IS 11108-1984 specifies the requirements for portable fire extinguishers using Halon 1211 as the extinguishing agent. It covers design, construction, materials, performance, and testing criteria for extinguishers with capacities ranging from 1.25 to 6.5 kg, ensuring safety and reliability in fire suppression. This standard is essential for manufacturers, safety engineers, and fire safety professionals involved in the production, selection, and maintenance of Halon 1211 type portable fire extinguishers in India.
Overview
IS 11108-1984 specifies the requirements for portable fire extinguishers using Halon 1211 as the extinguishing agent. It covers design, construction, materials, performance, and testing criteria for extinguishers with capacities ranging from 1.25 to 6.5 kg, ensuring safety and reliability in fire suppression. This standard is essential for manufacturers, safety engineers, and fire safety professionals involved in the production, selection, and maintenance of Halon 1211 type portable fire extinguishers in India.
Audience
Contents
Structure
| Component | Material | IS Standard Reference |
|---|---|---|
| Body | Steel (Grade D or DD) | IS 513-1973 |
| Neck ring | Steel | IS 6240-1976* or IS 226-1975 or others |
| Valve body | Leaded tin bronze | Grade LTB-2, IS 318-1957 |
| Nozzle | Extruded brass | Grade I, IS 291-1977 or IS 319-1974 |
| Spring | Steel (plated) | Grade I, IS 4454 (Part 1)-1975 |
| Piercer/spindle | Steel (04 Cr 13) | IS 6528-1972 |
| Siphon tube | Brass copper alloy | Alloy No. 2, IS 407-1981 or IS 1545-1969 |
| Sealing nuts, disc, discharge fitting | Brass | IS 291-1977 or IS 319-1974 |
| Washer | Rubber | IS 937-1981 |
| Sealing disc | Copper | IS 1972-1977 |
| Capacity (kg) | Min. Jet Throw (s) | Max. Discharge Time (s) | Min. Jet Range (m) |
|---|---|---|---|
| 1.25 | 8 | 14 | 2 |
| 2.5 | 8 | 16 | 2 |
| 4 | 10 | 20 | 3 |
| 5 | 12 | 24 | 4 |
| 6.5 | 14 | 28 | 4 |
| Component | Material | Relevant IS Standard(s) |
|---|---|---|
| Body | Steel (Grade D or DD) | IS: 513-1973 |
| Neck ring | Steel | IS: 6240-1976 or IS: 226-1975 or IS: 1875-1978 or IS: 2073-1970 or IS: 4855-1969 |
| Valve body | Leaded tin bronze (LTB-2) | IS: 318-1957 |
| Nozzle | Extruded brass section | IS: 291-1977 Grade I or IS: 319-1974 Type I |
| Spring | Steel (plated) | IS: 4454 (Part 1)-1975 Grade I |
| Piercer/spindle | Steel (04 Cr 13) | IS: 6528-1972 |
| Siphon tube | Brass copper alloy No. 2 | IS: 407-1981 or IS: 1545-1969 |
| Sealing nuts, Piercer disc, Discharge fitting | Extruded brass section | IS: 291-1977 Grade I or IS: 319-1974 Type I |
| Washer | Rubber | IS: 937-1981 |
| Sealing disc | Copper | IS: 1972-1977 |
[ t = \frac{p \times D_o}{200 \times 0.8 \times J \times R_e + p} ]
[ t = \frac{p \times D_o}{200 \times 0.8 \times J \times R_e + p} ]
[ t = \frac{p \times D_o}{200 \times 0.8 \times J \times R_e + p} \times \frac{K(0
IS 11108 - Key Design & Construction Specs
| Component | Material | Relevant IS Standard(s) |
|---|---|---|
| Body | Steel (Grade D or DD) | IS: 513-1973 |
| Neck ring | Steel | IS: 6240-1976, or IS: 226-1975, 1875-1978, 2073-1970, 4855-1969 |
| Valve body | Leaded tin bronze (LTB-2) | IS: 318-1957 |
| Nozzle | Extruded brass | IS: 291-1977, IS: 319-1974 |
| Spring | Plated Steel (Grade I) | IS: 4454 (Part 1)-1975 |
| Piercer/spindle | Steel (04 Cr 13) | IS: 6528-1972 |
| Siphon tube | Brass copper alloy No. 2 | IS: 407-1981, IS: 1545-1969 |
| Sealing nuts, disc, discharge fitting | Extruded brass | IS: 291-1977, IS: 319-1974 |
| Washer | Rubber | IS: 937-1981 |
| Sealing disc | Copper | IS: 1972-1977 |
| Capacity (kg) | Min. Throw Duration (s) | Max. Discharge Time for 95% Content (s) | Min. Jet Range (m) |
|---|---|---|---|
| 1.25 | 8 | 14 | 2 |
| 2.5 | 8 | 16 | 2 |
| 4 | 10 | 20 | 3 |
| 5 | 12 | 24 | 4 |
| 6.5 |
IS 11108 Key Points on Capacity and Filling Ratio
Water Capacity: Max 6.5 liters (Clause 2.1). Extinguishers covered: 1.25, 2.5, 4, 5, and 6.5 kg.
Filling Ratio: Shall not exceed 0.75 (Clause 6.1).
Filling Ratio = (Mass of extinguishing agent) / (Volume of container × Density)
Charging Pressure:
Discharge Test Requirements (Clause 10.5):
| Capacity (kg) | Min. Jet Throw Time (s) | Max. Time to Discharge 95% (s) | Min. Jet Range (m) |
|---|---|---|---|
| 1.25 | 8 | 14 | 2 |
| 2.5 | 8 | 16 | 2 |
| 4 | 10 | 20 | 3 |
| 5 | 12 | 24 | 4 |
| 6.5 | 14 | 28 | 4 |
[ \text{Filling Ratio} = \frac{\text{Mass of extinguishing agent}}{\text{Volume of container} \times \text{Density of agent}} \leq 0.75 ]
This ensures safe and effective filling without over-pressurizing the extinguisher.
flowchart TD
A[Extinguisher Capacity] --> B[Filling Ratio ≤ 0.75]
B --> C[Charging Pressure]
C --> D[Discharge Test]
D --> E[Minimum Jet Time & Range]
This encapsulates the key design and test parameters per IS 11108.
| Component | Material | IS Standard |
|---|---|---|
| Body | Steel (Grade D/DD) | IS: 513-1973 |
| Neck ring | Steel | IS: 6240-1976 or others |
| Valve body | Leaded tin bronze | IS: 318-1957 (Grade LTB-2) |
| Nozzle | Brass | IS: 291-1977, IS: 319-1974 |
| Spring | Steel (plated) | IS: 4454 (Part 1)-1975 |
| Piercer/spindle | Steel (04 Cr 13) | IS: 6528-1972 |
| Siphon tube | Brass copper alloy | IS: 407-1981, IS: 1545-1969 |
| Sealing nuts/disc | Brass/Copper | IS: 291-1977, IS: 1972-1977 |
[ P_{charge} = 9.5 \pm 0.5 , \text{kgf/cm}^2 ]
flowchart TD
A[Extinguisher Body (Cylindrical)] --> B[Filling with Agent (≤
IS 11108: Performance Requirements Summary
| Capacity (kg) | Min. Throw Duration (s) | Max. Discharge Time for 95% (s) | Min. Range of Jet (m) |
|---|---|---|---|
| 1.25 | 8 | 14 | 2 |
| 2.5 | 8 | 16 | 2 |
| 4 | 10 | 20 | 3 |
| 5 | 12 | 24 | 4 |
| 6.5 | 14 | 28 | 4 |
flowchart LR
A[Full Charged Extinguisher] --> B[Discharge Test at 27±5°C]
B --> C{Discharge ≥ 95% of content?}
C -- Yes --> D[Throw duration ≥ Min. Period]
C -- No --> E[Fail Test]
D --> F[Discharge completed ≤ Max. Time]
F --> G[Jet Range ≥ Min. Distance]
G --> H[Pass Performance Test]
This ensures reliable and effective extinguisher performance as per IS 11108.
IS 11108: Testing Procedures Key Points
| Capacity (kg) | Min. Throw Duration (s) | Max. Discharge Time for 95% (s) | Min. Jet Range (m) |
|---|---|---|---|
| 1.25 | 8 | 14 | 2 |
| 2.5 | 8 | 16 | 2 |
| 4 | 10 | 20 | 3 |
| 5 | 12 | 24 | 4 |
| 6.5 | 14 | 28 | 4 |
flowchart LR
A[Sample Selection] --> B[Drop Test (Clause 10.3)]
A --> C[Performance Test (Clause 10.5)]
C --> D{Check Discharge}
D -->|≥95% expelled| E[Pass]
D -->|<95% expelled| F[Fail]
This ensures extinguisher reliability and compliance with IS 11108.
IS 11108: Key Marking & Labeling Specifications
graph TD
A[Extinguisher] --> B[Marking]
B --> C[Fire Class Letters (B & C)]
B --> D[Manufacturer Info]
B --> E[Operational Instructions]
B --> F[Capacity & Pressure]
B --> G[Warnings]
This ensures clear identification, safe use, and regulatory compliance.
IS 11108: Safety Features - Key Specifications & Tables
| Component | Material | IS Standard Reference |
|---|---|---|
| Body | Steel (Grade D or DD) | IS 513-1973 |
| Neck Ring | Steel | IS 6240-1976 or IS 226/1875/2073/4855 |
| Valve Body | Leaded Tin Bronze (LTB-2) | IS 318-1957 |
| Nozzle | Extruded Brass Section | IS 291-1977 or IS 319-1974 |
| Spring | Steel (Plated) | IS 4454 (Part 1)-1975 |
| Piercer/Spindle | Steel (04 Cr 13) | IS 6528-1972 |
| Siphon Tube | Brass Copper Alloy No. 2 | IS 407-1981 / IS 1545-1969 |
| Sealing Nuts/Discs | Extruded Brass Section | IS 291-1977 / IS 319-1974 |
| Washer | Rubber | IS 937-1981 |
| Sealing Disc | Copper | IS 1972-1977 |
| Capacity (kg) | Min. Throw Duration (s) | Max. Discharge Time for 95% Content (s) | Min. Jet Range (m) |
|---|---|---|---|
| 1.25 | 8 | 14 | 2 |
| 2.5 | 8 | 16 | 2 |
| 4 | 10 | 20 | 3 |
| 5 | 12 | 24 | 4 |
| 6.5 | 14 | 28 |
IS 11108: Sampling and Conformity Criteria
| Number of Items in Lot | Sample Size (Number of Samples) |
|---|---|
| Up to 25 | 3 |
| 26 to 50 | 5 |
| 51 to 100 | 8 |
| 101 to 200 | 8% of lot size |
Summary:
Use the above sampling sizes for testing fire extinguisher lots. Ensure random sampling and rigorous quality control to guarantee reliability.
flowchart TD
A[Lot of Fire Extinguishers] --> B{Lot Size?}
B -->|Up to 25| C[Take 3 Samples]
B -->|26 to 50| D[Take 5 Samples]
B -->|51 to 100| E[Take 8 Samples]
B -->|101 to 200| F[Take 8% Samples]
C --> G[Test Samples]
D --> G
E --> G
F --> G
G --> H{Conformity?}
H -->|Yes| I[Accept Lot]
H -->|No| J[Reject Lot]
This ensures reliability and safety compliance per IS 11108.
IS 11108 - Certification and Standard Mark Key Points
| Component | Material | IS Standard Reference |
|---|---|---|
| Body | Steel (Grade D or DD) | IS: 513-1973 |
| Neck ring | Steel | IS: 6240-1976 or IS: 226/1875/2073/4855 |
| Valve body | Leaded tin bronze (LTB-2) | IS: 318-1957 |
| Nozzle | Extruded brass | IS: 291-1977 / IS: 319-1974 |
| Spring | Steel (plated) | IS: 4454 (Part 1)-1975 |
| Piercer/spindle | Steel (04 Cr 13) | IS: 6528-1972 |
| Siphon tube | Brass copper alloy | IS: 407-1981 / IS: 1545-1969 |
| Sealing nuts, disc | Extruded brass | IS: 291-1977 / IS: 319-1974 |
| Washer | Rubber | IS: 937-1981 |
| Sealing disc | Copper | IS: 1972-1977 |
flowchart TD
A[Manufacturer] --> B[Apply for BIS Licence]
B --> C[BIS Review & Testing]
C --> D{Compliance?}
D -- Yes --> E[Grant Licence & Standard Mark Use]
D -- No --> F[Reject Application]
E --> G[Mark Product with
IS 11108 Annexures & References – Key Specifications and Tables
| Component | Material | Relevant IS Standard(s) |
|---|---|---|
| Body | Steel (Grade D or DD) | IS: 513-1986 |
| Neck ring | Steel | IS: 6240-1976, IS: 226-1975, IS: 1875-1978, IS: 2073-1974, IS: 9550-1980 |
| Valve body | Leaded tin bronze | Grade LTB-2, IS: 318-1957 |
| Nozzle | Extruded brass | Grade I IS: 291-1977, Type I IS: 319-1974 |
| Spring | Steel (plated) | Grade I, IS: 454 (Part 1)-1981 |
| Piercer/spindle | Steel | IS: 6528-1972 |
| Siphon tube | Brass copper | Alloy No. 2 IS: 407-1981, IS: 1545-1982 |
| Sealing nuts, disc, discharge fitting | Extruded brass | Grade I IS: 291-1977, Type I IS: 319-1974 |
| Washer | Rubber | IS: 937-1981 |
| Sealing disc | Copper | IS: 1972-1977 |
Frequently Asked
IS 11108 specifies materials for Halon 1211 portable fire extinguishers focusing on durability, corrosion resistance, and safety.
| Component | Material Specification |
|---|---|
| Cylinder | Mild steel / Stainless steel + anti-corrosive treatment |
| Valve & Mechanism | Brass / Stainless steel / Corrosion-resistant alloys |
| Seals & Gaskets | Synthetic rubber / Elastomers compatible with Halon 1211 |
| External Coating | Anti-corrosive paint or powder coating |
This ensures structural integrity and chemical compatibility for safe and effective extinguisher performance.
According to IS 11108 Clause 10.5, the performance requirements for discharge duration and range of fire extinguishers are:
| Capacity (kg) | Min. Jet Throw Duration (s) | Max. Discharge Time for 95% Content (s) | Min. Range of Jet Throw (m) |
|---|---|---|---|
| 1.25 | 8 | 14 | 2 |
| 2.5 | 8 | 16 | 2 |
| 4 | 10 | 20 | 3 |
| 5 | 12 | 24 | 4 |
| 6.5 | 14 | 28 | 4 |
Key points:
This ensures effective and sustained discharge during firefighting.
Pressurization of Extinguishers (IS 11108):
Gas Used: Extinguishers are pressurized with dry nitrogen (Clause 5.11, IS:1747-1972).
Pressure Levels:
Pressure Gauge:
| Capacity | Hydrostatic Test Pressure | Duration | Pressurizing Gas |
|---|---|---|---|
| 1.25 kg | 2.5 MN/m² (25 kgf/cm²) | 30 seconds | Dry Nitrogen |
| Above 1.25 kg | 3 MN/m² (30 kgf/cm²) | 30 seconds | Dry Nitrogen |
Loading diagram...
This ensures safe operation and reliable pressure maintenance in fire extinguishers per IS 11108.
According to IS 11108, fire extinguishers must pass the following key tests to ensure safety and reliability:
| Capacity (kg) | Min Throw Duration (s) | Max Discharge Time (s) | Min Range (m) |
|---|---|---|---|
| 1.25 | 8 | 14 | 2 |
| 2.5 | 8 | 16 | 2 |
| 4 | 10 | 20 | 3 |
| 5 | 12 | 24 | 4 |
| 6.5 | 14 | 28 | 4 |
These tests ensure structural integrity, leak tightness, and effective discharge performance under normal conditions.
According to IS 11108, the mandatory markings and labels on a Halon 1211 fire extinguisher are:
These ensure clear identification, safe handling, and compliance with fire safety standards.
Loading diagram...
This labeling ensures compliance and user safety.