Specification for a dry powder fire extinguisher for metal fires

IS 11833:1986 specifies requirements for dry powder fire extinguishers designed specifically for metal fires (Class D fires). It covers materials, construction, chemical composition, performance, and environmental considerations for extinguishers with capacities from 10 to 100 kg. This standard is essential for manufacturers, safety engineers, and fire protection professionals dealing with reactive metal fire hazards.

13Sections
112Clauses Indexed
AI Search Ready
1986Edition
Fire FightingCategory
Alternative search terms: IS 11833 PDF, IS 11833 pdf free download, IS 11833 free download pdf, IS11833 PDF, IS-11833 PDF, IS 11833 1986 PDF, IS 11833:1986 PDF, IS 11833-1986 PDF, IS 11833 (1986) PDF, IS 11833 1986 edition PDF, IS 11833 edition 1986 PDF

What This Standard Covers

IS 11833:1986 specifies requirements for dry powder fire extinguishers designed specifically for metal fires (Class D fires). It covers materials, construction, chemical composition, performance, and environmental considerations for extinguishers with capacities from 10 to 100 kg. This standard is essential for manufacturers, safety engineers, and fire protection professionals dealing with reactive metal fire hazards.

Who Uses This Standard

  • Fire safety engineers
  • Manufacturers of fire extinguishers
  • Industrial safety officers
  • Facility managers in metal processing plants
  • Fire protection equipment suppliers
  • Regulatory compliance officers
  • Maintenance technicians for fire safety equipment

Key Topics Covered

Scope and application for metal fire extinguishers
Material specifications for extinguisher components
Construction and design requirements
Dry powder chemical composition and charge
Performance testing and discharge characteristics
Applicator design for safe powder discharge
Anti-corrosive treatments and durability
Environmental compliance including Ozone Depleting Substances (ODS)
Restrictions on hazardous substances like lead and mercury
Packaging and labeling requirements
Capacity classifications and minimum powder content
Safety features such as pressure venting and handles
Test methods for performance verification
ECO Mark optional environmental criteria
Amendments addressing updated environmental and safety standards

Table of Contents

1Scope

IS 11833: Scope - Key Specifications and Tables

Scope Summary:

IS 11833 covers dry powder fire extinguishers for metal fires, specifying materials, construction, dimensions, and environmental considerations.


Key Tables & Specifications

1. Materials of Construction (Table 1)

ComponentMaterialIS Code Reference
BodyMild steel platesIS: 2002-1982, IS: 226-1975
Neck ringMild steel seamless tubeIS: 1239 (Part 1)-1979
Cap, Discharge fittings, Drain plugLeaded tin bronze / BrassIS: 318-1981, IS: 319-1974
Discharge nozzle, ApplicatorAluminium alloy / BrassIS: 617-1975, IS: 319-1974
Cap washerRubberIS: 937-1981
Syphon tubeMild steel tube / BrassIS: 3601-1984, IS: 407-1981
HoseBraided rubber/plasticBursting pressure ≥ 50 kgf/cm²

2. Shape and Dimensions (Clause 5.1)

Nominal Capacity (kg)Outside Diameter (mm)Min. Thickness of Shell (mm)
10 - 25175 +10/-5≥ 2
50 - 75≤ 750≥ 3.15
100≤ 750≥ 6
  • Note: Minimum shell thickness ≥ d/100 (d = diameter in mm).

3. Environmental Considerations (Annex A, B, C)

Trade NameOzone Depleting Potential (ODP)Atmospheric Life (Years)Global Warming Potential (GWP)
Halon 130110.0655600
FM 200-413300
FE 13-
2Capacity

IS 11833: Key Formulas, Tables & Specifications for Capacity


1. Capacity of Dry Powder Content (Clause 2.1)

Nominal Capacity (kg)Dry Powder Content (kg, Min)
1010
2525
5050
7575
100100

2. Body Shape & Dimensions (Clause 5.1)

  • Shape: Cylindrical body
  • Outside Diameter & Thickness:
Nominal Capacity (kg)Outside Diameter (mm)Thickness of Shell Material (mm)
10, 25175 +10 / -5Not less than 2
50, 75Not more than 750Not less than 3.15
100Not more than 750Not less than 6
  • Note: Minimum thickness ≥ d/100 (d = diameter in mm) based on bursting formula.

3. Discharge Requirements (Clause 12.1)

  • Minimum discharge: 85% by mass of rated capacity at 27 ± 2℃.
  • Discharge duration:
Capacity (kg)Duration (seconds)
1020 to 30
2530 to 40
5040 to 50
7550 to 60
10070 to 80

4. Additional Specification (Clause 5.6)

  • Drain plug opening ≥ 25 mm diameter (except for 10 & 25 kg capacities).

flowchart TD
    A[Nominal Capacity] --> B[Dry Powder Content]
    B --> C[Body Dimensions]
    C --> D[Thickness ≥ d/100]
    D --> E[Discharge Capacity]
    E --> F[Minimum 85% mass discharge]
    F --> G[Discharge Duration per Capacity]

This summary ensures compliance with

3Materials

IS 11833: Key Materials & Specifications for Fire Extinguisher Construction

Table 1: Materials for Various Components

ComponentMaterial(s)IS Code Reference
BodyMild steel platesIS: 2002-1982, IS: 226-1975
Neck ringMild steel seamless tubeIS: 1239 (Part 1)-1979
CapLeaded tin bronze (Grade LTB-2) or Extruded brass (Type 1)IS: 318-1981, IS: 319-1974
Discharge fittingsLeaded tin bronze or Extruded brassIS: 318-1981, IS: 319-1974
Drain plugLeaded tin bronze, Extruded brass, or MS platesIS: 318-1981, IS: 319-1974, IS: 226-1975
Discharge nozzleAluminium alloy, Extruded brass, or Leaded tin bronzeIS: 617-1975, IS: 319-1974, IS: 318-1981
ApplicatorAluminium alloy/tube, Extruded brass, Leaded tin bronzeIS: 617-1975, IS: 1285-1975, IS: 319-1974, IS: 318-1981
Cap washerRubberIS: 937-1981
Syphon tubeMild steel tube or Brass Alloy No. 2IS: 3601-1984, IS: 407-1981
HoseBraided rubber plastic (burst pressure ≥ 50 kgf/cm²)-

Shell Thickness & Dimensions (Clause 5.1)

Nominal Capacity (kg)Outside Diameter (mm)Min. Shell Thickness (mm)
10175 (+10 / -5)≥ 2
50, 75≤ 750≥ 3.15
100≤ 750≥ 6
  • Note: Minimum thickness ≥ d/100
4Construction

IS 11833: Key Construction Specifications for Fire Extinguishers

1. Materials of Construction (Table 1)

PartMaterialIS Code Reference
BodyMild steel platesIS 2002-1982, IS 226-1975
Neck RingMild steel seamless tubeIS 1239 (Part 1)-1979
CapLeaded tin bronze / BrassIS 318-1981 (Grade LTB-2), IS 319-1974
Discharge FittingsLeaded tin bronze / BrassIS 318-1981, IS 319-1974
Drain PlugLeaded tin bronze / Brass / MSIS 318-1981, IS 319-1974, IS 226-1975
Discharge NozzleAluminium alloy / Brass / BronzeIS 617-1975, IS 319-1974, IS 318-1981
ApplicatorAluminium alloy / Brass / BronzeIS 617-1975, IS 1285-1975, IS 319-1974, IS 318-1981
Cap WasherRubberIS 937-1981
Syphon TubeMild steel tube / BrassIS 3601-1984, IS 407-1981
HoseBraided rubber plasticBursting pressure ≥ 50 kgf/cm²

2. Body Shape and Dimensions (Clause 5.1)

  • Shape: Cylindrical
  • Dimensions:
Nominal Capacity (kg)Outside Diameter (mm)Shell Thickness (mm)
10, 25175 +10/-5Not less than 2
50, 75Not more than 750Not less than 3.15
100Not more than 750Not less than 6
  • Note: Minimum thickness ≥ d/100 (d = diameter in mm).

3. Additional Construction Notes

  • Hose rest must have necessary
5Components and Fittings

IS 11833: Components and Fittings - Key Specifications

1. Materials for Components (Table 1, Clause 4.1.2)

ComponentMaterialIS Specification
BodyMild steel platesIS: 2002-1982, IS: 226-1975
Neck ringMild steel seamless tubeIS: 1239 (Part 1)-1979
CapLeaded tin bronze / Extruded brassIS: 318-1981 / IS: 319-1974
Discharge fittingsLeaded tin bronze / Extruded brassIS: 318-1981 / IS: 319-1974
Drain plugLeaded tin bronze / Brass / MS platesIS: 318-1981 / IS: 319-1974 / IS: 226-1975
Discharge nozzleAluminium alloy / Brass / Leaded tin bronzeIS: 617-1975 / IS: 319-1974 / IS: 318-1981
ApplicatorAluminium alloy / Tube / Brass / Leaded tin bronzeIS: 617-1975 / IS: 1285-1975 / IS: 319-1974 / IS: 318-1981
Cap washerRubberIS: 937-1981
Syphon tubeMild steel tube / BrassIS: 3601-1984 / IS: 407-1981
HoseBraided rubber plastic (burst pressure ≥ 50 kgf/cm²)-

2. Dimensions for Body (Clause 5.1)

Nominal Capacity (kg)Outside Diameter (mm)Min. Thickness (mm)
10, 25175 +10/-5Not less than 2
50, 75Not more than 750Not less than 3.15
100Not more than 750Not less than 6

Note: Minimum thickness ≥ d/100, where d = diameter in mm.

3

6Applicator Requirements

Applicator Requirements (IS 11833)

  • Applicator Design (Clause 8.1):

    • Fitted at hose discharge end via coupling.
    • Extended pipe length: ≥ 1 m.
    • Ends with a dome bell.
    • Equipped with deflecting vanes to sprinkle powder as a low-pressure discharge.
    • Ensures powder spreads uniformly on burning reactive metal.
  • Performance (Clause 12.1):

    • At 27 ± 2℃, still air, extinguisher with applicator must discharge ≥ 85% by mass of rated capacity.
    • Discharge duration based on capacity:
Capacity (kg)Duration (seconds)
1020 - 30
2530 - 40
5040 - 50
7550 - 60
10070 - 80
  • Body Dimensions (Clause 5.1):
Nominal Capacity (kg)Outside Diameter (mm)Shell Thickness (mm)
10, 25175 +10 / -5≥ 2
50, 75, 100≤ 750≥ 3.15 (50,75), ≥ 6 (100)
  • Thickness Note: Minimum thickness ≥ d/100 (d = diameter in mm), considering bursting pressure.
flowchart LR
    Hose -->|Coupling| Applicator
    Applicator -->|Extended pipe ≥1m| DomeBell
    DomeBell -->|Deflecting vanes| PowderSprinkle
    PowderSprinkle --> FireSurface

This ensures efficient, controlled powder discharge to suppress reactive metal fires per IS 11833.

7Anti-corrosive Treatment

IS 11833: Anti-Corrosive Treatment (Clause 9)

Key Specifications:

  • Internal surfaces of the extinguisher body and parts must be coated with:
    • Zinc or
    • Lead-tin alloy (tin ≥ 10%)
  • Coating methods: Hot dipping, electrodeposition, or phosphating.
  • Minimum coating thickness: 0.025 mm.
  • Thickness measurement: As per IS: 3203-1982.

Summary Table for Anti-Corrosive Coating

ParameterRequirement
Coating MaterialZinc or Lead-Tin alloy (Tin ≥ 10%)
Coating MethodHot dipping / Electrodeposition / Phosphating
Minimum Thickness0.025 mm
Thickness MeasurementIS: 3203-1982

Additional Notes

  • Proper anti-corrosive treatment ensures durability and performance of the extinguisher.
  • Zinc coating protects steel by sacrificial action.
  • Lead-tin alloy provides corrosion resistance and good adherence.
  • Phosphating improves paint adhesion if additional coatings are applied.

flowchart LR
    A[Internal Surface] --> B[Coating Application]
    B --> C{Coating Type}
    C -->|Zinc| D[Hot Dipping / Electrodeposition]
    C -->|Lead-Tin Alloy| E[Hot Dipping / Electrodeposition]
    C -->|Phosphating| F[Surface Treatment]
    D & E & F --> G[Minimum Thickness 0.025 mm]
    G --> H[Measurement per IS:3203-1982]

This treatment ensures the extinguisher's internal metal parts resist corrosion, extending service life and safety.

8Performance Requirements and Tests

IS 11833: Performance Requirements & Tests Summary

1. Discharge Requirement (Clause 12.1)

  • Extinguisher must discharge ≥ 85% by mass of rated capacity at 27 ± 2℃, still air.

2. Discharge Duration (Clause 12.1)

Capacity (kg)Duration (seconds)
1020 – 30
2530 – 40
5040 – 50
7550 – 60
10070 – 80

3. Atmospheric Life of Gas-Based Agents (Annex B, Clause 13.2.2)

AgentLife (Years) Atmosphere
Halon-13001<1 day
NAFS III12
FE 2536
FE 2416
FE 36250
FM 20041
Halon 130165
Others- (stable)

4. Global Warming Potential (GWP) (Annex C, Clause 13.2.3)

AgentGWP (100-year CO2 eq.)
Halon 13015600
FE 1312,100
FE 368000
FM 2003300
NAFS III1450
Others-

5. Ozone Depleting Potential (ODP) (Annex A, Clause 13.2.1)

SubstanceODP
Halon 130110.0
Halon 12113.0
CFC-111.0
Methyl Bromide0.6

Key Notes:

  • Extinguishers must ensure steady, low-pressure discharge.
  • Environmental impacts (OD
9Marking and Labeling

IS 11833: Marking and Labeling of Dry Powder Fire Extinguishers for Metal Fires

Clause 13.1: Mandatory Markings on Each Extinguisher

  • Manufacturer's name or trademark
  • Method of operation (prominently displayed)
  • Text: "DRY POWDER EXTINGUISHER FOR METAL FIRE"
  • Capacity in kg
  • Text: "RECHARGE AFTER USE"
  • Pressure test declaration: Body tested to 3.0 MN/m² (30 kgf/cm²)
  • Letter "D" indicating suitability for Class D fires
  • Year of manufacture
  • Working and design pressure

Clause 13.1.1: Optional Marking

  • May include the BIS Standard Mark indicating compliance with IS standards and quality control.

Summary Table of Marking Requirements

Marking ItemDescription/Value
Manufacturer/Trade-markName or logo
Operation methodClear instructions
Fire type"DRY POWDER EXTINGUISHER FOR METAL FIRE"
CapacityIn kilograms (kg)
Recharge note"RECHARGE AFTER USE"
Pressure testTested to 3.0 MN/m² (30 kgf/cm²)
Fire class suitabilityLetter "D"
Manufacture yearYear printed
Working & Design pressureSpecified pressure values

Additional Notes

  • Markings must be clear, permanent, and legible.
  • The Standard Mark use is regulated by BIS under the Bureau of Indian Standards Act 1986.
  • Markings ensure traceability, safety, and compliance.

flowchart TD
    A[Extinguisher Body] --> B[Marking Plate]
    B --> C{Markings}
    C -->|Manufacturer| D[Name/Trademark]
    C -->|Operation| E[Method of Operation]
    C -->|Fire Type| F["DRY POWDER EXTINGUISHER FOR METAL FIRE"]
    C -->|Capacity| G[Capacity in kg]
    C -->|Recharge| H["RECHARGE AFTER USE"]
    C -->|Pressure
10Environmental and Safety Requirements

IS 11833: Environmental & Safety Requirements Summary


1. Ozone Depleting Substances (ODS) - Annex A (Clause 13.2.1)

Trade NameODP (Ozone Depleting Potential)
Halon 130110.0
Halon 12113.0
Halon 24026.0
CFC-111.0
CFC-121.0
Methyl Bromide0.6

High ODP values indicate severe ozone layer impact.


2. Atmospheric Life Time of Gas-Based Agents - Annex B (Clause 13.2.2)

Trade NameDesignationLife Time (Years)
Halon-13001CF 31< 1 day
NAFS IIIHCFC (Blend A)12
FE 25HCFC-12536
FM 200HFC-227 EA41
FE 36HFC-227 fa250
CEA 410FC-3-1-102,600

3. Global Warming Potential (GWP) - Annex C (Clause 13.2.3)

Trade NameGWP (100-year CO2 Equivalent)
Halon 13015,600
FM 2003,300
FE 1312,100
FE 368,000
NAFS III1,450
CF 31< 5

4. Discharge Duration Requirements (Clause 12.1)

Capacity (kg)Duration (seconds)
1020 – 30
2530 – 40
5040 – 50
75
11Packaging

IS 11833 - Packaging: Key Formulas, Tables, and Specifications


1. Shape & Dimensions (Clause 5.1, Table 5)

Nominal Capacity (kg)Outside Diameter (mm)Thickness of Shell (mm)
10 - 25175 +10 / -5≥ 2
50 - 75≤ 750≥ 3.15
100≤ 750≥ 6
  • Note: Minimum thickness ≥ d/100, where d = diameter in mm (accounts for bursting pressure).

2. Material Specifications (Clause 4.1.2, Table 1)

ComponentMaterialIS Code Reference
BodyMild steel platesIS: 2002-1982, IS: 226-1975
Neck ringMild steel seamless tubeIS: 1239 (Part 1)-1979
CapLeaded tin bronze / BrassIS: 318-1981 / IS: 319-1974
Discharge fittingsLeaded tin bronze / BrassIS: 318-1981 / IS: 319-1974
Drain plugLeaded tin bronze / Brass / MSIS: 318-1981 / IS: 319-1974 / IS: 226-1975
Discharge nozzleAluminium alloy / Brass / BronzeIS: 617-1975 / IS: 319-1974 / IS: 318-1981
ApplicatorAluminium alloy / Brass / BronzeIS: 617-1975 / IS: 319-1974 / IS: 318-1981
Cap washerRubberIS: 937-1981
Syphon tubeMild steel tube / BrassIS: 3601-1984 / IS: 407-1981
HoseBraided rubber plasticBursting pressure ≥ 50 kgf/cm²

3. Additional Packaging Requirements

  • **Clause
12Optional ECO Mark Requirements

IS 11833: Optional ECO Mark Requirements Summary

  • ECO Mark Purpose:
    Introduced by the Ministry of Environment and Forests (MEF), the ECO Mark certifies environment-friendly products administered by BIS under the BIS Act, 1986.

  • Eligibility:

    • Product must have the BIS Standard Mark (ISI Mark).
    • Must meet additional optional environmental criteria specified in the relevant standards.
    • ECO Mark is a combined logo: ISI Mark + ECO logo.
  • Clause Highlights:

    • 13.1.1: Any fire extinguisher with BIS Standard Mark qualifies for ECO Mark consideration.
    • 13.1.3: Products may briefly display criteria for ECO Mark award.
  • Key Notes:

    • ECO Mark requirements are optional; manufacturers can opt for ISI Mark alone.
    • Specific environmental criteria are included via amendments in relevant standards.

No explicit formulas or tables are given in IS 11833 for ECO Mark; compliance depends on additional environmental parameters defined per product type.

flowchart LR
  A[Product] --> B{Has BIS ISI Mark?}
  B -- No --> C[No ECO Mark]
  B -- Yes --> D{Meets ECO criteria?}
  D -- No --> E[ISI Mark only]
  D -- Yes --> F[ISI Mark + ECO Mark]

Summary: ECO Mark is an optional environmental certification combined with ISI Mark, requiring compliance with additional eco-friendly criteria per product standards.

13Amendments and Updates

IS 11833: Amendments & Updates Key Points

1. Amendments Overview

  • Amendment No. 1 (March 2002): Added new subclauses (Clause 6).
  • Amendment No. 2 (Sept 2006): Changed clause 13 title from "OPTIONAL" to "ADDITIONAL".
  • Amendment No. 3 (Aug 2007): Further updates in clause 6.

2. Important Tables from Clause 13

TableContentKey Data
Annex A (13.2.1)Ozone Depleting Substances (ODS) & ODP valuesHalon 1301: ODP = 10.0 (highest)
Annex B (13.2.2)Atmospheric Life Time of Gas-Based AgentsFE 36: 250 years; NAFS III: 12 years
Annex C (13.2.3)Global Warming Potential (GWP) vs CO2FE 13: 12,100; FM 200: 3,300; Halon 1301: 5,600

3. Key Specifications

  • ODP (Ozone Depletion Potential): Relative to CFC-11 (ODP=1.0).
  • Life Time: Indicates environmental persistence (years).
  • GWP: 100-year global warming potential compared to CO2.

4. Summary Table Example: ODP Values

Trade NameODP
Halon 130110
Halon 12113
CFC-111
Methyl Bromide0.6

5. Usage Note

  • Use updated values from amendments to select environmentally safer extinguishing agents.
  • Prioritize agents with low ODP and GWP for compliance and sustainability.

flowchart LR
    A[Fire Extinguisher Agents] --> B{Environmental Impact}
    B --> C[Ozone Depletion Potential (ODP)]
    B --> D[Global Warming Potential (GWP)]
   

Popular Questions About IS 11833

?What materials are specified for the construction of dry powder metal fire extinguishers?

Materials specified for Dry Powder Metal Fire Extinguishers (IS 11833):

  • Body & Shell:

    • Mild steel plates (IS: 513 - 1973 for 10 kg capacity)
    • Mild steel seamless tubes (IS: 1239 Part 1 - 1979)
  • Discharge Fittings:

    • Leaded tin bronze, Grade LTB-2 (IS: 318 - 1981)
    • Extruded brass sections, Type I (IS: 319 - 1974)
  • Discharge Nozzle:

    • Aluminium alloy (IS: 407 - 1981 Alloy No. 2)
    • Extruded brass sections (IS: 319 - 1974)
    • Leaded tin bronze, Grade LTB-2 (IS: 318 - 1981)
  • Expellent Gas Cylinder:

    • Mild steel tube (IS: 3601 - 1984)
    • Manganese steel cylinder (IS: 4947 - 1985, IS: 7285 - 1982)
  • Other Components:

    • Braided rubber/plastic hoses with bursting pressure ≥ 50 kgf/cm²
    • Wheeled carriage details per Fig. 1 (MS tube/rod, solid rubber tyre 200×50 mm)

Summary Table

PartMaterial & IS Code
BodyMild steel plates (IS: 513), tubes (IS: 1239)
Discharge fittingsLeaded tin bronze (IS: 318), Brass (IS: 319)
Discharge nozzleAluminium alloy (IS: 407), Brass (IS: 319), Bronze (IS: 318)
Expellent gas cylinderMild steel (IS: 3601), Manganese steel (IS: 4947)
HosesBraided rubber/plastic, bursting pressure ≥ 50 kgf/cm²

This ensures durability, corrosion resistance, and pressure containment suitable for metal fire extinguishers.

?What are the minimum powder content requirements for different extinguisher capacities?

According to IS 11833, the minimum dry powder content for metal fire extinguishers is directly equal to their nominal capacity:

Nominal Capacity (kg)Minimum Dry Powder Content (kg)
1010
2525
5050
7575
100100

Additional Key Points:

  • The extinguisher must discharge at least 85% by mass of the rated capacity (Clause 12.1).
  • Discharge duration varies with capacity, e.g., 10 kg extinguisher discharges in 20-30 seconds, 100 kg in 70-80 seconds.
  • A space above the powder ensures internal pressure does not exceed 1.5 MN/m² (15 kgf/cm²) during operation at 27 ± 2℃ (Clause 7.1).

This ensures safety, performance, and compliance with IS 11833 for metal fire extinguishers.

?How does the applicator design ensure safe and effective powder discharge on metal fires?

According to IS 11833 Clause 8.1, the applicator design ensures safe and effective powder discharge on metal fires by:

  • Using an extended pipe of at least 1 meter to keep the operator at a safe distance from the reactive metal fire.
  • Fitting a dome bell at the pipe end to spread the powder gently over the fire.
  • Incorporating deflecting vanes inside the dome bell to sprinkle the powder uniformly on the burning metal surface.
  • Ensuring a low-pressure discharge to avoid disturbing the reactive metal and causing violent reactions.

This design achieves controlled, uniform powder distribution, minimizing splashing or scattering of burning metal and enhancing fire suppression efficiency while maintaining operator safety.

Loading diagram...
?What environmental restrictions does IS 11833 impose regarding Ozone Depleting Substances and hazardous metals?

IS 11833 imposes strict environmental restrictions as follows:

Ozone Depleting Substances (ODS) - Clause 13.2.1 & Annex A

  • Fire extinguishers shall NOT contain any ODS listed under the Montreal Protocol relevant to the fire extinguisher industry.
  • Examples of banned ODS include:
    SubstanceOzone Depleting Potential (ODP)
    Halon 12113.0
    Halon 130110.0
    CFC-111.0
    Methyl Bromide0.6
    • (Full list in Annex A)

Hazardous Metals in Coatings - Clause 13.2.5

  • Metallic part coatings must NOT contain:
    • Mercury or mercury compounds
    • Pigments of lead, cadmium, chromium VI, and their oxides
  • Exception: Natural impurities ≤ 0.1% by weight in raw materials are allowed.

Additional Notes

  • Chemicals used should have no global warming potential (Clause 13.2.3).
  • CO2 extinguishers allowed temporarily until substitutes are available.

This ensures environmental safety by avoiding substances harmful to the ozone layer and toxic metals in fire extinguisher components.

?What performance tests must a dry powder metal fire extinguisher pass according to this standard?

According to IS 11833, a dry powder metal fire extinguisher must pass the following performance tests:

  • Discharge Test (Clause 12.1):
    The extinguisher, operated with its applicator at 27 ± 2℃ in still air, must discharge at least 85% by mass of its rated capacity.

  • Discharge Duration (Seconds) by Capacity:

    Capacity (kg)Duration (s)
    1020 to 30
    2530 to 40
    5040 to 50
    7550 to 60
    10070 to 80
  • The discharge must be a steady, low-pressure stream.

These ensure the extinguisher delivers sufficient agent effectively for metal fires (Class D).

Loading diagram...

This ensures reliability and effectiveness in metal fire emergencies.