Flour Mills
First-aid Fire Fighting Equipment:
Internal Hydrant System:
External Hydrant System:
Emergency Lighting:
| Parameter | Requirement |
|---|---|
| Max travel distance to equipment | 15 meters |
| Equipment location | Near fire-prone areas & exits |
| Passage obstruction | Equipment must not obstruct passage |
flowchart LR
A[Fire Prone Areas] --> B[First Aid Fire Equipment]
C[Exits & Staircase Landings] --> B
B -->|Max 15 m travel| D[Personnel Access]
E[Power Failure] --> F[Emergency Lighting]
For detailed design, refer to IS 2190, IS 3844, and IS 13039 as indicated.
IS 13045: Housekeeping Key Points & Specifications
| Area | Minimum Illumination (Lux) | Limiting Glare Index |
|---|---|---|
| Roller purifier, silks, packing floors | 150 | 25 |
| Wetting tables | 300 | 25 |
| Godowns, loading bays, packing, dispatch | 150 | 25 |
| Open compounds | 50 | - |
flowchart TD
A[Minimize Horizontal Surfaces] --> B[Incline Inaccessible Surfaces]
B --> C[Smooth Surface Finish]
C --> D[Weekly Cleaning of Machinery & Floors]
D --> E[Daily Cleaning of Rope Alloys]
E --> F[Remove Sweepings Before Nightfall]
F --> G[Use Vacuum/Air Blowers After Shutdown]
G --> H[Fire Warning System Installed]
H --> I[Audible & Conspicuous Location]
I --> J[Painted Red (IS 5:1978, No. 536)]
J --> K[Maintain Illumination Levels for Fire Fighting]
This ensures dust control, safety, and compliance with IS 13045 housekeeping standards.
IS 13045 - Key Specifications for Flour Bins and Hoppers
| Requirement | Specification |
|---|---|
| Material of bins/hoppers | Non-combustible or fire-resistive |
| Openings between adjacent bins/hoppers | Not allowed if dust-producing |
| Waste disposal near bins/hoppers | No oily/greasy waste in open areas |
graph TD
A[Flour Bins & Hoppers] --> B[Non-combustible Material]
A --> C[No Openings Between Adjacent Bins]
A --> D[No Oily Waste Deposited Nearby]
B --> E[Fire Resistance Ensured]
C --> F[Prevents Dust Spread]
D --> G[Reduces Fire Hazard]
Note: For detailed design and fire safety installation, consult IS 1642, IS 1644, and IS 1646 as referenced in IS 13045 Annex A.
Frequently Asked
According to IS 13045 Clause 14.1, flour bins and hoppers inside the mill must be made of non-combustible or fire-resistive materials to prevent fire hazards.
| Material Type | Fire Resistance | Typical Use |
|---|---|---|
| Steel (mild or stainless) | Non-combustible | Structural bins, hoppers |
| Concrete | Fire-resistive (high) | Large bins, foundations |
| Fire-retardant coated metals | Fire-resistive | Lightweight hoppers |
Loading diagram...
This ensures fire safety and aligns with IS 13045 requirements.
Electrical Installation Fire Safety in Flour Mills (IS 13045)
To minimize fire risk from electrical installations in flour mills:
Loading diagram...
Summary: Use dust-proof, metal collectors, explosion-proof fittings, maintain cleanliness, and install clear fire alarms to reduce electrical fire hazards in flour mills.
According to IS 13045, the recommended distances are:
Between mill buildings and storage (grain, flour, hazardous goods):
Use a separating wall to ensure safety (Clause 5.7).
Between any two buildings or between a building and open storage:
Maintain a minimum distance of 6 meters (Clause 6.1).
Between factories located near each other:
Maintain a clear distance of at least 90 meters (Clause 3.2).
From factories to railway sidings, yards, and high-tension lines:
Maintain a distance of at least 300 meters (Clause 3.3).
| Location Type | Minimum Distance |
|---|---|
| Mill building & storage (hazardous) | Separating wall |
| Between buildings or building & open storage | 6 m |
| Between factories | 90 m |
| From railway sidings, yards, HT lines | 300 m |
This ensures safety, fire prevention, and operational efficiency.
To manage housekeeping effectively and reduce dust accumulation and fire hazards as per IS 13045:
This integrated approach minimizes dust hazards and enhances fire safety in flour mills.
Loading diagram...
IS 13045 Fire Fighting Equipment & Warning Systems Requirements:
| Equipment Type | Standard Reference | Location/Requirement |
|---|---|---|
| First-aid fire fighting | IS 2190:1979 | Near fire-prone areas, max 15 m travel |
| Internal hydrant system | IS 3844:1989 | Installed within the flour mill |
| External hydrant system | IS 13039:1991 | Outside the flour mill premises |
| Emergency lighting | Clause 11.2 of IS 13045 | For power failure scenarios |
| Fire safety notices | Clause 13.5 of IS 13045 | Displayed at conspicuous locations |
Loading diagram...
This ensures quick access to firefighting means and clear guidance during emergencies.