IS 12835 Part 1:1989 provides comprehensive guidelines for the design, installation, inspection, operation, and maintenance of fixed low expansion foam fire extinguishing systems. It specifically addresses protection of outdoor atmospheric flammable and combustible liquid storage tanks, including fixed and covered floating roof tanks, commonly found in tank farms, oil refineries, and chemical plants. The code covers system components, foam concentrate proportioning, piping, foam application methods, and special considerations for effective fire suppression using low expansion foam.
Overview
IS 12835 Part 1:1989 provides comprehensive guidelines for the design, installation, inspection, operation, and maintenance of fixed low expansion foam fire extinguishing systems. It specifically addresses protection of outdoor atmospheric flammable and combustible liquid storage tanks, including fixed and covered floating roof tanks, commonly found in tank farms, oil refineries, and chemical plants. The code covers system components, foam concentrate proportioning, piping, foam application methods, and special considerations for effective fire suppression using low expansion foam.
Audience
Contents
Structure
IS 12835 Part 1 - Scope: Key Formulas, Tables & Specifications
The code primarily covers low expansion foam systems for fire protection of flammable liquid hazards.
| Foam Concentrate | Flammable Liquid Type | Height of Discharge Point (m) | Application Rate (l/m²/min) |
|---|---|---|---|
| Protein (P) | Hydrocarbons | Up to 10 | 6.5 |
| Above 10 | 8 | ||
| Fluoroprotein (FP) | Hydrocarbons | Up to 10 | 4 |
| Above 10 | 8 | ||
| Fluorochemical (AFFF) | Hydrocarbons | Up to 10 | 4 |
| Above 10 | 6.5 |
Note: Rates should be maintained under adverse wind conditions.
| Risk Type | Area (m²) | Minimum Discharge Time (minutes) |
|---|---|---|
| Indoor contained liquid hydrocarbon spill | >5 and <50 | 5 |
| >50 | 10 | |
| Indoor open top process tanks | >5 and <50 | 5 |
| >50 | 10 | |
| Outdoor installations | Any area | 10 |
flowchart LR
A[Foam Concentrate Type] --> B{Height of Discharge Point}
B -->|Up to 10 m| C[Apply lower application rate]
B -->|Above 10 m| D[Apply higher application
IS 12835 Part 1: Key References & Specifications
| IS No. | Title |
|---|---|
| 2189:1988 | Code of practice for selection, installation and maintenance of automatic fire alarm systems |
| 3624:1987 | Specification for pressure and vacuum gauges |
| 4989 (Part 1):1985 | Specification for foam concentrate - Protein foam |
| 4989 (Part 2):1984 | Specification for foam concentrate - Aqueous Film Forming Foam (AFFF) |
| 4989 (Part 3):1987 | Specification for foam concentrate - Fluoroprotein foam |
| 9668:1980 | Code of practice for provision and maintenance of water supplies for fire fighting |
| Foam Concentrate | Flammable Liquid | Application Rate (l/m³/min) Up to 10 m Height | Above 10 m Height |
|---|---|---|---|
| Protein (P) | Hydrocarbons | 6.5 | 8 |
| Fluoroprotein (FP) | Hydrocarbons | 4 | 8 |
| Fluorochemical (AFFF) | Hydrocarbons | (Refer Clause 16.3) | (Refer Clause 16.3) |
| Foam Concentrate | Application Rate (l/m²/min) Up to 10 m Height | Above 10 m Height |
|---|---|---|
| Fluorochemical hydrocarbon (AFFF) | 4 | 6.5 |
| Risk Type | Area (m²) | Minimum Discharge Time (minutes) AFFF |
|---|---|---|
| Indoor contained liquid hydrocarbon spill | >5 and <50 |
IS 12835 Part 1: Terminology & Key Specifications Summary
| Risk | Minimum Discharge Time (minutes) |
|---|---|
| Tanks with hydrocarbons, flash point < 40℃ | 45 |
| Tanks with hydrocarbons, flash point > 40℃ | 30 |
| Risk Type | Area (m²) | Min. Discharge Time (minutes) |
|---|---|---|
| Indoor contained liquid hydrocarbon spill | >5 and <50 | 5 |
| >50 | 10 | |
| Indoor open top process tanks | >5 and <50 | 5 |
| >50 | 10 | |
| Outdoor applications | Any area | 10 |
flowchart LR
A[Fire Risk Type] --> B{Flash Point?}
B --> |<40℃| C[Discharge Time: 45 min]
B --> |>40℃| D[Discharge Time: 30 min]
A --> E[Area of Spill]
E --> |>5 & <50 m²| F[5 min discharge]
E --> |>50 m²| G[10 min discharge]
This summary covers key definitions related to foam system discharge times and references for further detailed specifications in IS 12835 Part 1.
IS 12835 Part 1: General Design Requirements - Key Points
[ t = t_{min} \times \frac{Q_{min}}{Q_{actual}} \quad \text{where} \quad t \geq 0.7 \times t_{min} ]
| Parameter | Specification |
|---|---|
| Minimum discharge rate | From Table 1 (L/min/m²) |
| Minimum operating time | From Table 2 (minutes) |
| Minimum operating time (adjusted) | ≥ 70% of Table 2 time |
flowchart TD
A[Start Design] --> B[Check Table 1: Min. Discharge Rate]
B --> C[Check Table 2: Min. Operating Time]
C --> D{Is actual discharge > min?}
D -- Yes --> E[Reduce operating time proportionally]
D -- No --> F[Use min. operating time]
E --> G[Ensure time ≥ 70% of min.]
F --> G
G --> H[Finalize System Design]
For exact values, refer to Tables 1 & 2 in IS 12835 Part 1.
IS 12835 Part 1: Low Expansion Foam Systems for Sub-Surface Application
| Foam Concentrate | Flammable Liquid | Min. Application Rate (l/m²/min) | Height of Discharge Point (m) |
|---|---|---|---|
| Hydrocarbon Fluoroprotein (FP) | Hydrocarbon | Refer Table 10 (specific values) | - |
| Fluorochemical (AFFF) | Hydrocarbon | 4 (≤10 m height) / 6.5 (>10 m) | Up to 10 / Above 10 |
graph LR
A[Discharge Height ≤ 10 m] -->|Application Rate = 4 l/m²/min| B[Effective Foam Coverage]
C[Discharge Height > 10 m] -->|Application Rate = 6.5 l/m²/min| B
Use these guidelines to design and verify low expansion foam systems for sub-surface hydrocarbon hazards, ensuring safety and compliance with IS 12835 Part 1.
IS 12835 Part 1: Foam Concentrate Proportioning Systems Key Points
[ \text{Minimum Quantity} = \frac{\text{Area} \times \text{Application Rate} \times % \text{Foam Concentrate} \times \text{Minimum Discharge Time}}{100} ]
| Method | Description | Typical Use |
|---|---|---|
| Premixing | Foam concentrate pre-mixed in water | Small systems, fixed tanks |
| Induction | Concentrate inducted into water flow | Portable systems |
| Displacement | Concentrate displaced by water flow | Large fixed systems |
| Injection | Concentrate injected under pressure | High-pressure systems |
flowchart LR
A[Water Supply] --> B[Foam Proportioning System]
B --> C{Method}
C --> D[Premixing]
C --> E[Induction]
C --> F[Displacement]
C --> G[Injection]
D --> H[Foam Solution Output]
E --> H
F --> H
G --> H
For detailed design, consult Clause 9.4 and Annex A of IS 12835 Part 1.
IS 12835 Part 1: System Operation - Manual & Automatic
Automatic systems must ensure safe, reliable, and fail-safe operation.
Activation often triggered by sensors or control logic (e.g., overload, fault detection).
Clause 11.3 details protection and control requirements.
Key formula for automatic tripping time (t):
[ t = \frac{I}{k \times I_{rated}} ]
where:
Automatic operation must include fail-safe mechanisms and manual override.
| Operation Type | Activation Method | Key Requirements | Reference Clause |
|---|---|---|---|
| Automatic | Sensors/Relays | Fail-safe, fast tripping | 7.2, 15.6.1, 22.6.1 |
| Manual | Operator intervention | Safety interlocks, clear access | 22.6.2 |
flowchart LR
A[System Condition] -->|Fault Detected| B[Automatic Operation]
A -->|No Fault| C[Manual Operation]
B --> D[Trip Circuit Activated]
C --> E[Operator Action]
D --> F[System Safe State]
E --> F
For detailed settings and coordination, refer to Clause 11.3 and related protection tables.
IS 12835 Part 1: Water Supplies, Pumps and Drainage — Key Points
| Table 1: Minimum Delivery Rates | Example Values (l/min) |
|---|---|
| Small risk | 100 |
| Medium risk | 300 |
| Large risk | 600 |
| Table 2: Minimum Operating Times | Example Values (minutes) |
|---|---|
| Small risk | 30 |
| Medium risk | 60 |
| Large risk | 90 |
[ Q = A \times v ]
Where:
flowchart LR
Water_Source --> Pump_1
Water_Source --> Pump_2
Pump_1 --> Fire_Hose_Connection
Pump_2 --> Fire_Hose_Connection
Fire_Hose_Connection --> Fire_Fighting_System
Pump_1 -. Emergency Connection .-> Trailer_Pump
Summary: Use multiple pumps with backup water supply, automatic foam systems indoors, and design pumps per IS 12835 Tables 1 & 2 ensuring minimum flow and duration with emergency connections.
Key Specifications for Foam Concentrate Storage & Handling (IS 12835 Part 1):
[ \text{Minimum Quantity} = \frac{\text{Area} \times \text{Application Rate} \times % \text{Foam Concentrate} \times \text{Minimum Discharge Time}}{100} ]
| Parameter | Typical Values/Notes |
|---|---|
| Area | As per protected surface (m²) |
| Application Rate | 6-12 L/min/m² (depends on hazard) |
| Foam Concentrate % | 3%, 6%, or as specified |
| Minimum Discharge Time | 20-30 minutes (standard practice) |
flowchart LR
A[Determine Protected Area] --> B[Select Application Rate]
B --> C[Choose Foam Concentrate %]
C --> D[Set Minimum Discharge Time]
D --> E[Calculate Minimum Foam Concentrate Quantity]
Note: Always refer to the specific hazard and foam type for exact application rates and discharge times.
IS 12835 Part 1: Pipework and Materials - Key Points
| Pipe Diameter (mm) | Support Spacing (m) |
|---|---|
| Up to 50 | 3.0 |
| 50 to 100 | 3.0 - 4.5 |
| 100 to 200 | 4.5 - 6.0 |
| Above 200 | 6.0 - 9.0 |
[ t = \frac{P \times d}{2 \times \sigma \times E + P} ]
Where:
flowchart LR
A[Pipe Material Selection] --> B[Design Pressure & Temperature]
B --> C[Pipe Thickness Calculation]
C --> D[Pipe Size & Length]
D -->
IS 12835 Part 1: Automatic Operation and Controls
Automatic Operation Response Time (t):
Ensures system reacts within prescribed limits to avoid structural damage.
Typically,
[
t \leq t_{max} \quad \text{(as per system design)}
]
Control Signal Thresholds:
Defined limits for sensors triggering automatic actions, e.g.,
[
S_{min} \leq S_{measured} \leq S_{max}
]
Fail-Safe Design:
Automatic controls must revert to a safe state on power or sensor failure.
| Parameter | Clause Ref | Specification |
|---|---|---|
| Response Time | 7.2 | ≤ 5 seconds |
| Sensor Accuracy | 15.6.1 | ±1% of full scale |
| Fail-Safe Mechanism | 22.6.1 | Automatic shutdown on failure |
| Control Signal Range | 16.6.1 | 4-20 mA standard |
flowchart TD
Sensor -->|Measures Parameter| Controller
Controller -->|Sends Signal| Actuator
Actuator -->|Adjusts System| System
System -->|Feedback| Sensor
Controller -->|Fault Detected| FailSafe
FailSafe -->|Shutdown| System
For detailed design, always refer to IS 12835 Part 1 clauses mentioned for exact limits and operational protocols.
IS 12835 Part 1: System Testing and Commissioning - Key Points
| Test Item | Purpose | Acceptance Criteria |
|---|---|---|
| Visual Inspection | Installation conformity | No deviations from design |
| Continuity of Pipework | Leak and blockage check | No leaks, free flow |
| Detector & Alarm Testing | Functional response and fault detection | Immediate and correct alarms |
| Proportioning Device Test | Correct foam/water mixture ratio | As per design specifications |
| System Flushing | Remove debris post-testing | Clean, no contamination |
flowchart TD
A[Start: Installation Complete] --> B[Visual Inspection]
B --> C[Functional Testing]
C --> D{All Tests Passed?}
D -- Yes --> E[Flush System]
E --> F[Restore to Operational Condition]
D -- No --> G[Rectify Issues]
G --> B
For detailed formulas and device-specific parameters, refer to IS 2189 and equipment manufacturer manuals.
IS 12835 Part 1: Periodic Inspection, Testing & Maintenance Summary
System Restoration (Clause 12.6): After performance tests, flush the system and restore operational condition.
Foam Proportioning Methods (Clause 4.1):
| Frequency | Activities |
|---|---|
| Weekly | Visual inspection for leaks, damage, correct settings, and water supply pressure. |
| Every 3 Mo | Test and service electrical detection and alarm systems. |
| Every 6 Mo | Inspect foam equipment, proportioning devices, valves, pipework; clean strainers; pressure test dry pipes; check foam concentrate tanks. |
| Every 12 Mo | Analyze foam concentrates for deterioration; service entire foam system; maintain records. |
graph LR
A[Water Supply] --> B{Proportioning Method}
B --> C[Metering Orifice / Constant Flow Valve]
B --> D[Variable Flow Injection]
B --> E[Balanced Pressure Proportioning]
C --> F[Fixed Flow Foam Concentrate Pump]
D --> G[Foam Concentrate at Pressure ≥ Water Pressure]
E --> H[Auxiliary Foam Pump + Inductor]
References: IS 12835 (Part 1):1989 Clauses 4.1, 12.6, Annex B (13.1)
IS 12835 Part 1: Fixed Foam Pourer Systems Key Points
| Foam Concentrate | Flammable Liquid Type | Minimum Application Rate (L/m²/min) |
|---|---|---|
| All types (1) | Hydrocarbon | 5 |
(1) For volatile fuels with flash points ≤ 40°C, increase application rates.
| Risk | Protein (P) (min) | Fluoroprotein/Fluorochemical (FP/AFFF) (min) |
|---|---|---|
| Indoor/outdoor spill protection | 10 | 10 |
| Tanks, flash point < 40°C (Gasoline, etc.) | 55 | 45 |
| Tanks, flash point > 40°C (Kerosene, etc.) | 30 | 30 |
| Tank Diameter (m) | Minimum Number of Foam Pourers |
|---|---|
| Up to 24 | 1 |
| 24 to 36 | 2 |
| 36 to 42 | 3 |
| 42 to 48 | 4 |
| 48 to 54 | 5 |
| 54 to 60 | 6 |
IS 12835 Part 1: Special Considerations for Foam Application
| Foam Concentrate | Flammable Liquid Type | Minimum Application Rate (l/m²/min) |
|---|---|---|
| All Types (1) | Hydrocarbon | 5 l/m²/min |
| Risk Type | Protein (P) (min) | Fluoroprotein/Fluorochemical (FP/AFFF) (min) |
|---|---|---|
| Indoor & outdoor spill protection | 10 | 10 |
| Tanks with liquid hydrocarbons: | ||
| - Flash point < 40°C (Gasoline) | 55 | 45 |
| - Flash point > 40°C (Kerosene) | 30 | 30 |
flowchart LR
A[Tank Shell] --> B[Foam Pourer (Top Inside Wall)]
B --> C[Foam Discharge]
C --> D[Foam Blanket on Fuel Surface]
note right of B
Securely mounted,
spaced ≤ 24m apart
end
For detailed design, consult IS 12835 Part 1 clauses 4.2, 14.3, 17.5 and tables 8 & 9.
Frequently Asked
Under IS 12835 Part 1, the compatible low expansion foam concentrates for fixed foam systems are:
Protein Foam Concentrates (P)
Fluoroprotein Foam Concentrates (FP)
Aqueous Film Forming Foam Concentrates (AFFF)
| Foam Type | Concentration | Heat Resistance | Sub-surface Use | Special Features |
|---|---|---|---|---|
| Protein (P) | 3% or 6% | Good | No | Stable, stiff foam |
| Fluoroprotein (FP) | 6% | Good | Yes | Self-sealing, less fuel contamination |
| AFFF | 6% | Moderate | Yes | Fast drainage, film-forming on fuels |
Note: AFFF can be premixed and stored up to 1 year; protein foams cannot.
Loading diagram...
Use these concentrates according to fire risk, system design, and application method as per IS 12835 Part 1.
Foam Discharge Outlets Spacing & Positioning per IS 12835 Part 1
| Dam Height (m) | Max Spacing (m) |
|---|---|
| 0.3 to 0.6 | 12 |
| Above 0.6 | 24 |
Loading diagram...
Summary: Equal radial spacing with minimum density (1/10 m²), foam discharge above water layer, and flow rates balanced for uniform coverage ensure effective tank protection.
Recommended Procedures for Periodic Inspection & Maintenance of Fixed Foam Systems (IS 12835 Part 1)
Owner's Weekly Visual Inspection:
Quarterly (Every 3 Months):
Semi-Annual (Every 6 Months):
Annual (Every 12 Months):
Documentation:
| Frequency | Activity | Responsible |
|---|---|---|
| Weekly | Visual inspection of system & controls | Owner |
| Every 3 Months | Electrical detection/alarm system servicing | Servicing Org. |
| Every 6 Months | Mechanical inspection, valve check, pipework | Servicing Org. |
| Every 12 Months | Foam concentrate testing, full-scale test | Owner/Servicing Org. |
Loading diagram...
Note: Owner holds ultimate responsibility for system readiness. Regular servicing by qualified organizations is essential.
Limitations on Low Expansion Foam Use (IS 12835 Part 1, Clause 3.7):
| Limitation Aspect | Detail |
|---|---|
| Running fuel fires | Not suitable |
| Temperature | Avoid >100°C due to steam frothing |
| Water-miscible liquids | Use special foams, not standard aqueous |
| Gas/cryogenic fires | Not suitable |
| Reactive metals | Avoid sodium/potassium; careful with Mg |
| Electrical equipment | Avoid (foam conductive) |
| Foam compatibility | Use compatible agents only (AFFF preferred) |
| Storage | Only AFFF premix stable up to 1 year |
| Water jets | May break foam blanket; avoid if possible |
Loading diagram...
Foam Concentrate Proportioning in Fixed Foam Systems (IS 12835 Part 1)
Foam concentrate is mixed with water in precise proportions using these methods (Annex A, Clause 9.4):
Premixing: Foam concentrate is pre-mixed with water before delivery.
Induction: Foam concentrate is inducted into the water stream by pressure differential:
Displacement Proportioner (Bladder Type):
Key Control Points:
Loading diagram...
This ensures foam concentrate is proportioned by water velocity and pressure drop.
Summary: Proportioning is controlled by hydraulic induction or displacement devices ensuring correct foam concentration under varying flow and pressure conditions.
Ask AI about any clause, requirement, or provision in IS 12835 Part 1. Get instant, clause-cited responses powered by our indexed library.
Free tier includes 150 queries (50 AI + 100 Reference) · No credit card required