The standard IS 4878:1986 outlines detailed regulations governing the planning, construction, and upkeep of cinema buildings across India. It encompasses safety measures, fire prevention, structural design criteria, ventilation systems, electrical setups, and sanitation to ensure secure and well-organized cinema facilities. This code is crucial for architects, engineers, municipal bodies, and cinema proprietors involved in cinema development and approval processes.
Overview
The standard IS 4878:1986 outlines detailed regulations governing the planning, construction, and upkeep of cinema buildings across India. It encompasses safety measures, fire prevention, structural design criteria, ventilation systems, electrical setups, and sanitation to ensure secure and well-organized cinema facilities. This code is crucial for architects, engineers, municipal bodies, and cinema proprietors involved in cinema development and approval processes.
Audience
Contents
Structure
Clause 1: This standard specifies design, construction, and safety requirements applicable to both permanent and semi-permanent cinema buildings.
| Sheet Size | Trimmed (mm) | Untrimmed (mm) |
|---|---|---|
| A0 | 841 × 1189 | 880 × 1230 |
| A1 | 594 × 841 | 625 × 880 |
| A2 | 420 × 594 | 450 × 625 |
| A3 | 297 × 420 | 330 × 450 |
| A4 | 210 × 297 | 240 × 330 |
| A5 | 148 × 210 | 165 × 240 |
flowchart LR
A[Initiate Cinema Building Design] --> B[Prepare Plans & Specs]
B --> C{Are Material Specs Included?}
C -- Yes --> D[Sign by Licensed Architect/Engineer]
D --> E[Submit Notice & Documents]
C -- No --> F[Revise Specifications]
E --> G[Submit HVAC Plans if Needed]
G --> H[Authority Reviews]
H --> I[Construction Approval]
Summary of Key Definitions in IS 4878
| Parameter | Requirement |
|---|---|
| Material Details | Clearly specified with type and grade |
| Professional Signoff | Must be signed by licensed architect/engineer |
| Submission | Provided to authority as required |
Always consult Appendix D for detailed specification formats to ensure full compliance.
flowchart LR
A[Design Stage] --> B[Prepare Specs]
B --> C{Include Material Type & Grade?}
C -- Yes --> D[Sign by Licensed Architect/Engineer]
D --> E[Submit with Construction Notice]
E --> F[Authority Approval]
IS 4878: Administrative Procedures and Permit Requirements
| Appendix | Purpose | Page |
|---|---|---|
| A | Notice for Cinema Building Construction | 63 |
| B | Request for No Objection Certificate | 64 |
| C | No Objection Certificate (NOC) | 65 |
| D | Application for Cinema Building License | 66 |
| E | Supervision Form | 67 |
| F | Licensed Architect/Engineer Qualifications | 68 |
| G | Permit Sanction or Refusal Form | 69 |
| H | Commencement Notice Form | 70 |
| J | Completion Certificate Form | 71 |
| K | Occupancy Certificate Form | 72 |
| L | Off-Street Parking Regulations | 73 |
flowchart TD
A[Submit Construction Notice (Appx A)] --> B[Provide Specifications (Clause 3.7.2.5)]
B --> C[Apply for Permit/License (Appx D)]
C --> D[Permit Granted or Denied (Appx G)]
D -->|If Approved| E[Notify Commencement (Appx H)]
E --> F[Supervision & Compliance (Appx E)]
F --> G[Completion Certificate Issued (Appx J)]
G --> H[Occupancy Certificate Granted (Appx K)]
IS 4878 Regulations on Off-Street Parking (Appendix L & Clause 8.1)
| Vehicle Type | Parking Bay Size (m) | Notes |
|---|---|---|
| Four-wheeler | 2.5 × 5.0 | Standard car parking bay |
| Two-wheeler | 1.0 × 2.0 | Motorcycle and scooter bays |
| Driveway Width | Minimum 3.0 m | Allows two-way vehicle flow |
[ \text{Total Parking Area} = N \times (L \times W) + \text{Driveway Area} ] Where:
flowchart LR
A[Entrance/Exit Point] --> B[Driveway (≥3m wide)]
B --> C[Designated Parking Bays]
C --> D[Vehicle Parking]
Summary of Height Limitations in IS 4878
| Street Width (m) | Maximum Height (m) | Remarks |
|---|---|---|
| Less than 5 | As per local rules | More stringent limits |
| 5 to less than 6.7 | Up to 6.7 m | Moderate height allowed |
| 6.7 or more | 6.7 m or above | Permitted for taller structures |
[ \text{FAR} = \frac{\text{Total floor area across all levels}}{\text{Plot area}} ]
Building height and storeys are controlled to maintain FAR within permissible limits.
flowchart TD
A[Plot with Adjacent Street Width] --> B{Street Width}
B -->|<5m| C[Low Height Restriction]
B -->|5m to <6.7m| D[Medium Height Restriction (≤6.7m)]
B -->|≥6.7m| E[Higher Height Allowed]
E --> F[Check FAR and Open Space]
F --> G[Approve Building Height]
IS 4878: Specifications for Building Components and Facilities
| Item | Information Needed |
|---|---|
| Building & Ownership Info | Name, type, location, owner details |
| Orientation | Indicate North direction |
| Room Characteristics | Dimensions, height, usage |
| Structural Details | Wall, roof, floor, window construction, insulation, finishes |
| HVAC Equipment Layout | Cooling towers, ducts, air distribution system |
| Equipment Specifics | Refrigeration, heating plants, air handling units |
| Dampers | Type and installation locations |
| Chimneys and Vents | Size and placement |
| Internal Loads | People, electrical and mechanical devices |
| Fire Separations | Location and fire resistance grades |
flowchart TD
A[Building & Owner Info] --> B[Room Details & Use]
B --> C[Construction Details]
C --> D[HVAC Plant Layout]
D --> E[Airflow & Dampers]
E --> F[Load Calculations & Fire Separation]
F --> G[Submit for Approval]
IS 4878: Guidelines on Access and Exit Provisions
| Access Length (m) | Minimum Width (m) |
|---|---|
| Up to 200 | 12.0 |
| Up to 400 | 15.0 |
| Up to 600 | 18.0 |
| Over 600 | 24.0 |
flowchart LR
A[Determine Occupant Load] --> B[Calculate Exit Width]
B --> C{Access Length}
C -->|≤200m| D[Width = 12m]
C -->|≤400m| E[Width = 15m]
C -->|≤600m| F[Width = 18m]
C -->|>600m| G[Width = 24m]
D & E & F & G --> H[Compare with Internal Access Width]
H --> I[Establish Final Access Width]
IS 4878: Specifications for Seating and Lifts
| Parameter | Minimum Value |
|---|---|
| Seat Width (min) | 45 cm |
| Seat Width (avg.) | 50 cm |
| Legroom | 30.5 cm |
flowchart TD
A[Design Seating] --> B[Ensure Seat Width ≥ 45 cm]
A --> C[Maintain Average Seat Width ≥ 50 cm]
A --> D[Provide Legroom ≥ 30.5 cm]
E[Provide Lifts] --> F[Capacity per Occupant Load]
E --> G[Minimum Car Size]
E --> H[Accessibility Compliance]
IS 4878 Electrical Installation Guidelines
When designing electrical systems, consider:
| Factor | Consideration |
|---|---|
| Supply & Load | Type, earthing, occupancy |
| Environment | Temperature, moisture, explosive presence |
| Protection | Electrical and mechanical safeguards |
| Continuity | Standby supply and critical load management |
| Future-proofing | Potential modifications and expansions |
| Cost | Operational and maintenance expenses |
| Interference | Radio and telecom suppression |
| Maintenance | Access and ease of upkeep |
| Safety | Compliance with safety standards |
| Energy Efficiency | Conservation practices |
For detailed calculations like load analysis and cable sizing, consult SP:7-1983 and IS codes such as IS 732 (wiring) and IS 3043 (earthing).
flowchart LR
A[Begin Electrical Design] --> B[Assess Supply & Load]
B --> C[Evaluate Environmental Factors]
C --> D[Define Protection Levels]
D --> E[Plan for Continuity & Backup]
E --> F[Consider Future Extensions]
F --> G[Analyze Costs & Interference]
G --> H[Implement Safety & Energy Conservation]
H --> I[Refer to SP:7-1983]
I --> J[Finalize Electrical Design]
IS 4878 Fire Protection Overview
| Component Type | Fire Resistance (hours) |
|---|---|
| Load-bearing RCC | 2 to 4 |
| Load-bearing Brick | 1 to 2 |
| Non-load-bearing walls | 1 |
| Protected Steel Members | 2 to 3 |
flowchart LR
A[Fire Safety] --> B[Fire Resistance Ratings]
A --> C[Installed Fire Fighting Systems]
A --> D[Audio-Visual Fire Alarms]
B --> E[Structural Elements]
B --> F[Non-Structural Elements]
C --> G[Sprinkler Systems]
C --> H[Fire Hydrants]
C --> I[Portable Extinguishers]
D --> J[Alarm Systems per SP:30-1984]
IS 4878 Water Supply and Sanitation Guidelines
| Parameter | Typical Values / Notes |
|---|---|
| Water Demand | 135-150 liters per capita per day (domestic) |
| Drainage Pipe Slope | Between 1:40 and 1:60 depending on diameter |
| Minimum Pipe Diameter | 15 mm for water supply; 100 mm for soil drainage |
| Trap Seal Depth | At least 75 mm to prevent sewer gas ingress |
| Vent Pipe Diameter | Minimum 50 mm |
flowchart TD
A[Water Supply Design] --> B[Calculate Demand]
B --> C[Select Pipe Sizes]
C --> D[Distribution Network]
A --> E[Storage Provisions]
F[Drainage Design] --> G[Trap & Vent Systems]
G --> H[Pipe Slopes & Diameters]
H --> I[Sewage Disposal]
IS 4878 Maintenance and Cleanliness Requirements (Clause 17.5)
| Fresh Air Required (m³/min per occupant) | Smoking Area | Non-Smoking Area |
|---|---|---|
| 0.42 | Yes | 0.28 |
| 0.21 | No | 0.14 |
flowchart TD
A[Maintenance Tasks] --> B[Maintain Windows & Vents]
A --> C[Sanitary Upkeep & Waste Removal]
A --> D[Periodic Hot Lime Washing]
A --> E[Clean Electrical Devices]
A --> F[Inspect Mechanical Systems]
A --> G[Check Fire Fighting Equipment]
A --> H[Clean Storage Tanks]
IS 4878: Guidelines on Semi-Permanent Cinema Buildings
| Feature | Requirements |
|---|---|
| Side Wall Height | 1.0 m plastered masonry |
| Wall Covering | Black canvas or tarpaulin curtains |
| Construction Material | Non-flammable materials |
| Safety & Services | Equivalent to permanent cinema norms |
flowchart TD
A[Semi-Permanent Cinema] --> B[1.0 m Plastered Walls]
A --> C[Canvas/Tarpaulin Cover]
A --> D[Use Non-Combustible Materials]
A --> E[Apply Permanent Cinema Safety & Service Standards]
E --> F[Manage Traffic & Parking]
E --> G[Implement Fire Safety]
E --> H[Ensure Water & Drainage]
IS 4878: Occupancy Certificate Form Details (Appendix K)
This certificate confirms that the cinema building is fit for occupancy, conforming to all relevant safety and regulatory byelaws.
I hereby certify that the erection or material alteration of the cinema building located on plot No. ___, street/road ___, colony/bazar ___, supervised by licensed architect/engineer License No. ___, has been inspected and found to comply with all relevant byelaws regarding structural safety, fire protection, hygiene, and sanitation, and is hereby declared fit for occupation.
Signed,
[Authority Signature]
Issued by licensing or local authority after satisfactory inspection.
flowchart TD
A[Construction Completed] --> B[Supervised by Licensed Architect/Engineer]
B --> C[Completion Certificate Issued (Appendix J)]
C --> D[Inspection by Licensing Authority]
D --> E[Occupancy Certificate Issued (Appendix K)]
E --> F[Building Ready for Use]
Frequently Asked
IS 4878 mandates that projection rooms must be enclosed within a fire-resistant fixed compartment known as the 'Projection Room' (Clause 15.14.8). There should be no direct communication with the auditorium, and the room must contain only the cinematograph apparatus, necessary fire-fighting equipment, and controls (15.14.8.1). Access requires one entrance and one alternative exit opening directly to the open air, with self-closing, outward-opening doors made of fire-resistant materials to prevent smoke ingress into the auditorium (15.14.8.2). Additionally, front openings must be fitted with non-combustible shutters that can be closed from near the projector and outside the room, capable of simultaneous closure, and fit tightly to prevent fire and smoke spread (15.14.8.5). These shutters and closing mechanisms must be tested daily before public admission to ensure functionality.
The standard regulates exit widths by defining a unit width of 50 cm (Clause 10.3.2.1), where widths below 25 cm are disregarded and 25 cm counts as half a unit. Occupant capacity per unit width varies by exit type: stairways accommodate 40 persons per 50 cm, ramps 50 persons, and doors or corridors 60 persons (Clause 10.3.2.2). Exit corridors must be at least as wide as the combined width of all exit doorways leading outside to ensure smooth egress (Clause 10.6.1). This system guarantees that exit widths correspond proportionally to the occupant load, facilitating timely and safe evacuation without bottlenecks.
IS 4878 specifies that interior staircases should be made entirely from non-combustible materials to enhance fire safety (Clause 10.7.1). The staircase must be a fully enclosed, self-contained unit with one side formed by an external wall to prevent fire and smoke spread (Clause 10.7.2). Furthermore, staircases should not be arranged around lift shafts unless the lift shaft is fully enclosed with materials having a fire-resistance rating equivalent to the building's classification (Clause 10.7.3). These provisions ensure that stairways serve as safe evacuation routes protected against fire hazards.
For large auditoriums, IS 4878 and NBC 1983 recommend natural ventilation combined with adequately sized and suitably located power-driven exhaust fans for non-air-conditioned halls, targeting 6 to 9 air changes per hour (Clauses 13.1.3 and 13.1.4). For air-conditioned auditoriums, fresh air supply must be provided according to occupancy and smoking status (Clause 13.2.6): 0.21 m³/min per person for non-smoking areas and 0.42 m³/min per person where some smoking occurs. The fresh air supply must be calculated based on the number of occupants and the enclosure’s cubic volume to maintain air quality and occupant comfort.
Semi-permanent cinema buildings, as defined in Clause 2.48 of IS 4878, are structures built with non-combustible materials featuring approximately 1.0 m high plastered side walls topped with durable black canvas or tarpaulin curtains to block light and rain. Most provisions applicable to permanent cinema buildings, covering clauses on design, safety, and services (with specified exceptions), apply with necessary modifications (mutatis mutandis) to semi-permanent structures (Clause 19.2). Administrative requirements, such as detailed building plans, may be relaxed by authorities provided safety is not compromised. Load calculations and fire safety measures should follow guidelines for permanent buildings or relevant Indian Standards like IS 875 and IS 1641. Adequate drainage and ventilation must also be ensured to prevent moisture and heat buildup.
Ask AI about any clause, requirement, or provision in IS 4878. Get instant, clause-cited responses powered by our indexed library.